ATC1510 Advanced Terminal Unit Controller

Installation Guide

About This Product

The Advanced Terminal Unit Controller (ATC) runs

custom, freely-programmed applications, and provides

the inputs and outputs required to monitor and control

a wide variety of HVAC/R equipment.
The ATCs operate as BACnet

®

 Application Specific

Controllers (B-ASC) and integrate into Johnson

Controls

®

 and third-party BACnet systems.

Communication Protocols

You can configure the field bus communication

protocol in the ATC as a standard BACnet MS/TP device

or an N2 protocol device. You can use the Controller

Configuration Tool (CCT) to switch the communication

protocol. Switchable communication protocols provide

a cost-effective upgrade and modernization path for

customers with existing N2 controllers.

Compliance Information

This equipment has been tested and found to comply

with the limits for a Class A digital device pursuant to

Part 15 of the FCC Rules. These limits are designed

to provide reasonable protection against harmful

interference when this equipment is operated

in a commercial environment. This equipment

generates, uses, and can radiate radio frequency

energy and, if not installed and used in accordance

with the instruction manual, may cause harmful

interference to radio communications. Operation

of this equipment in a residential area may cause

harmful interference, in which case the users will

be required to correct the interference at their own

expense.

This Class (A) digital apparatus meets all the

requirements of the Canadian Interference-Causing

Equipment Regulations.

Installation

Observe the following guidelines when installing an

ATC:
• To minimize vibration and shock damage to the

controller, transport the controller in the original

container.

• Verify that all parts shipped with the controller.
• Do not drop the controller or subject it to physical

shock.

Parts Included

• One Advanced Terminal Unit Controller
• One installation instruction guide
• 10 cable ties
• One multi-language warning sheet

Accessories

Table 1: Accessories

Product Code Number

Description

LC-IP20

IP20 Terminal Cover Kit

Required Materials and Special Tools

• Three fasteners appropriate for the mounting

surface (M4 screws or #8 screws)

• One 20 cm (8 in.), or longer, piece of 35 mm DIN rail

and the appropriate hardware for DIN rail mount

• Small straight-blade screwdriver to secure the wires

in the terminal blocks

*241014302015—*

24-10143-02015 Rev —

2019-05-20

(barcode for factory use only)

LC-ATC1510-0

Summary of Contents for ATC1510

Page 1: ...dio frequency energy and if not installed and used in accordance with the instruction manual may cause harmful interference to radio communications Operation of this equipment in a residential area ma...

Page 2: ...the back of the controller extend the two mounting clips as illustrated 3 Position the controller so that the two extended mounting clips are facing downwards and place the controller on the DIN rail...

Page 3: ...fa on incor recte risquent d endommager irr m diablement l quipement 1 Wire the FC Bus Terminal Block The ATC features a blue removable 4 terminal FC Bus block that fits into a board mounted jack Wire...

Page 4: ...450 ft and the wire cross sectional area is 1 5 mm 2 16 AWG to 0 5 mm 2 22 AWG Input and Output wiring guidelines Table 2 and Table 3 provide information and guidelines about the functions ratings an...

Page 5: ...Accumulator Mode 0 01 second minimum pulse width 50 Hz at 50 duty cycle Internal 18 V 3k ohm pull up BINARY Inputs ICOMn Binary Input Common for all Binary Input IN terminals Note All Binary ICOMn ter...

Page 6: ...240 VAC 0 66FLA 4LRA 50k cycles BINARY RELAY 5A Output OCOMn Binary Relay Output Common for OUTn terminal Note Each Binary Relay Output Common terminal OCOMn is isolated from all other commons includi...

Page 7: ...wire 137 m 450 ft twisted wire 0 5 mm 2 22 AWG stranded copper 183 m 600 ft twisted wire 91 m 300 ft twisted wire B 0 25 mm 2 24 AWG stranded copper 107 m 350 ft twisted wire 61 m 200 ft twisted wire...

Page 8: ...s COM Signal Reference Common for Bus communications FC BUS 2 SHIELD Isolated terminal optional shield drain connection 0 5 mm 2 22 AWG stranded 3 wire twisted shielded cable recommended SA Bus Commun...

Page 9: ...le termination diagrams Table 5 Termination diagrams Type of Field Device Type of Input Output Termination Diagrams Temperature Sensor UI Voltage Input External Source UI Voltage Input Self Powered UI...

Page 10: ...t Output CO 24 VAC Triac Output Switch Low External Source CO Incremental Control to Actuator Switch Low Externally Sourced Triac Jumpers where applicable BO 24 VAC Binary Output Switch Low Externally...

Page 11: ...he TE 700 and TE 6x00 Series Sensors is not usable as a zone bus or an SAB connection Network Stat with Terminals Addressable SA Bus Network Stat with Terminals Fixed Address 199 SA Bus The following...

Page 12: ...rs Accessory Kit all wiring must be secured to the stress brackets as illustrated below The following procedure describes how to install the IP20 Covers Accessory Kit to the ATC 1 Attach the IP20 cove...

Page 13: ...ential device address for each of the equipment controllers connected on the FC or SA Bus 2 To ensure the best bus performance set sequential device addresses with no gaps in the device address range...

Page 14: ...commission the controller but you cannot use the Bluetooth connection to Transfer to Device Download The MAP Gateway serves as a replacement for the BTCVT which is no longer available for purchase but...

Page 15: ...d required if controller is in Boot mode Blink 2 Hz Download or Startup in progress not ready for normal operation Rapid blink SA Bus communications issue SA BUS Green Blink 2 Hz Blink 2 Hz Data Trans...

Page 16: ...ical Features The following section describes the physical features of the ATC Figure 6 Advanced Terminal Unit Controller Physical Features ATC1510 Advanced Terminal Unit Controller Installation Guide...

Page 17: ...outputs C 24 VAC out D 5 A relay outputs E DIN clips F Triac outputs G 10 A relay output H 240 VAC power input I FC Bus J FC Bus EOL switch K SA Bus L SA Bus RJ12 M USB N Universal inputs O Binary inp...

Page 18: ...and not valid field controller addresses N2 Valid field controller device addresses 1 to 254 Device address 255 is reserved for the broadcast address and not a valid field controller address Communica...

Page 19: ...d common terminal between all 5A ROs Binary Output Triac BO 24 VAC or 240 VAC 500 mA Resistive Externally powered Shared common terminal between all BO Triacs 10 A Relay Output 10A RO K8 Single Pole S...

Page 20: ...E VOLTAGE 4000 V Ball Pressure temperature 90 C BINARY RELAY Outputs Reference all relay commons to the same pole of the supply circuit BINARY Triacs Outputs Reference all triac commons to the same po...

Reviews: