To hold the snow protection hood properly to the outdoor unit against a strong wind or an earthquake, safety
wire rope should be used for reinforced installation. Use the
fi
eld-supplied safety wire rope to prevent the
outdoor unit from overturning.
●
Install the snow protection hood so as to avoid facing directly toward seasonal or strong winds.
●
Apply touch-up coating or caulking (
fi
eld-supplied) at the screw holes of the outdoor unit in order to
prevent rusting.
●
Even though the hood is stainless, salt or iron may cause rust. Be aware of this during installation or
maintenance.
●
The snow protection hood is heavy-weight. More than two people are required for installation. Be sure
to wear protective equipment (such as gloves).
●
The screws and the snow protection hood must be protected from scratches or scrapes. If they aren’t,
it may be the cause of rusting. Handle with care when the snow protection hood is installed and
assembled.
3. Selection of Installation Location
(1) Install the outdoor unit at the suitable height with consideration for snow accumulation. Increase the
base height or additionally provide the frame under the unit (higher than snow accumulation), and
fi
x
the outdoor unit securely with anchor bolts.
(2) Secure enough service space with consideration for snow accumulation height and snow removal
operation.
(3) There must be no obstacles in the air discharge direction.
(4) Be sure to apply touch-up coating or caulking agent at the screw attaching portions for rustproo
fi
ng.
(5) In case of multiple outdoor units installation, provide the service space as shown below.
< Service Space for Multiple Outdoor Units Installation >
< Caulking Procedures (Example) >
1
2
Caulking Agent
(field-supplied)
(field-supplied)
Fill the screw hole
with caulking agent.
Preparation Articles
Caulking Agent (with high viscosity)
(Recommended Product: SHINETSU Silicon KE45RTV (transparent type),
Cloth (for wiping off surplus caulking agent)
Screw into the hole filled with
caulking agent.
* Wipe off any excess agent
with a cloth.
Screw
(accessories)
Caulking Agent
Hood for Left Side Air Inlet
(Other Snow Protection
Hood Option)
Outdoor Units
Min. 2 inch (50mm)
Min. 2 inch (50mm)
Hood for Right Side Air Inlet
(Other Snow Protection Hood Option)
If no air inlet hood is provided
between outdoor units,
2 inches (50mm) or more space
is required for servicing.