background image

 

Electrical Ratings 

 A28AA* 

A19BAC 

Volts, 

AC 

120 208 240 277 120  208 240  277 

Full Load Amp 

16.0 

9.2 8.0 --  16.0 9.2 8.0  -- 

Locked Rotor Amp 

96.0 55.2 48.0 -- 

96.0  55.2 48.0  -- 

Non-Inductive Amp 

 

 

16.0 

9.2 8.0 7.2 16.0 16.0 

16.0 16.0 

 SPDT 

 SPST 

16.0 

9.2 8.0 7.2 22.0 22.0 

22.0 22.0 

Pilot Duty 

125 VA, 24 to 277 VAC 

125VA, 24 to 600 VAC 

* Max connected load not to exceed 2000 VA. 

 

*Disconnecting means and overload protection as required. 

Fig. 4 – A19BAC typical heating control circuit. 

 

Fig. 5 – A19BAC typical ventilating or cooling control circuit. 

 

 

Fig. 6 – Switch action of the A28AA two-stage control. 

RB

H

, RY

H

 indicate HI-TEMP. RB

L

, RY

L

 indicate LO-TEMP. D 

is the differential between stages. 