Johnson Controls 2951J Installation And Maintenance Instructions Download Page 2

J200-07-00                                                                                                      2                                                                                                  I56-1930-02R

© 2003 Johnson Controls

      This sensor can be functionally tested with a test magnet. The test magnet elec-

tronically simulates smoke in the sensing chamber, testing the sensor electronics 

and connections to the control panel.

      1. Hold the test magnet in the magnet test area as shown.

      2. The sensor should alarm the panel.

      Two  LEDs  on  the  sensor  are  controlled  by  the  panel  to  indicate  sensor  status. 

Coded signals, transmitted from the panel, can cause the LEDs to blink, latch on, 

or  latch  off.  Refer  to  the  control  panel  technical  documentation  for  sensor  LED 

status operation and expected delay to alarm.

B.  Smoke Entry: Aerosol Generator

 

      For  2951TMJ,  smoke  entry  testing  should  be  performed  immediately  following 

the  magnet  test.  Magnet  test  initiates  an  approximately  10  minute  period  when 

the detector’s signal processing software routines are not active. Failure to first 

perform the magnet test will introduce a time delay before the detector alarms.

      The  GEMINI  model  501  aerosol  generator  can  be  used  for  smoke  entry  test-

ing. Set the generator to represent 4%ft to 5%ft obscuration as described in the 

GEMINI  501  manual.  Using  the  bowl-shaped  applicator,  apply  aerosol  until  the 

panel alarms.

C.  Direct  Heat  Method  (Hair  dryer  of  1000-1500  watts).  2951TJ  and  2951TMJ 

only.

      Direct the heat toward either of the side thermistors. Hold the heat source about 

12 inches from the detector in order to avoid damage to the plastic. The detector 

will reset only after it has had sufficient time to cool.

Both smoke and heat detection testing are recommended for verifying system protec-

tion capability.

A  sensor  that  fails  any  of  these  tests  should  be  cleaned  as  described  under 

CLEANING

, and retested. If the sensor fails after cleaning, it must be replaced and 

returned for repair. When testing is complete, restore the system to normal operation 

and notify the proper authorities that the system is back in operation.

HIGH SENSITIVITY SETTING

The use of the 0.2% to 0.5% per foot sensitivity setting requires a 90 day test period 

to  ensure  that  the  detector’s  environment  is  suitable  for  this  setting.  The  following 

steps must be followed to meet Johnson Controls and UL requirements for this high 

sensitivity application:

1.   Each  detector  intended  for  0.2%  to  0.5%  per  foot  alarm  application  shall  have 

its  initial  alarm  setting  set  for  0.5%  obscuration  per  foot  alarm  level.  The  initial 

pre alarm setting for the detector shall be set to the intended alarm setting of the 

system. Pre alarm shall be set for non latching operation.

2.   Detectors set at 0.2% to 0.5% per foot are intended for use in smoke-free, envi-

ronmentally  controlled  applications,  such  as  computer  rooms  and  clean  rooms. 

In order to determine if an environment is suitable for installation, the detectors 

shall be operated continuously for 90 days with all environmental factors, including 

temperature, humidity, air flow, occupancy, etc., similar to the intended application 

for these detectors. An electronic history file or printer shall be used to record all 

events associated with the detectors under testing.

3.   At the end of 90 days, the results of the test shall be inspected by an authorized 

Johnson  Controls  representative  or  the  end  user,  if  trained  by  an  authorized 

Johnson Controls representative. If no alarms or pre alarms are recorded for the 

detectors under testing, the system may be set to the tested pre alarm level in the 

0.2% to 0.5% per foot range.

CLEANING

Before removing the detector, notify the proper authorities that the smoke detector system is undergoing maintenance and will be temporarily out of service. 

Disable the zone or system undergoing maintenance to prevent unwanted alarms.
1.   Remove the sensor to be cleaned from the system.

2.   Remove the sensor cover by pressing firmly on each of the four removal tabs that hold the cover in place.

3.   Vacuum the screen carefully without removing it. If further cleaning is required continue with Step 4, otherwise skip to Step 7.

4.   Remove the chamber cover/screen assembly by pulling it straight out.

5.   Use a vacuum cleaner or clean, compressed air to remove dust and debris from the sensing chamber.

6.   Reinstall the chamber cover/screen assembly by sliding the edge over the sensing chamber. Turn until it is firmly in place.

7.   Replace the cover using the LEDs to align the cover and then gently pushing it until it locks into place. Make sure that the thermistors do not become bent 

under the cover on the 2951TJ and 2951TMJ.

9.   Reinstall the detector.

10. Test the detector as described in TESTING.

11. Reconnect disabled circuits.

12. Notify the proper authorities that the system is back on line.

Please refer to insert for the Limitations of Fire Alarm Systems

FCC Statement

This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) 

this device must accept any interference received, including interference that may cause undesired operation.

Note: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to 

provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, 

if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interfer-

encewill not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by 

turning the equipment off and on,  the user is encouraged to try to correct the interference by one or more of the following measures:

                   – Reorient or relocate the receiving antenna.

                   – Increase the separation between the equipment and receiver.

                   – Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.

                   – Consult the dealer or an experienced radio/TV technician for help.

LED Status

Indicators

Magnet Test

Marker

Test Magnet 

Position

Test Magnet 

Position

Magnet Test

Marker

Cover

Removal Tabs

Sensing

Chamber

Sensing

Chamber

Cover and

Screen

Sensor

Cover

Optional
Thermistors
(2951TJ and
2951TMJ)

Figure 3.

C0119-00

Figure 4.

C0163-00

Reviews: