2951J, 2951TJ and 2951TMJ Intelligent Photoelectric Smoke Sensors

Installation and Maintenance Instructions

This sensor must be installed in compliance with the control panel system installation manual. The installation must meet the requirements of the Authority 
Having Jurisdiction (AHJ). Sensors offer maximum performance when installed in compliance with the National Fire Protection Association (NFPA); see NFPA 
72. 

GENERAL DESCRIPTION

Model  2951J,  2951TJ  and  2951TMJ  are  intelligent  sensors  that  combine  a  state-of-the-art  photoelectronic  sensing  chamber  with  communications.  Models 
2951TMJ and 2951TJ combines a photoelectronic sensing chamber and 135°F (57.2°C) fixed temperature heat detector. These sensors are designed to provide 
open area protection and are intended for use with compatible control panels only.
Two LEDs on each sensor light to provide a local, visible sensor indication. Remote LED annunciator capability is available as an optional accessory (Part No. 
RA400Z). The sensor will support either FlashScan™ or CLIP (Classic Loop Interface Protocol) SLC communication mode.
Johnson Controls panels offer different feature sets across different models. As a result, certain features of the 2951J, 2951TJ or 2951TMJ may be available on 
some control panels, but not on others. The possible features available in the 2951J, 2951TJ and 2951TMJ, if supported by the control unit are:
1. The panel controls the LED operation on the sensor. Operational modes are RED blink, RED continuous, GREEN blink, GREEN continuous, and off.
2. The remote output may be synchronized to the LED operation or controlled independent of the LEDs.

SPECIFICATIONS

Operating Voltage Range:                15 to  32 VDC

Standby Current:                               300

µ

A

 

@ 24 VDC (one

 

communication every 5 seconds with LED blink enabled)

Max.  Alarm Current (LED on):         6.5 mA @ 24  VDC

Operating Humidity Range:               10% to 93% Relative Humidity, noncondensing

Operating Temperature Range:        0° to 49°C (32° to 120°F); 2951J

                                                          0° to 38°C (32° to 100°F); 2951TJ and 2951TMJ 

Height:                                               2.0 inches (51 mm) installed in B210LPJ and B501J Bases

Diameter:                                          6.1 inches (155 mm) installed in B210LPJ Base

                                                          4.1 inches (104 mm) installed in B501J Base
Weight:                                              5.2 oz. (147 gm)

SPACING

Johnson Controls recommends spacing sensors in compliance with NFPA 72. In low air flow applications with smooth ceilings, space sensors 30 feet apart. 
For specific information regarding sensor spacing, placement, and special applications, refer to NFPA 72 or the 

System Smoke Detector Application Guide

(A05-103-XX) available from Johnson Controls.
Duct Applications: 2951J and 2951TJ are listed for use in ducts. See Duct Applications Guide A05-1004 for details on pendant mount applications.

NOTE:

 These products are not listed for use inside duct smoke detectors.

WIRING INSTRUCTIONS

All wiring must be installed in compliance with the National Electrical Code, applicable 

local codes, and any special requirements of the Authority Having Jurisdiction. Proper 

wire gauges should be used. The installation wires should be color-coded to limit wiring 

mistakes and ease system troubleshooting. Improper connections will prevent a system 

from responding properly in the event of a fire.

Disconnect power from the SLC communication line before installing sensors.

1.   Wire the sensor base (supplied separately) per the wiring diagram (Figure 1).

2.   Set the desired SLC address on the sensor address switches.

      NOTE: Some panels support extended SLC addressing. In order to set the sensor 

above address 99 on compatible systems, carefully remove the stop on the upper 

rotary switch with thumb or finger as shown in Figure 2.

3.   Install the sensor into the sensor base. Push the sensor into the base while turning it 

clockwise to secure it in place.

4.   After all sensors have been installed, apply power to the control unit and activate the 

communication line.

5.   Test the sensor(s) as described in the 

TESTING

 section of this manual.

TAMPER-RESISTANCE

Models 2951J, 2951TJ and 2951TMJ include a tamper-resistant capability that prevents their removal from the 

bracket without the use of a tool. Refer to the base manual for details on making use of this capability.

TESTING

Before testing, notify the proper authorities that the system is undergoing maintenance, and will temporarily be out 

of service. Disable the system to prevent unwanted alarms.
All sensors must be tested after installation and periodically thereafter. Testing methods must satisfy the Authority  

 

 

 

 

Having Jurisdiction (AHJ). Sensors offer maximum performance when tested and maintained in compliance with   

 

 

 

 

NFPA 72. The sensor can be tested in the following ways:

A.  Functional: Magnet Test (P/N M02-04-01 or M02-09-00)

 

3

2

1

3

2

1

+

-

-

+

UL LISTED COMPATIBLE

CONTROL PANEL

OPTIONAL RETURN LOOP

REMOTE ANNUNCIATOR

+

-

C0147-00

CAUTION

Dust  covers  provide  limited  protection  against  airborne  dust  particles  during  shipping.  Dust  covers  must  be 
removed before the sensors can sense smoke. Remove sensors prior to heavy remodeling or construction.