T7200
P/N 24-85784-00186 Rev. C Issue Date: 01 2020
English
PARAMETER SETTING (PART 2/2)
Code
T7200-
TB21-9JS0,
T7200-
TB21-9JS1
T7200-TF20-
9JS0,
T7200-TF20-
9JS1
Parameter Name
Default Function
15
■
■
Default display
00
00:
Display room temp.
01:
Display setpoint only
16
■
3
■
3
Auto changeover
00
00:
Disable
01:
Enable
17
■
■
Digital input function
00
00:
Setpoint reduction when contact is Closed (UnOccupied)
01:
Setpoint reduction when contact is Open (UnOccupied)
02:
Dew Point Alarm when contact is Closed
03:
Dew Point Alarm when contact is Open
04:
Shut off Fan and Valves when contact is Closed
05:
Filter Alarm when contact is Closed
06:
Filter Alarm when contact is Open
18
■
■
Unit selection
00
00:
Celsius degree (°C)
01:
Fahrenheit degree (°F)
19
■
■
Temperature offset
0
Setting range -5°C to 5°C (-9°F to 9°F)
20
■
1
■
1
Fan speed
00
00:
3 Speed
01:
2 Speed (MED, LOW)
02:
1 Speed (LOW)
03:
No Fan
21
■
■
Language
00
00:
Chinese
01:
English
22
■
■
Mode selection
00
00:
Cooling/heating/ventilation
01:
Cooling only
02:
Heating
23
■
■
Back light
30
The back light will be OFF in 05 seconds to 60 seconds.
25
■
8
■
8
Remote sensor type
00
00:
China market 10KNTC
01:
JCI type II 10NTC
28
■
4
---
Sample time
10
Setting range 1 to 99
29
■
■
Deadband
1
Setting range 0°C to 10°C (32°F to 50°F)
30
■
4
---
KP
10
Setting range 1 to 99
31
■
4
---
KI
01
Setting range 0 to 99
32
■
5
■
5
TiO2/ESP operation
00
00:
Operate separately (Pressing Timer button shortly)
01:
Work in parallel with FCU fan
33
■
6
■
6
Inter stage difference
3
Setting range 0°C to 10°C (32°F to 50°F)
34
■
6
■
6
Heating stage
00
00:
2 Stages
01:
1 Stage
35
■
7
---
Set Damper Opening time control
00
00:
Disable
01:
Enable
36
■
7
---
Damper opening time, 75 - 174 seconds
(only AHU application)
00
00 - 99
(00 = 75 s / 99 = 174 s)
37
■
■
Fan off timer (time position setting for
fan off)
00
00-99 seconds
Note
•
Terminal blocks changes depending on the application selected, please check the table beside first
• The relay output are line voltage, they are connected with Terminal “L” internally
•
The digital input “OCC” can assume different meaning depending on parameter 17 setting
1
Appeared when application parameter is 00,01,02,03,04,05,07
2
Appeared when application parameter is 00,01,02,03,04,05
3
Appeared when application parameter is 01 for T7200-TB21-9JS0 and T7200-TF20-9JS0
4
Appeared when application parameter is 06 07
5
Appeared when application parameter is 03
6
Appeared when application parameter is 04
7
Appeared when application parameter is 06
8
Parameter 25 is supported by T7200-TB21-9JS1 and T7200-TF20-9JS1