Note:
The EOL termination rules for
SA buses and FC buses are different.
Refer to the
MS/TP Communications Bus
Technical Bulletin (LIT-12011034)
for detailed
information regarding EOL termination
rules and EOL switch settings on SA and FC
buses.
3. If the expansion module is a terminating
device on the FC bus, set the EOL switch
to ON. If the expansion module is not a
terminating device on the bus, set the EOL
switch to OFF.
When an expansion module is connected
to power with its EOL switch set to ON, the
amber EOL LED on the expansion module
cover is lit.
Commissioning
You commission expansion modules with CCT
software through Mobile Access Portal (MAP)
Gateway at version 4.2 or above, or in BACnet router
mode when connected to an SNC, SNE, NAE or NCE.
Refer to the
Controller Tool Help (LIT-12011147)
for
detailed information on commissioning expansion
modules.
Note:
To configure the IOM on the Field
Controller (FC) bus, use CCT 10.4 release mode.
Firmware Package File
The MS-FCP-0 equipment controller firmware
package files are required for CCT to configure and
commission the controllers. The firmware package
files also allow you to upgrade an existing IOM
to the latest firmware release available for that
expansion module.
Beginning at CCT Release 13, the firmware package
files are orderable separately; they are not included
with CCT. They are obtained from the Metasys
software licensing portal, and are loaded and
licensed on the computer/server that is running
CCT.
For additional information about the firmware
package files, refer to the
CCT Installation Instructions
(LIT-12011259)
.
LED status and states
Observe the Status LEDs on the front of the
expansion module. Table 7 provides LED status
indicator information for troubleshooting the
expansion module.
Table 7: Status LEDs and description of LED states
LED label
LED color
Normal LED state Description of LED states
POWER
Green
On Steady
Off Steady = No Supply Power or the expansion module’s polyswitch/resettable
fuse is open. Check Output wiring for short circuits and cycle power to expansion
module.
On Steady = Power Connected
FAULT
Red
Off Steady
Off Steady = No Faults
On Steady = Device Fault; no application loaded; Main Code download required,
if the expansion module is in Boot mode, or a firmware mismatch exists between
the expansion module and the ZFR1811 Wireless Field Bus Router
Blink - 2 Hz = Download or Startup in progress, not ready for normal operation
SA/FC BUS
Green
Blink - 2 Hz
Blink - 2 Hz = Data Transmission (normal communication)
Off Steady = No Data Transmission (N/A - auto baud not supported)
On Steady = Communication lost, waiting to join communication ring
EOL
Amber
Off (Except on
terminating
devices)
On Steady = EOL switch in ON position
Off Steady = EOL switch in Off position
Accessories
Table 8: Accessories Ordering Information
Product Code Number Description
Mobile Access Portal
(MAP) Gateway
Refer to the
Mobile Access Portal Gateway Catalog Page (LIT-1900869)
to identify the appropriate product for
your region.
TL-CCT-0
Controller Configuration Tool (CCT) Software
MS-FCP-0
Field Controller Firmware Package Files for CCT
TP-2420
Transformer, 120 VAC Primary to 24 VAC secondary, 20 VA, Wall Plug
IOM3723 Input/Output Module Installation Guide