The dehumidifier is supplied with two 8” round collars. An integral backflow damper is installed in the outlet collar. In a ducted installation, the 

dehumidifier pulls air from the living space or HVAC return duct and supplies the dehumidified air to the HVAC supply duct (See 

Figures 5, 6 & 7

). 

DUCTED INSTALLATION

•   Move supply collar to the desired location, if necessary. (See 

Supply Collar

 in 

SET-UP

 section.)

•   The unit can be ducted to the supply or both the return and supply. The dehumidifier inlet ducting must be a minimum of 6” upstream of the 

HVAC system air cleaner and the outlet must be ducted a minimum of 6” downstream of the cooling coil.

   An additional option is to duct the dehumidifier inlet and outlet to the return duct. This installation must include wiring the dehumidifier to 

activate the HVAC blower during dehumidification. (See 

Wiring to HVAC System

 in 

WIRING

 section.) 

•   Use the least amount of ductwork possible. To ensure best performance, do not exceed a total of 50 feet of duct installed in accordance with 

SMACNA Standards. UL approved, 8” diameter, insulated duct is recommended for all connections.

•   All joints and seams must be sealed.

DUCTING 

HVAC / FURNACE

115 VAC

CIRCUIT

DEHUMIDIFIER

SUPPLY DUCT

RETURN

DUCT

A-COIL

DEHUMIDIFIED AIR IS SUPPLIED

DOWNSTREAM

  FROM A-COIL TO

MINIMIZE EVAPORATION OFF A-COIL

AIR IS PULLED

FROM MAIN

RETURN DUCT

DEHUMIDISTAT WITH 

SET POINT KNOB

CONDENSATE HOSE

(TO COMMON DRAIN OR OUTSIDE)

NOTE: 

DO NOT BLOCK

FURNACE ACCESS

FIGURE 5 – Basement Installation

90-1423

MAIN RETURN 

DUCT

DEHUMIDIFIER

MAIN SUPPLY DUCT

CONDENSATE

HOSE

(TO COMMON

DRAIN OR

OUTSIDE)

PRINCIPAL

LIVING SPACE

115 VAC

CIRCUIT

HVAC/FURNACE SYSTEM 

SHOWN IN HORIZONTAL

ORIENTATION

DEHUMIDIFIED AIR IS SUPPLIED

DOWNSTREAM 

FROM EVAPORATOR COIL

TO MINIMIZE EVAPORATION OFF COIL

HVAC EVAPORATOR COIL

RELOCATE DEHUMIDISTAT

TO LIVING SPACE

AIR FILTER ACCESS DOOR

CONDENSATE PAN

AND FLOAT SWITCH

FIGURE 7 – Attic Installation

90-1423

DEHUMIDIFIED AIR IS SUPPLIED 

DOWNSTREAM 

FROM A-COIL TO 

MINIMIZE EVAPORATION OFF A-COIL

115 VAC

CIRCUIT

A-COIL

SUPPLY DUCT

HVAC / FURNACE

CONDENSATE HOSE

ON DEHUMIDIFIER

(TO COMMON DRAIN

OR OUTSIDE)

DEHUMIDIFIER

NOTE: 

DEHUMIDIFIER

DRAWS AIR FROM 

LIVING SPACE THROUGH 

RETURN GRILL

FIGURE 6 – Equipment Room/Closet Installation

90-1423

Note 1:

 Attic installations require the following.

1.  The dehumidistat must be removed from the 

unit and relocated in the living space. An 

insulated cover plate is provided to cover the 

dehumidistat opening.

2.  The dehumidifier must be installed in the 

supplied condensate pan with a field supplied 

float switch. 

Note 2:

 Vibration isolators placed under the 

dehumidifier feet are recommended when the 

dehumidifier is installed on ceiling joists.

 CAUTION

Ensure return grill in door is not obstructed so dehumidifier 

does not pull from HVAC system.

3

Summary of Contents for S1-CD065T01

Page 1: ...ION 1 Do not use in pool applications 2 If unit has been shipped or stored on its side wait 24 hours before running 3 Do not use solvents or cleaners on or near the circuit board P w c Airflow cfm 0 2...

Page 2: ...inside wall of the living space Do not locate dehumidistat in the direct path of drafts from open doors and windows Do not install where operation might be affected by lamps outside sources of humidit...

Page 3: ...ION OFF A COIL AIR IS PULLED FROM MAIN RETURN DUCT DEHUMIDISTAT WITH SET POINT KNOB CONDENSATE HOSE TO COMMON DRAIN OR OUTSIDE NOTE DO NOT BLOCK FURNACE ACCESS Figure 5 Basement Installation 90 1423 M...

Page 4: ...f the unit is not wired to the HVAC system air is pulled through the unit dehumidified and circulated solely by the dehumidifier blower Wiring To HVAC System DEHUMIDIFIER CIRCUIT BOARD TERMINALS HVAC...

Page 5: ...EMOTE terminals from the circuit board remove the two wires and cut off bare leads Once cut the wires may remain in the unit 9 Run a 2 wire cable 18 22AWG from the dehumidifier to the wall mount locat...

Page 6: ...h the wiring access panel in the back of the dehumidifier see Figure 15 Remove the wiring access panel and pull the FLOAT SWITCH terminal block off the circuit board Remove the float switch jumper wir...

Page 7: ...ressor do not activate 6 Check LED indicators Green should remain on If Red LED is on refer to the TROUBLESHOOTING GUIDE The red LED turns on when a fault condition is active Possible fault conditions...

Page 8: ...t is not ducted to HVAC return install approximately 2 of 8 flex duct on inlet collar Vibration Install vibration isolators under dehumidifier feet Dehumidifier is producing hot air This is normal ope...