Electrical Data
Table 5:
Electrical Data - Outdoor Unit - AC Without Powered Convenience Outlet
Model
Compressors
Outdoor Fan Motor
Pwr Conv Outlet
Minimum
Circuit
Ampacity
1
Maximum
Fuse Size
(A)
2
Power
Supply
Qty
RLA
(each)
MCC
(each)
LRA
(each)
Power
Supply
HP
Qty
FLA
(each)
FLA
J07YC
208/230-3-60
1
25.0
39
164
208/230-1-60
1/3
2
2.1
-
35.5
45
460-3-60
1
12.2
19
100
460-1-60
1/3
2
1.2
-
17.6
25
575-3-60
1
9.0
14
78
575-1-60
1/3
2
0.9
-
13.1
20
J10YC
208/230-3-60
2
18.1
28.3
137
208/230-1-60
3/4
2
3.0
-
46.8
60
460-3-60
2
9.0
14.0
62
460-1-60
3/4
2
1.6
-
23.5
30
575-3-60
2
6.8
10.6
50
575-1-60
3/4
2
1.4
-
18.0
20
J10YD
208/230-3-60
2
17.3
27
123
208/230-1-60
3/4
2
3.0
-
45.0
60
460-3-60
2
9.6
15
70
460-1-60
3/4
2
1.6
-
24.8
30
575-3-60
2
7.7
12
53
575-1-60
3/4
2
1.4
-
20.0
25
J12YC
208/230-3-60
2
22.4
35
149
208/230-1-60
3/4
2
3.0
-
56.5
70
460-3-60
2
10.6
17
75
460-1-60
3/4
2
1.6
-
27.1
35
575-3-60
2
7.7
12
54
575-1-60
3/4
2
1.4
-
20.0
25
J12YD
208/230-3-60
2
23.1
36
160
208/230-1-60
3/4
2
3.0
-
58.0
80
460-3-60
2
12.2
19
87
460-1-60
3/4
2
1.6
-
30.7
40
575-3-60
2
8.7
14
62
575-1-60
3/4
2
1.4
-
22.3
30
J15YC
208/230-3-60
2
25.0
39
164
208/230-1-60
1/3
4
2.1
-
64.7
80
460-3-60
2
12.2
19
100
460-1-60
1/3
4
1.2
-
32.2
40
575-3-60
2
9.0
14
78
575-1-60
1/3
4
0.9
-
24.0
30
J15YD
208/230-3-60
2
25.0
39
164
208/230-1-60
1/3
4
2.1
-
64.7
80
460-3-60
2
12.2
19
100
460-1-60
1/3
4
1.2
-
32.2
40
575-3-60
2
9.0
14
78
575-1-60
1/3
4
0.9
-
24.0
30
J20YC
208/230-3-60
2
30.1
47
225
208/230-1-60
3/4
4
3.0
-
79.8
100
460-3-60
2
16.7
26
114
460-1-60
3/4
4
1.6
-
44.0
60
575-3-60
2
12.2
19
80
575-1-60
3/4
4
1.4
-
32.9
45
J20YD
208/230-3-60
2
30.1
47
225
208/230-1-60
3/4
4
3.0
-
79.8
100
460-3-60
2
16.7
26
114
460-1-60
3/4
4
1.6
-
44.0
60
575-3-60
2
12.2
19
80
575-1-60
3/4
4
1.4
-
32.9
45
J25YC
208/230-3-60
2
48.1
75
245
208/230-1-60
3/4
4
3.0
-
120.3
150
460-3-60
2
18.6
29
125
460-1-60
3/4
4
1.6
-
48.3
60
575-3-60
2
14.7
23
100
575-1-60
3/4
4
1.4
-
38.5
50
1.
Based on three, 75°C insulated copper conductors in conduit and ambient of 30°C.
2. Maximum fuse or maximum circuit breaker (HACR type per NEC).
Refer to NEC/NFPA No. 70, Articles 440-11, 12 for information on minimum disconnect sizing.