background image

5165699-BIM-C-0516

2

Johnson Controls Unitary Products

SECTION II: SAFETY

This is a safety alert symbol. When you see this symbol on
labels or in manuals, be alert to the potential for personal
injury.

Understand and pay particular attention to the signal words 

DANGER

,

WARNING

, or 

CAUTION

DANGER 

indicates an 

imminently

 hazardous situation, which, if not

avoided, 

will result in death or serious injury

.

WARNING 

indicates a 

potentially

 hazardous situation, which, if not

avoided, 

could result in death or serious injury

.

CAUTION 

indicates a potentially hazardous situation, which, if not

avoided 

may  result  in  minor  or  moderate  injury.

 It is also used to

alert against unsafe practices and hazards involving only property dam-
age.

1.

Install this electric furnace only in a location and position as speci-
fied in SECTION III of these instructions.

2.

Always install the electric furnace to operate within the electric fur-

nace’s intended maximum outlet air temperature. Only connect the
air handler to a duct system which has an external static pressure
within the allowable range, as specified on the EB rating plate.

3.

When an electric furnace is installed so that supply ducts carry air
circulated by the air handler to areas outside the space containing
the air handler, the return air shall also be handled by duct(s)
sealed to the air handler casing and terminating outside the space
containing the air handler.

4.

The electric furnace is not to be used for temporary heating of
buildings or structures under construction.

5.

The size of the unit should be based on an acceptable heat loss or
gain calculation for the structure. ACCA, Manual J or other
approved methods may be used.

SAFETY REQUIREMENTS

1.

This electric furnace should be installed in accordance with all
national and local building/safety codes and requirements, local
plumbing or wastewater codes, and other applicable codes.

2.

Refer to the unit rating plate for the EB model number, and then
see the dimensions page of this instruction for supply air plenum
dimensions in Figure 3. The plenum must be installed according to
the instructions.

3.

Provide clearances from combustible materials as listed under
Clearances to Combustibles.

4.

Provide clearances for servicing ensuring that service access is
allowed for electric furnace elements and blower.

5.

Failure to carefully read and follow all instructions in this manual
can result in electric furnace malfunction, death, personal injury
and/or property damage.

6.

Check the rating plate and power supply to be sure that the electri-
cal characteristics match.

7.

Electric furnace shall be installed so the electrical components are
protected from water.

8.

Installing and servicing heating/cooling equipment can be hazard-
ous due to the electrical components. Only trained and qualified
personnel should install, repair, or service heating/cooling equip-
ment. Untrained service personnel can perform basic maintenance
functions such as cleaning and replacing the air filters. When
working on heating/cooling equipment, observe precautions in the
manuals and on the labels attached to the unit and other safety
precautions that may apply.

9.

These instructions cover minimum requirements and conform to
existing national standards and safety codes. In some instances
these instructions exceed certain local codes and ordinances,
especially those who have not kept up with changing residential
and non-HUD modular home construction practices. These
instructions are required as a minimum for a safe installation.

INSPECTION

As soon as a unit is received, it should be inspected for possible dam-

age during transit. If damage is evident, the extent of the damage
should be noted on the carrier’s freight bill. A separate request for
inspection by the carrier’s agent should be made in writing. Also, before
installation the unit should be checked for screws or bolts, which may
have loosened in transit. There are no shipping or spacer brackets
which need to be removed.

Also check to be sure all accessories such as heater kits, suspension

kits, and coils are available. Installation of these accessories or field
conversion of the unit should be accomplished before setting the unit in
place or connecting any wiring, electric heat, ducts or piping.

CODES

The electric furnace must be installed in accordance with the following
codes:

Standard for the Installation of Air Conditioning and Ventilating
Systems (NFPA 90A)

Standard for the Installation of Warm Air Heating and Air Condi-
tioning Systems (NFPA 90B)

National Electric Code (NFPA 70)

Canadian Electrical Code, Part I (CSA C22.1)

All local codes (state/county/township).

 WARNING

Improper installation may create a condition where the operation of
the product could cause personal injury or property damage.
Improper installation, adjustment, alteration, service or mainte-
nance can cause injury or property damage. Refer to this manual
for assistance or for additional information, consult a qualified con-
tractor, installer or service agency.

 CAUTION

This product must be installed in strict compliance with the installa-
tion instructions and any applicable local, state, and national codes
including, but not limited to building, electrical, and mechanical
codes.

 WARNING

FIRE OR ELECTRICAL HAZARD
Failure to follow the safety warnings exactly could result in serious
injury, death or property damage.

A fire or electrical hazard may result causing property damage, per-

sonal injury or loss of life.

!

!

!

NOTICE

All applicable codes take precedence over any recommendation

made in these instructions.

Summary of Contents for EB10F

Page 1: ...mance 7 Electrical Data 7 SECTION I GENERAL The following list includes important facts and information regarding the EB furnace and its packaging inclusions 1 Furnace is rated at 240 volts 60 Hz single phase 2 Filters are furnished with each model and are the same for all models 16 x 20 x 1 in top and 20 x 20 x 1 in the louvered door 3 Furnace size is the same for all models See Figure 1 4 Four w...

Page 2: ...stalling and servicing heating cooling equipment can be hazard ous due to the electrical components Only trained and qualified personnel should install repair or service heating cooling equip ment Untrained service personnel can perform basic maintenance functions such as cleaning and replacing the air filters When working on heating cooling equipment observe precautions in the manuals and on the ...

Page 3: ...s not required if there is a return grille installed above the furnace height This return grille cannot start more than three feet above the fur nace height For Upflow installations a closet 32 81 3 cm wide by 30 76 2 cm deep with a 30 76 2 cm wide door is necessary See Figure 3 When installing furnace in a separate closet or room which is accessi ble only through an outside door a minimum of 200 ...

Page 4: ... floor opening See Figure 6 TABLE 1 Duct Connector for Electric Furnaces FLOOR TO DUCT DIMENSIONS FINGERED STYLE SCREW TAB STYLE 1 2 54 cm 7990 6211 7990 6011 2 5 1 cm 7990 6221 7990 6021 3 7 6 cm 4 10 2 cm 7990 6241 7990 6041 5 12 7 cm 6 15 2 cm 7990 6261 7990 6061 7 17 8 cm 7990 6271 7990 6071 8 20 3 cm 7990 6281 7990 6081 9 22 8 cm 10 25 4 cm 7990 6301 7990 6101 11 282 cm 12 30 5 cm 7990 6321 7...

Page 5: ...width ducts there will not be suf ficient clearance to bend the tabs on two sides of the duct connector In such cases the tabs may be attached to the sides of the duct by using sheet metal screws or other suitable fasteners Holes for sheet metal screws are provided in three 3 tabs on each side of the duct connector If more than 3 tabs need to be used to provide a more secure and air tight connecti...

Page 6: ...hed under the casing flange and screws provided can be used to capture the other end of duct con nector Secure collar to top of furnace 10 The flange plate shipped with kit 3500 7211 is mounted to the fur nace using eight 8 screws supplied with kit 3500 8961A Two blunt screws should be used to secure the front edge of flange plate to furnace See Figure 11 11 Secure the top of the furnace to a stru...

Page 7: ... 50 0 59 2 58 4 Minimum Wire Size 90ºC 8 10 6 10 8 8 6 6 Minimum Wire Size 75ºC 6 10 6 10 6 8 6 6 Minimum Wire Size 60ºC 6 10 4 10 6 6 4 4 Ground Wire Size 4 4 Refer to National Electrical Code Table 250 122 for Non Sheathed Conductor Ground Wire 10 10 10 10 10 10 10 10 Max Fuse or C B Amps 60 30 60 30 60 50 60 60 TABLE 3 EB Series Blower Performance Static Pressure inches of w c 0 0 0 1 0 2 0 3 0...

Page 8: ...FORMER LIMIT SWITCHES GROUND LUGS 3500 378P JUMPER BARS FOR SINGLE BRANCH CIRCUIT SERVICE THERMOSTAT WIRES CIRCUIT BREAKERS SEQUENCERS NOTE As Shipped the jumper bar assembly is set up for bottom entry For side entry the top lug can be removed and re positioned as shown to provide proper wire bending clearances A0345 001 0 6 F F O N O N O F F O 0 6 WARNING For personal safety be sure to turn the e...

Page 9: ...tallation instructions packed with the accessory package for more information FIGURE 15 Thermostat Wiring DELUXE BLEND AIR II FRESH AIR FRESH AIR OFF AUTO ALARM RED RED WHITE WHITE GREEN GREEN BLACK B L A C K BLACK RED WHITE GREEN Y E LL O W WIRES FROM FURNACE NOT FACTORY INSTALLED STANDARD OR DELUXE BLEND AIR CONTROL BOX THERMOSTAT WIRING SCHEMATIC FOR BLEND AIR AND FURNACE The EB Furnaces are A ...

Page 10: ...F L REPLACE FILTER WITH SAME SIZE 240 VAC 60 Hz 1 PHASE NOTE 4 SPEED BLOWER EB SERIES FURNACES GRN WHT M4 H1 YEL L L YEL YEL SINGLE BRANCH CIRCUIT SERVICE 240 VAC 60Hz 1 PHASE GND LUG DO NOT OPEN THIS PANEL UNTIL ELECTRICAL POWER IS SHUT OFF AT HOUSEHOLD SERVICE BOX CHECK WITH A VOLTMETER OR OTHER PROPER INSTRUMENT HAZARD OF ELECTRICAL SHOCK SERVICE CONNECTION COVER MUST BE INSTALLED IF FILTERS AR...

Page 11: ... F L REPLACE FILTER WITH SAME SIZE 240 VAC 60 Hz 1 PHASE NOTE 4 SPEED BLOWER EB SERIES FURNACES GRN WHT M4 H1 YEL L L YEL YEL SINGLE BRANCH CIRCUIT SERVICE 240 VAC 60Hz 1 PHASE GND LUG THIS FURNACE MAY BE CONNECTED TO MORE THAN ONE POWER SUPPLY TURN OFF ALL POWER TO THE FURNACE AT THE WALL BOX AND LOCK IT OUT DO NOT OPEN THIS PANEL UNTIL ELECTRICAL POWER IS SHUT OFF AT HOUSEHOLD SERVICE BOX CHECK ...

Page 12: ...LL BOX AND LOCK IT OUT DO NOT OPEN THIS PANEL UNTIL ELECTRICAL POWER IS SHUT OFF AT HOUSEHOLD SERVICE BOX CHECK WITH A VOLTMETER OR OTHER PROPER INSTRUMENT HAZARD OF ELECTRICAL SHOCK SERVICE CONNECTION COVER MUST BE INSTALLED IF FILTERS ARE USED CLEAN REPLACE EACH SEASON OR MORE OFTEN IF NEEDED CAUTION IMPORTANT HIGH VOLTAGE WARNING IF ANY OF THE ORIGINAL WIRE SUPPLIED WITH THIS UNIT MUST BE REPLA...

Page 13: ... POWER TO THE FURNACE AT THE WALL BOX AND LOCK IT OUT DO NOT OPEN THIS PANEL UNTIL ELECTRICAL POWER IS SHUT OFF AT HOUSEHOLD SERVICE BOX CHECK WITH A VOLTMETER OR OTHER PROPER INSTRUMENT HAZARD OF ELECTRICAL SHOCK SERVICE CONNECTION COVER MUST BE INSTALLED IF FILTERS ARE USED CLEAN REPLACE EACH SEASON OR MORE OFTEN IF NEEDED CAUTION IMPORTANT HIGH VOLTAGE WARNING IF ANY OF THE ORIGINAL WIRE SUPPLI...

Page 14: ...LL POWER TO THE FURNACE AT THE WALL BOX AND LOCK IT OUT DO NOT OPEN THIS PANEL UNTIL ELECTRICAL POWER IS SHUT OFF AT HOUSEHOLD SERVICE BOX CHECK WITH A VOLTMETER OR OTHER PROPER INSTRUMENT HAZARD OF ELECTRICAL SHOCK SERVICE CONNECTION COVER MUST BE INSTALLED IF FILTERS ARE USED CLEAN REPLACE EACH SEASON OR MORE OFTEN IF NEEDED CAUTION IMPORTANT HIGH VOLTAGE WARNING IF ANY OF THE ORIGINAL WIRE SUPP...

Page 15: ...ARS P N 3500 378 NOTE 4 SPEED BLOWER EB SERIES FURNACES GRN WHT M4 H1 M7 M8 RED R L SHOCK HAZARD THIS FURNACE MAY BE CONNECTED TO MORE THAN ONE POWER SUPPLY TURN OFF ALL POWER TO THE FURNACE AT THE WALL BOX AND LOCK IT OUT DO NOT OPEN THIS PANEL UNTIL ELECTRICAL POWER IS SHUT OFF AT HOUSEHOLD SERVICE BOX CHECK WITH A VOLTMETER OR OTHER PROPER INSTRUMENT HAZARD OF ELECTRICAL SHOCK SERVICE CONNECTIO...

Page 16: ... change without notice Published in U S A 5165699 BIM C 0516 Copyright 2016 by Johnson Controls Inc All rights reserved Supersedes 5165699 BIM B 0316 York International Corp 5005 York Drive Norman OK 73069 NOTES ...

Reviews: