background image

1101790-UIM-C-0414

Johnson Controls Unitary Products

23

Blower Speed Selection

The variable speed blowers are designed to deliver constant 
CFM regardless of the external static pressure (ESP) in the 
ductwork. Therefore, if too many supply registers are closed, a 
filter becomes clogged, or there is a restriction in the ductwork, 
the motor will automatically operate at a higher speed to 
compensate for the higher ESP. This may result in a higher 
operating sound level.

These units have variable speed motors that automatically adjust 
to provide constant CFM from 0.2" to 0.6" w.c. static pressure. 
From 0.6" to 1.0" static pressure, CFM is reduced by 2% per 0.1" 
increase in static. Operation on duct systems with greater than 
1.0" w.c. external static pressure is not recommended.

To Set Cooling CFM for DHQ Units:

Refer to Airflow Performance Tables 13 and 14 for the possible 
cooling speed CFM selections.

Set “COOL” and “ADJ” Jumpers on the CFM selection board as 
indicated in Tables 13, 14 and Figure 11.

NOTE: 

CFM indicator light flashes once for every 100 CFM 
(i.e. 12 flashes = 1200 CFM).

To Set Delay Profile:

Every unit has multiple cooling “blower off delay” profiles to 
optimize system performance and efficiency. Refer to Table 16 
for the regional climate in your area. Place the “DELAY” jumper 
tap on the CFM selection board on the appropriate pin setting.

Factory Set Gas Heat CFM:

The blower speed required for gas heat is different than for 
cooling. The heating CFM is factory set, but is adjustable.

The “Heat” Jumper on the CFM selection board should be 
set to “A” from the factory.

Fan Only CFM:

When the connection is made from “R” to “G”, the fan only 
mode is activated. In this mode, the blower will deliver 75% of 
the cooling system CFM. This connection is factory set from the 
manufacturer, but can be field adjusted.

Figure 11: Control Board Speed Tap Location

Operation

The unit is controlled by a conventional heating/cooling 
thermostat common to this class of equipment.

Sequence Of Operation

Heat

First Stage Cooling Call 

On a first stage cooling call, the thermostat sends 24 Volts AC 
out of the “Y1”, “O”, and “G” terminals to the CFM Selector 
Board (CFMCB).

When 24 Volts AC is sent from CFMCB to the “Y1” terminal of 
the YorkGuard VI defrost control board (DCB) energizing the 
“M1” contactor coil. 

When the contactor coil is energized, the compressor operates 
in first stage cooling; the “ODF” contacts on the DCB close and 
energize the ECM 142R outdoor fan motor in low speed. 

Exception: The 2 ton dual fuel units operate the outdoor fan at 
high speed anytime the compressor is operating.

24 Volts AC is also sent out of the CFMCB to the ECM Blower 
Motor for first stage cooling fan speed and out of the “RV” and 

Table 15: Indoor Blower Specifications

Model

(Tons)

Motor

HP

RPM

Eff.

SF

Frame

DHQ

024

(2.0)

 1/2

1050

0.8

1.0

48

DHQ

030

(2.5)

3/4

1050

0.8

1.0

48

DHQ

036

(3.0)

 3/4

1050

0.8

1.0

48

DHQ

042

(3.5)

1

1050

0.8

1.0

48

DHQ

048

(4.0)

1

1050

0.8

1.0

48

DHQ

060

(5.0)

1

1050

0.8

1.0

48

Do not change the “ADJ” tab position on the CFM 
selection board as this will change your cooling CFM 
previously selected.

Table 16: Delay Profile

Delay Tap

Regional Climate Type

Jumper at “A”

Standard Setting

Jumper at “B”

Humid Climate

Jumper at “C”

Dry Climate

Jumper at “D”

Temperate Climate

W2

W1

R

Y1

Y/Y2

Summary of Contents for DHQ024

Page 1: ...T OF FIGURES 1 Component Location 4 2 Unit 4 Point Load Weight 6 3 Unit Dimensions 7 4 Dimensions Front and Bottom 8 5 Dimensions Back and Bottom 8 6 Roof Curb 9 7 Typical Field Control Wiring Diagram...

Page 2: ...nual For assistance or additional information consult a qualified installer service agency or the gas supplier This system uses R 410A Refrigerant which operates at higher pressures than R 22 No other...

Page 3: ...heating of buildings or structures under construction Limitations These units must be installed in accordance with the following In U S A 1 National Electrical Code ANSI NFPA No 70 Latest Edition 2 Na...

Page 4: ...orary heating of buildings or structures under construction Figure 1 Component Location Direct Drive Condenser Fan Motor Highly Efficient Enhanced Copper Tube Aluminum Fin Evaporator Coil Highly Effic...

Page 5: ...unit Do not remove any packaging until the unit is near the place of installation Rig the unit by attaching chain or cable slings to the lifting holes provided in the base rails Spreader bars whose l...

Page 6: ...D A B C D E F DHQ024 2 0 418 413 25 20 1 81 88 128 116 53 56 60 87 81 76 DHQ030 2 5 431 426 24 4 20 1 85 89 129 123 56 58 60 86 84 81 DHQ036 3 0 438 433 24 6 20 1 86 91 132 124 57 59 61 89 85 82 DHQ0...

Page 7: ...TMENT PANEL 1 1 2 2 5 8 3 1 3 12 3 4 11 5 3 8 49 1 8 47 1 4 LEFT FRONT RIGHT Table 4 Unit Dimensions Front Unit Model Dimensions A B DHQ024 030 036 33 1 2 18 1 4 DHQ042 048 060 41 1 2 23 1 8 Table 5 U...

Page 8: ...SUPPLY 1 5 8 DIA KNOCKOUT 1 2 NPTF CONNECTION LOW VOLTAGE CONN 7 8 DIA KNOCKOUT 4 5 8 26 3 4 CONDENSATE DRAIN 3 4 NPTF HIGH VOLTAGE CONN 1 3 32 DIA KNOCKOUT 4 14 1 2 28 3 8 14 1 2 BACK 3 3 8 SIDE RETU...

Page 9: ...to note supply and return openings Refer to Figures 4 and 5 for information concerning rear and bottom supply and return air duct openings Roof Curb On applications when a roof curb is used the unit m...

Page 10: ...l ordinances The unit must be electrically grounded in accordance with local codes or in their absence with the N E C C E C Voltage tolerances which must be maintained at the compressor terminals duri...

Page 11: ...ompressors each OD Fan Motors each Supply Blower Motor MCA1 Amps 1 Minimum Circuit Ampacity Max Fuse2 Breaker3 Size Amps 2 Maximum Over Current Protection per standard UL 1995 3 Fuse or HACR circuit b...

Page 12: ...60 160 160 175 175 170 175 170 Gas piping connection in 1 2 1 2 1 2 1 2 1 2 1 2 DIMENSIONS inches Length 49 1 8 49 1 8 49 1 8 49 1 8 49 1 8 49 1 8 Width 47 1 4 47 1 4 47 1 4 47 1 4 47 1 4 47 1 4 Heigh...

Page 13: ...efer to Tables 8 and 9 The heating value of the gas may differ with locality The value should be checked with the local gas utility NOTE There may be a local gas utility requirement specifying a minim...

Page 14: ...6 180 370 80 43 90 170 350 90 40 84 160 320 100 38 79 150 305 Table 9 Propane LP Gas Pipe Sizing Chart1 1 Maximum capacity of pipe in thousands of BTU per hour based upon a pressure drop of 0 5 inch w...

Page 15: ...Table 11 Propane1 LP Gas Application Data Two Stage 1 Propane applications are accomplished by field installation of a Propane Conversion Accessory Model 1NP0809 for 2 and 3 Ton units with 33 1 2 tall...

Page 16: ...690 129 155 181 209 237 W1 HEAT C 710 137 164 191 219 248 W1 HEAT D 750 155 183 211 241 271 W1 W2 HEAT A 940 255 291 328 364 400 W1 W2 HEAT B 970 273 311 349 386 424 W1 W2 HEAT C 1000 292 332 371 410...

Page 17: ...W2 HEAT A 1200 384 427 470 514 W1 W2 HEAT B 1300 461 507 552 598 W1 W2 HEAT C 1400 546 595 643 690 W1 W2 HEAT D 1480 619 671 721 770 DHQ042 3 5 Cool Low Y1 O COOL A 934 225 253 281 317 352 384 415 447...

Page 18: ...W2 HEAT D 1700 598 644 689 783 DHQ060 5 0 Cool Low Y1 O COOL A 1034 247 277 307 354 401 431 470 508 546 Y1 O COOL B 1101 266 298 330 383 437 466 510 552 594 Y1 O COOL C 1167 289 322 355 415 475 505 5...

Page 19: ...181 209 237 W1 HEAT C 710 137 164 191 219 248 W1 HEAT D 750 155 183 211 241 271 W1 W2 HEAT A 940 255 291 328 364 400 W1 W2 HEAT B 970 273 311 349 386 424 W1 W2 HEAT C 1000 292 332 371 410 448 W1 W2 H...

Page 20: ...W2 HEAT A 1200 384 427 470 514 W1 W2 HEAT B 1300 461 507 552 598 W1 W2 HEAT C 1400 546 595 643 690 W1 W2 HEAT D 1480 619 671 721 770 DHQ042 3 5 Cool Low Y1 O COOL A 934 225 253 281 317 352 384 415 447...

Page 21: ...W2 HEAT D 1700 598 644 689 783 DHQ060 5 0 Cool Low Y1 O COOL A 1034 247 277 307 354 401 431 470 508 546 Y1 O COOL B 1101 266 298 330 383 437 466 510 552 594 Y1 O COOL C 1167 289 322 355 415 475 505 5...

Page 22: ...5 0 01 0 13 1200 0 06 0 02 0 16 1300 0 07 0 03 0 17 DHQ0036 3 0 700 0 01 0 00 0 04 800 0 02 0 01 0 06 900 0 03 0 01 0 08 1000 0 04 0 01 0 10 1100 0 05 0 01 0 13 1200 0 06 0 02 0 16 1300 0 07 0 03 0 17...

Page 23: ...ion board should be set to A from the factory Fan Only CFM When the connection is made from R to G the fan only mode is activated In this mode the blower will deliver 75 of the cooling system CFM This...

Page 24: ...nal to the CFM Selector Board CFMCB When the CFMCB receives 24 Volts AC at Y1 control voltage is sent to the Y1 terminal of the YorkGuard VI Defrost Control Board DCB energizing the M1 contactor coil...

Page 25: ...is also removed from the RV and RVG terminals de energizing the reversing valve The ODF contacts on the DCB re close energizing the outdoor fan motor Mechanical heating operation resumes Emergency Hea...

Page 26: ...t the DM and provides 120 Volts AC out of the IND terminal reducing the DM to low speed Control voltage is also removed from HI at the gas valve reducing gas heat operation to low fire operation Secon...

Page 27: ...utes W1 Out W2 Out after 15 Minutes When a Y1 Y2 W call are present mechanical heat is de energized 30 seconds after the gas heat section is energized and is locked out for the remainder of the heatin...

Page 28: ...control enters a hard lockout flashing 9 on the LED If the pilot or main valve becomes Un Welded the inducer will de energize but the control will remain in a hard lockout and not respond to any ther...

Page 29: ...n 7 Wait five 5 minutes to clear out any gas If you then smell gas STOP Follow B in the information on the unit safety label If you don t smell gas go to the next step 8 Turn the gas valve switch to t...

Page 30: ...e pilot flame should envelope 3 8 of the end of the flame sensor and not contain any yellow color see Figure 14 4 Replace the pilot adjustment cover screw after the pilot flame is set To check adjust...

Page 31: ...r particular locality Contact your gas company for this information since it varies widely from city to city BTUH Output 1 08 x CFM OR CFM BTUH Output Degrees F Temp Rise 1 08 x Degrees F Temp Rise Ta...

Page 32: ...AND OR NATIONAL CODES IN EFFECT AT THE TIME OF INSTALLATION OF THIS UNIT 2 CAUTION LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROLS WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS OPERAT...

Page 33: ...ONAL CODES IN EFFECT AT THE TIME OF INSTALLATION OF THIS UNIT 2 CAUTION LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROLS WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS OPERATION IF ANY O...

Page 34: ...88 17 80 64 7 4 95 167 77 398 99 16 80 64 8 4 400 Cfm Ton 75 63 75 138 67 288 77 21 75 54 6 3 85 141 68 335 88 20 75 55 7 2 95 145 70 386 98 19 75 56 8 2 Air Flow Indoor Db Wb Outdoor DB Suction Press...

Page 35: ...80 63 10 8 95 159 71 393 99 17 80 63 11 1 400 Cfm Ton 75 63 75 132 61 288 77 22 75 53 9 3 85 134 63 332 87 22 75 54 10 4 95 138 64 393 99 21 75 54 12 1 Air Flow Indoor Db Wb Outdoor DB Suction Pressur...

Page 36: ...16 80 64 15 4 95 160 70 409 101 16 80 64 17 3 400 Cfm Ton 75 63 75 132 60 301 79 21 75 54 13 1 85 134 62 348 90 20 75 55 15 1 95 137 64 396 99 20 75 55 17 1 Air Flow Indoor Db Wb Outdoor DB Suction P...

Page 37: ...mpressor amperes L1 L2 L3 Measured voltage R and C outdoor unit control board Electrical Connections Inspection Check all that apply Equipment Data Additional Kits Accessories Installed Check all that...

Page 38: ...turn Air Dry Bulb Temp Manifold Pressure at 100 Firing Rate w c Inlet Gas Pressure w c LP Gas Conversion Kit LP Conversion Kit Installed By Two Stage Single Stage Propane LP Requires LP Conversion Kit...

Page 39: ...only Manifold sets must be at least 700 psig high side and 180 psig low side with 550 psig retard All hoses must have a service pressure rating of 800 psig Leak detectors must be designed to detect H...

Page 40: ...change without notice Printed in U S A 1101790 UIM C 0414 Copyright 2014 by Johnson Controls Inc All rights reserved Supersedes 1101790 UIM B 0314 York International Corporation 5005 York Drive Norma...

Reviews: