5   Adjusting the Switching Unit 

Flow switch 

5   Adjusting the Switching Unit 

5.1   Contact type 

5.1.1   Standard contact 

The switching unit of the control switch enables 2 contact types: 

1. Make contact (normally open):   

“RED” arrow on the switching unit 

2. Break contact (normally closed): 

“WHITE” or “BLUE” arrow on the switching unit 

The following table explains the two contact types: 

Contact type

 

Setting

 

Flow rate:

 

Electric contact

 

increasing

closing

Make contact

 

RED arrow 

decreasing

opening

increasing

opening

Break contact

 

WHITE or BLUE arrow

decreasing

closing

If not otherwise agreed with the customer, the switching unit is factory set as a make contact, i.e. the reed 
contact opens if the set switching point is exceeded. 

5.1.2   Change-over contact (only for VH3...) 

For flow switches with a change-over contact a fine adjustment can only be carried out within the red arrow. 
The contact switches after reaching the set switching point. 

5.2   Flow switch version VH...X 

The flow switch version VH...X is supplied ex works with a fixed switching point. Adjustment of the switching 
point for flow switch version VH...X is not permitted. 

Page 13 of 15

Copyright ©  Jlso Tec Trade GmbH

JLSO Tec Trade GmbH 

In den Birken 98

Fon:

 

+49 (0) 

6369 230 9961

 

[email protected]

Fax:

 

+49 (0) 

6369 230 9963

 

https://jlso-tec-trade.de

Daniel

 

H.

 

Meckel

D-66999

 

Hinterweidenthal

Summary of Contents for VH M 1 1 1 Series

Page 1: ...age 1 15 www jlso tec trade de Page 1 of 15 Copyright Jlso Tec Trade GmbH JLSO Tec Trade GmbH In den Birken 98 Fon 49 0 6369 230 9961 info jlso tec trade de Fax 49 0 6369 230 9963 https jlso tec trade...

Page 2: ...g connector EN 175301 803 A 25 4 2 3 Sensor plug M12x1 4 pole 26 4 2 4 Fixed connecting cable 26 5 Adjusting the Switching Unit 27 5 1 Contact type 27 5 1 1 Standard contact 27 5 1 2 Change over conta...

Page 3: ...sion VH X is designed for application in explosive atmospheres The ignition energy of the explosive atmosphere should not be below 60 J Please observe the following separation of zones The constructio...

Page 4: ...witch and the monitored system only use JLSO flow switches for minimum or maximum monitoring of the flow of liquids Always follow and adhere to the flow switch installation instructions Never operate...

Page 5: ...ive loads Details of the protective circuit can be requested from the manufacturer 3 Material Specifications of Wetted Components Type VH M 1 1 1 VH M 1 1 C VH M 1 1 1X VH M 3 3 3 VH M 3 3 3X VH M P 1...

Page 6: ...re desired Please make sure that there are no external magnetic fields in the immediate vicinity of the flow switch since these can impair device functioning Fig 2 There is an arrow on the flow switch...

Page 7: ...tallation with the help of brass soldering threaded nipples or stainless steel welding threaded nipples including O ring V 05M V 06M up to DN 50 V 07M up to DN 50 Fig 4 V 06M from DN 50 V 07M from DN...

Page 8: ...before connecting the wires of the mains cable CAUTION Ensure that the maximum electrical contact load specified on the type plate is never exceeded otherwise the reed contact integrated in the switc...

Page 9: ...unction box pos 2 Tighten the cable gland PG 9 pos 5 Place the junction box pos 2 on the connector pos 1 and retighten the central screw pos 6 Fig 7 Fig 8 Fig 9 Fig 10 To guarantee the protection clas...

Page 10: ...ing to the connection diagram see Fig 13 or Fig 14 Standard contact Flow switch version VH3 VK3 Flow switch version VH3 X Fig 13 To prevent electrostatic charging the VH3 X devices have to be connecte...

Page 11: ...wise agreed with the customer the switching unit is factory set as a make contact i e the reed contact opens if the set switching point is exceeded 5 1 2 Change over contact only for VH3 For flow swit...

Page 12: ...ried out on the basis of the arrow length Movement towards the arrow head Switching point is set to lower flow rate Movement towards the arrow tail Switching point is set to higher flow rate Carefully...

Page 13: ...wise agreed with the customer the switching unit is factory set as a make contact i e the reed contact opens if the set switching point is exceeded 5 1 2 Change over contact only for VH3 For flow swit...

Page 14: ...deviate from the details in these instructions Please observe the details on the type plate Reduced pressure level for devices with copper pipe section Please observe the details on the type plate 8...

Page 15: ...rate m h DN 50 30 25 DN 80 80 65 DN 100 150 100 V 05M mounting length 51 mm DN 150 200 170 DN 100 100 40 DN 150 150 95 V 06M mounting length 111 mm DN 200 200 160 DN 50 30 DN 80 100 DN 100 150 V 01M...

Reviews: