INSTALLATION AND OPERATOR'S

MANUAL

Model number: JS I - x x x x T L se r i e s f o r A u s t r a l i a

Rev. 1.4

Summary of Contents for JSI-1500TL

Page 1: ...www JFY tech com Solar Inverters INSTALLATION AND OPERATOR S MANUAL Model number JSI xxxxTL series for Australia Rev 1 4 ...

Page 2: ...1 2 Falcon Tang 22 03 2012 Increase the information for JSI 3600TL S 1 3 Falcon Tang 12 09 2012 Cancel the accessory of special RS 232 cable 1 4 Falcon Tang 18 01 2013 Increase the information for JSI 2500TL S SAVE THESE INSTRUCTIONS IMPORTANT SAFETY INSTRUCTIONS JFY tech Reproduction and disclosure of the contents of this manual are strictly forbidden without prior authorization of JFY tech ...

Page 3: ...r if you need to know the nearest authorized repair center or qualified service personnel As a qualified service personnel you should know both ac and dc voltage sources are terminated inside this units Each circuit must be individually disconnected before servicing Read and understand all the instructions contained in this manual and become familiar with the safety symbols in the relevant paragra...

Page 4: ... floating way i e with positive and negative terminal not connected to the ground The equipment is provided with several labels some of them with a yellow background which are related to safety issues Make sure to read the labels and fully understand them before installing the equipment The symbols are Equipment grounding conductor Main grounding protective earth PE Alternate Current AC value Dire...

Page 5: ...ut 13 3 CONTROL PANEL FUNCTIONS 13 3 1 Operate the Function Key 14 3 2 General LCD Display Information 16 4 INVERTER START UP AND OPERATION 17 5 COMMUNICATIONS 18 5 1 Data communications with RS232 18 5 2 Data communications with RS485 optional 18 5 2 1 RS485 Serial Port 18 5 2 2 RJ45 Connectors 19 5 2 3 RS485 Daisy Chain 19 5 3 Monitor Inverter 21 6 MAINTENANCE 21 7 TROUBLE SHOOTING 22 8 SPECIFIC...

Page 6: ... OVERVIEW 1 1 Machine Overview Front View Bottom View Fig 1 Overviews of inverter Control and display panel PV input DC switch optional RS232 outlet RS485 inlet and outlet optional AC terminals cover AC terminals is inside ...

Page 7: ...2pcs 4pcs 5 Socket head wrench 1pcs 6 DC socket assembly 1set 2set 3set 7 RS 485 sockets one with 120 ohm terminal resistor Optional 8 Instruction manual 1pcs 9 Monitor software CD 1pcs 10 Warranty sheet 1pcs JSI xxxxTL series include JSI 1500TL JSI 1500TL S JSI 2000TL JSI 2000TL S JSI 2500TL JSI 2500TL S JSI 3000TL JSI 3000TL S JSI 3600TL JSI 3600TL S JSI 5000TL JSI 5000TL S JSI 6000TL and JSI 60...

Page 8: ... to verify damage If the inspection reveals damage to the inverter please call your local supplier or the authorized distributor They will determine if the equipment should be returned for repair They will also provide instructions on how to get the equipment repaired It is the customer s responsibility to file a claim with the carrier Failure to file a claim with the carrier may void all warranty...

Page 9: ...d in the Fig 3 Step2 Fix the mounting frame as illustrated in the Fig 4 by the screws then hang the inverter on the mounting frame Step3 Fix safety lock screws at left side and right side as illustrated in Fig 5 with the attached socket head wrench Step4 Check the installation conditions For JSI 1500TL S For JSI 2000TL S JSI 2500TL S JSI 3000TL S and JSI 3600TL S ...

Page 10: ... Fix safety lock screws The customer is encouraged to perform the following checks Do not install the solar inverter on a gradient surface Check the upper straps of solar inverter and ensure it to fit on to the bracket Ensure safety lock screws M5 socket head cap screws to insert into the mounting frame through inverter s heatsink ...

Page 11: ...llows Fig 6 The PV system diagram A PV Panels Provide DC power to inverter B Solar inverter Converts DC Direct Current power from PV panel s to AC Alternating Current power Because Inverter is grid connected it controls the current amplitude according to the PV Panel power supply Inverter always tries to convert the maximum power from your PV panel s C DC Switch and AC Switch DC switch is between ...

Page 12: ...le provided by JFY tech G RS485 daisy chain communication for one or more inverters H AC TERMINAL three blocks in right hand Connected to AC Grid 2 5 Connecting to the AC Grid Utility A Measure AC grid utility voltage and frequency It should be 230VAC or 220VAC 50Hz and single phase B Open AC Switch between solar inverter and AC Grid Utility C Open AC terminals cover and connect AC wires on AC ter...

Page 13: ...hen DC Switch to the terminals of inverter please make sure the polarity is correct Incorrect polarity connection could permanently damage the unit Please confirm short circuit current of the PV string The total short circuit current of the PV string should be less than the inverter s maximum DC input current E High voltages exist when the PV panel is exposed to the sun To reduce risk of electric ...

Page 14: ...ction Key Used to set different parameter and display language for the inverter F Description of inverter Note To save power the LCD display s backlight automatically turns off after 10 seconds 3 1 Operate the Function Key To view the operating data of the inverter you can press the Function Key Of course the data also will automatically and periodically display To set different display contrast a...

Page 15: ...www JFY tech com 15 To lockup or unlock display message as follows ...

Page 16: ...ng code Auto Test State Auto Testing Protection auto test Program State Programming Update Software Main Operating Messages In LCD STATE DISPLAY CONTENT COMMENTS Normal Operation JFY TECH Abbr company name WWW JFY TECH COM JFY TECH s website JSI xxxTL The inverter model Ver Jx x The FW version SN xxxxxxx The Serial Number Etoday xx xkWh The energy today Etotal xxxxkWH The total energy in lifetime ...

Page 17: ...de just enough voltage to minimum requirements of the internal controller unit Waiting When the PV string DC voltage is greater than 100V The inverter enters a waiting state and attempts to connect to the grid Normal When PV string DC voltage is greater than 150V Inverter operates in the normal state The Inverter will keep MPPT function and deliver power to AC Grid when it is in normal operation M...

Page 18: ... sensor fault DC current sensor fault E14 GFCI failure GFCI Device is damaged 5 COMMUNICATIONS 5 1 Data communication with RS232 Fig 10 RS232 serial port Open the cover of RS232 serial port connect solar Inverter and computer by RS232 cable By the way the communication distance should be below 10m If your computer doesn t have any RS232 port only has USB ports please buy a RS232 USB converter for ...

Page 19: ...h RJ45 connector another socket is for output ethernet cable with RJ45 connector The output ethernet cable reaches the following unit RS485 pin definition is as follows RJ45 connectors Pin Signal Name Description 1 Not Used 2 Not Used 3 RTN Signal Return Common reference for logical signals 4 Not Used 5 Not Used 6 Not Used 7 TR Data Line Required for RS485 communication 8 TR Data Line Required for...

Page 20: ...st one in the chain please draw out the terminal resistor and use it as a vacant RJ45 socket In order to ensure that the communication on the RS485 line is very safe JFY tech recommends connecting an isolating RS232 485 adapter between the first inverter in the daisy chain system and the computer Of course non isolating RS232 485 adapter can also work The following diagram shows how to connect mul...

Page 21: ...or that is installed from the attached CD the user can monitor the inverters The right side of the main interface is the detailed information of inverter As to more detailed setting methods and other functions please refer to JFY communicator user s manual in the CD 6 MAINTENANCE The inverter is maintenance free Take it easy for its daily operation ...

Page 22: ...e impedance must be greater than 2MΩ E02 Ileak error The leakage current is too high Unplug the inputs from the PV string and check the peripheral AC system E03 Grid fault Make sure grid voltage and frequency meet the specifications NOTE During periods of little or no sunlight the solar inverter may continuously start up and shut down This is due to insufficient power generated to operate the cont...

Page 23: ...x input current total 10A Output Data Nominal AC output power 1500W Max AC power 1650W Max output current 7 9A AC grid voltage range 206 270Vac AC grid frequency range 49 25 50 75Hz Power factor cos φ 0 99 THDI at nominal output power 3 AC connection Single phase Max efficiency 96 5 Euro efficiency 95 5 MPPT efficiency 99 6 General Data Dimensions W D H in mm 345 152 315 Weight 12Kg Operating temp...

Page 24: ... Data Nominal AC output power 2000W 2490W Max AC power 2200W 2490W Max output current 10 5A 12 5A AC grid voltage range 206 270Vac 206 270Vac AC grid frequency range 49 25 50 75Hz 49 25 50 75Hz Power factor cos φ 0 99 0 99 THDI at nominal output power 3 3 AC connection Single phase Single phase Max efficiency 97 97 Euro efficiency 96 2 96 1 MPPT efficiency 99 6 99 6 General Data Dimensions W D H i...

Page 25: ...ta Nominal AC output power 3000W 3600W Max AC power 3400W 3600W Max output current 15 7A 16 0A AC grid voltage range 206 270Vac 206 270Vac AC grid frequency range 49 25 50 75Hz 49 25 50 75Hz Power factor cos φ 0 99 0 99 THDI at nominal output power 3 3 AC connection Single phase Single phase Max efficiency 97 2 97 3 Euro efficiency 96 4 96 5 MPPT efficiency 99 6 99 6 General Data Dimensions W H D ...

Page 26: ...t Data Nominal AC output power 4600W 6000W Max AC power 5000W 6000W Max output current 24A 31 2A AC grid voltage range 206 270Vac 206 270Vac AC grid frequency range 49 25 50 75Hz 49 25 50 75Hz Power factor cos φ 0 99 0 99 THDI at nominal output power 3 3 AC connection Single phase Single phase Max efficiency 97 6 97 6 Euro efficiency 97 97 1 MPPT efficiency 99 6 99 6 General Data Dimensions W H D ...

Page 27: ...orized distributors will replace any products or parts of the product during the warranty period proved to be defective in design or manufacture The following cases will be excluded from the warranty the Distributors are liable for investigation of the following 1 Warranty Card not being sent back to distributor or JFY tech 2 Product modified or design changed or parts replaced not approved by JFY...

Page 28: ... brief error description to the JFY tech s distributors If we agree to a replacement we generally send an equivalent replacement device according to model and age the remainder of the warranty entitlement will be transferred to the replacement device In this case you do not receive a new certificate since your entitlement is documented at JFY tech The replacement will be packaged appropriately for...

Page 29: ...10 JFY tech CONTACT INFORMATION Shenzhen JingFuYuan Tech Co LTD ADD 5th Floor 12th Block Nangang Second Industrial Park Nanshan District Shenzhen P R China Tel 86 755 26632536 Fax 86 755 26505986 Email support jfy tech com ...