JetMove 204-480
5.1 Electrical Specification
Jetter AG
35
5
Technical Data
5.1
Electrical Specification
Electrical Specification
Rated voltage supply
• 3-phase
Direct supply V
rms
= 3x400/480 V
Common mode of the voltage 2 % max.
(voltage dips 10 ms max. at continuous
power)
• 48 ... 62 Hz
(Frequency change 2 % / s max.)
Power supply tolerance
-15 % ... + 10 %
Inrush current limitation
< 10 A limited to < 500 ms during the
switch-on sequence
Overload protection
For each phase an external overload
protection is required, for example
– circuit-breaker 10 A C
– fuse 10 A M (medium time lag)
– motor circuit breaker 10 A
For
systems with UL approval
use
overload protection devices that are UL
listed (acc. to UL 508)(NKJH) self
protected combination motor controller
(Specification: 480 V, 16 A).
The JetMove 204-480 is suitable for use on
a circuit capable of delivering not more
than 50 kA (symmetric) at 600 Volt eff.
max.
Supply cable
Cable size
Material
Temperature class
4 * 1.5 mm
2
min. (AWG 16)
Copper
> 60 °C
Maximum output voltage of the
motor
850 V
Motor output current at an ambient
temperature of 45 °C
Nominal current: I
rms
= 4 A
Peak current for a max. period of 3
minutes:
I
rms
= 8 A
(The duration depends on the temperature
of the heat sink)
See "Note 1!" on page 38.
Continuous power of motor
2 kW (1.5 hp)
Summary of Contents for JM-204-480
Page 1: ...User Manual JM 204 480 Digital Servo Amplifier 60870618 We automate your success...
Page 34: ...4 Physical Dimensions 34 Jetter AG...
Page 42: ...5 Technical Data 42 Jetter AG...
Page 82: ...82 Jetter AG...
Page 86: ...86 Jetter AG...
Page 106: ...13 Safe Standstill Option 106 Jetter AG...
Page 116: ...15 Ordering Information 116 Jetter AG...
Page 117: ...JetMove 204 480 Appendices Jetter AG 117 Appendices...
Page 118: ...Appendices 118 Jetter AG...