Application-oriented manual – Control of alphanumeric HMIs (LCD) and printers
12
Specification
Connecting cable
Parameter
Description
Number of cores
6
Recommended core
cross section
0.14 mm
2
Maximum cable length
400 m
Cable shielding
■
Complete, not paired
■
The shield must connect to the connector enclosures on both ends of the ca-
ble with the greatest possible surface area. Place the shield as follows:
– Bundle the shielding.
– Clamp it under a strain relief.
– Wrap it with copper foil.
Wiring diagram
The interface cable assembly no. 192 xM is wired as follows:
Controller
Shield
HMI
SER/X11
2
1
5
4
3
6
7
8
8
1
15
9
Connect shield with the greatest possi-
ble surface area
A metallized housing is required