3 Fixed Software Bugs
Initializing by means of LioN-S Modules
In case of CAN system bus configurations consisting of LioN-S and JX2-/JX3
modules, not all connected JX2-/JX3 modules are commissioned.
Effects of this Bug
The following revisions are affected by this bug:
Affected Revisions
OS revision
JX6-SB(-I)
JC-24x
JM-D203-JC24x
< 2.21.0.00
< 3.26.0.00
< 1.13.0.00
Hardware revision
not relevant
Configuration or operating mode
not relevant
Comment 698
Carry out the following steps for a workaround:
Remedy / Workaround
Step
Action
1
Start the CAN system bus
2
Re-start the CAN system bus without de-energizing the expansion
modules
Starting from the following revisions this bug has been fixed:
Bug Fix
OS revision
JX6-SB(-I)
JC-24x
JM-D203-JC24x
2.21.0.00
3.26.0.00
1.13.0.00
Hardware revision
not relevant
Configuration or operating mode
not relevant
16
Jetter AG