IMPORTANT:

Read all instructions carefully before starting installation. Failure to follow these instructions 

may result in a fire hazard and will void the warranty.

Due to continued product improvement, The Fireplace Ltd reserves the right to change product specifications without prior notification. 

Please check to ensure you have the latest installation instructions. 

TYPICAL JETMASTER IN-BUILT TIMBER FRAME & MASONRY 

FIREBOX   INSTALLATION INSTRUCTIONS  FOR  

QUADRO OUTDOOR WOOD FIRE & BBQ GRILL 

08/2022

1

Summary of Contents for QUADRO 1050

Page 1: ...id the warranty Due to continued product improvement The Fireplace Ltd reserves the right to change product specifications without prior notification Please check to ensure you have the latest installation instructions TYPICAL JETMASTER IN BUILT TIMBER FRAME MASONRY FIREBOX INSTALLATION INSTRUCTIONS FOR QUADRO OUTDOOR WOOD FIRE BBQ GRILL 08 2022 1 ...

Page 2: ...Front Face Margin Firebox Installation Masonry Cavity Plan Section Firebox Installation and Margins Flue Installation Flue Penetration Chimney Chase Air Ventilation Floor Protector requirements Hebel Cut Out Schedule 3 4 4 5 6 7 8 9 10 11 12 13 14 2 Head Office Showroom 12 Tawari St Mt Eden Auckland Ph 09 623 6990 thefireplace co nz ...

Page 3: ... OR AEROSOLS TO START OR REKINDLE THE FIRE OR IN THE VICINITY OF THIS APPLIANCE WHEN OPERATING DO NOT STORE FUEL WITHIN HEATER INSTALLATION CLEARANCES WHEN OPERATING THIS APPLIANCE AS AN OPEN FIRE USE A FIRE SCREEN THIS APPLIANCE SHOULD BE MAINTAINED AND OPERATED AT ALL TIMES IN ACCORDANCE WITH THESE INSTRUCTIONS USE OF SOME TYPES OF PRESERVATIVE TREATED WOOD AS A FUEL CAN BE HAZARDOUS IF INSTALLE...

Page 4: ...is raised it must be placed on top of a 75mm Hebel panel which is placed on top of a steel structure or masonry blocks A TIMBER BASE IS NOT ACCEPTABLE Please note that these dimensions based on Hebel Block margins are the absolute minimum sizes widths A B maybe increased if desired Table 2 TIMBER FRAME DIMENSIONS JETMASTER FIREBOX DIMENSIONS 4 Table 1 Note All dimensions are in mm ...

Page 5: ...be bird rodent proofed with permanently fixed screen Rebate to suit tiles or other non combustible material on Floor Protector It is important to ensure the Jetmaster firebox is seated at the required finished Floor Protector level see Table 5 min 25mm from flue pipe casing to combustible material 25 25 Drawing Not To Scale Drawing Not To Scale Optional Finishing Stone Brick Plaster on Brick min 2...

Page 6: ...6 ...

Page 7: ...al wall lining eg Promatect H to cover the extent of the Hebel panel surround shown shaded Directly touching the firebox with any board or plaster finish will cause cracking from heat expansion Allow 2mm minimum space away from the firebox J e t ma s t er Margin Lintel min 300mm Timber Framing 75mm min Hebel Block or 100mm Concrete Note Ensure allowance made for firebox to sit on top of finished F...

Page 8: ...sure a strip of glass rock wool insulation is between the inner hebel leg face and the firebox Nail through stud into hebel leg to secure in place Locate and position firebox fit and seal gather in cavity Earthquake restraints may be positioned by drilling through firebox into the floor protector in a position midway beneath the log pan Two 12mm dynabolts or similar will suffice Do not over tighte...

Page 9: ... Vent Refer to Table 5 for Floor Protector dimension Air Vent min 2 x 100 x 50mm or 80mm diam wall of floor mounted air vents Drawings Not To Scale 9 Note If the appliance is exposed not under protective cover please recess the appliance Min 40mm Max recess 100mm Add recess dimension to B dimension in Table 3 100 700mm recess Allow 5mm gap around all four sides of the firebox to fit Stainless Stee...

Page 10: ...d on Masonry margins are the absolute minimum sizes widths A B maybe increased if desired If you intend on recessing the firebox please add the recess value to Dimension B WARNING Minimum cavity sizes leave NO MARGIN FOR ERROR If the cavity is larger than minimum dimensions A B close up the lateral sides using Hebel block concrete block or similar do not use any combustible material Refer to Table...

Page 11: ... cutting down should be carried out prior to the flue pipe casing being fitted over the flue pipe 7 Before fitting casing cover place the spider in opposition with the spider post facing down between the flue pipe and flue pipe casing Secure spider in position Place the casing cover over the flue pipe press down firmly onto the spider Check airway around the casing cover is clear then secure in po...

Page 12: ... min 2 x 80mm dia or equal square or rectangle shaped area min 25mm gap between flue pipe casing combustible surface EXTERNAL REQUIREMENTS SOLID FUEL Refer to AS NZS2918 2001 4 9 1 Note All external air vents ceiling penetrations must be bird rodent proofed with permanently fixed screens Drawing Not To Scale Minimum 25mm gap between flue pipe casing combustible surface Air Vent min 2 x 80mm diam o...

Page 13: ...ce from flue pipe casing to combustible material must be maintained A Minimum clearance of 200mm above Heat Shield must be maintained CHIMNEY CHASE MINIMUM TRIM OUT MODEL A B C Floor Level 1400 800 75 Raised 500mm 1400 1000 75 A B C A minimum 75mm thickness refers only to Hebel Block for solid fuel installations Minimum 100mm thickness required if poured concrete Table 5 MINIMUM FLOOR PROTECTOR SI...