DOMESTIC SOLID FUEL BURNINGAPPLIANCE – TEST REPORT SUMMARY

CLIENT:

Jetmaster (Vic) Pty Ltd

REPORT NO:

M7100/92

CLIENT REF:

Request by Jetmaster

DATE:

19/8/92

TEST SPECIFICATION:

  Australian Standard 2918:1990, Appendix B

TEST FUEL:

Wood

TEST DATE:

6 August 1992

APPLIANCE:

Model:

Jetmaster Zero Clearance Fireplace

Manufactured by:

Jetmaster (Vic) Pty Ltd

FLUE SYSTEM:

Ventilated single casting flue system

HEARTH:

6mm thick sheet of fibre cement with a layer of 100mm thick clay bricks on top which

extended 300mm in front and 200mm either side of the firebox opening.

TEST INSTALLATION:

The appliance was installed in accordance with the manufacturer’s specifications, Jetmaster

drawing numbers ZC8/92/1 and ZC8/92/2.

The minimum appliance/flue casing clearance from combustible materials was 25mm.

CONCLUSION:

When installed as described above

 the appliance tested complied with the requirements of AS 2918:1990.

Investigation and Report by:          Michael J Greenwood

For William V Yeo

Approved Signatory

Manager

Michael J Greenwood

Materials Services

Product Testing Officer

Laboratory Registration

No: 2326

FOR SOLID FUEL ONLY

JETMASTER AIR VENTILATED

ZERO CLEARANCE FIREPLACE

JM-140(03/10)

JETMASTER (VIC) PTY LTD

ACN 005 872 159   ABN13 659 821 337

444 Swan St. Richmond VIC 3121  PO Box 5051 Burnley 3121

Ph: (03) 9429 5573   Fax: (03) 9427 0031   

Website: www.jetmaster.com.au   Email: [email protected]

Amdel Limited

A.C.N. 008 127 802

MATERIALS SERVICES

Certified to AS 3901 / ISO 9001

31 Flemington Street

Telephone: (08) 372 2700

FREWVILLE SA 5061

Facsimile: (08) 379 6623

DOMESTIC SOLID FUEL BURNINGAPPLIANCE – TEST REPORT SUMMARY

CLIENT:

Jetmaster (Vic) Pty Ltd

REPORT NO:

M7100/92

CLIENT REF:

Request by Jetmaster

DATE:

19/8/92

TEST SPECIFICATION:

  Australian Standard 2918:1990, Appendix B

TEST FUEL:

Wood

TEST DATE:

6 August 1992

APPLIANCE:

Model:

Jetmaster Zero Clearance Fireplace

Manufactured by:

Jetmaster (Vic) Pty Ltd

FLUE SYSTEM:

Ventilated single casting flue system

HEARTH:

6mm thick sheet of fibre cement with a layer of 100mm thick clay bricks on top which

extended 300mm in front and 200mm either side of the firebox opening.

TEST INSTALLATION:

The appliance was installed in accordance with the manufacturer’s specifications, Jetmaster

drawing numbers ZC8/92/1 and ZC8/92/2.

The minimum appliance/flue casing clearance from combustible materials was 25mm.

CONCLUSION:

When installed as described above

 the appliance tested complied with the requirements of AS 2918:1990.

Investigation and Report by:          Michael J Greenwood

For William V Yeo

Approved Signatory

Manager

Michael J Greenwood

Materials Services

Product Testing Officer

Laboratory Registration

No: 2326

FOR SOLID FUEL ONLY

JETMASTER AIR VENTILATED

ZERO CLEARANCE FIREPLACE

JM-140(03/10)

JETMASTER (VIC) PTY LTD

ACN 005 872 159   ABN13 659 821 337

444 Swan St. Richmond VIC 3121  PO Box 5051 Burnley 3121

Ph: (03) 9429 5573   Fax: (03) 9427 0031   

Website: www.jetmaster.com.au   Email: [email protected]

Amdel Limited

A.C.N. 008 127 802

MATERIALS SERVICES

Certified to AS 3901 / ISO 9001

31 Flemington Street

Telephone: (08) 372 2700

FREWVILLE SA 5061

Facsimile: (08) 379 6623

DOMESTIC SOLID FUEL BURNINGAPPLIANCE – TEST REPORT SUMMARY

CLIENT:

Jetmaster (Vic) Pty Ltd

REPORT NO:

M7100/92

CLIENT REF:

Request by Jetmaster

DATE:

19/8/92

TEST SPECIFICATION:

  Australian Standard 2918:1990, Appendix B

TEST FUEL:

Wood

TEST DATE:

6 August 1992

APPLIANCE:

Model:

Jetmaster Zero Clearance Fireplace

Manufactured by:

Jetmaster (Vic) Pty Ltd

FLUE SYSTEM:

Ventilated single casting flue system

HEARTH:

6mm thick sheet of fibre cement with a layer of 100mm thick clay bricks on top which

extended 300mm in front and 200mm either side of the firebox opening.

TEST INSTALLATION:

The appliance was installed in accordance with the manufacturer’s specifications, Jetmaster

drawing numbers ZC8/92/1 and ZC8/92/2.

The minimum appliance/flue casing clearance from combustible materials was 25mm.

CONCLUSION:

When installed as described above

 the appliance tested complied with the requirements of AS 2918:1990.

Investigation and Report by:          Michael J Greenwood

For William V Yeo

Approved Signatory

Manager

Michael J Greenwood

Materials Services

Product Testing Officer

Laboratory Registration

No: 2326

FOR SOLID FUEL ONLY

JETMASTER AIR VENTILATED

ZERO CLEARANCE FIREPLACE

JM-140(03/10)

1

Jetmaster Air Ventilated Zero Clearance Fireplace

DOMESTIC SOLID FUEL BURNING APPLIANCE – TEST REPORT SUMMARY

CLIENT:

 

Jetmaster (Vic) Pty Ltd 

REPORT NO:

 

M7100/92

CLIENT REF: 

Request by Jetmaster 

DATE:

 19/8/92

TEST SPECIFICATION:

  Australian Standard 2918:1990, Appendix B

TEST FUEL:

 Wood 

TEST DATE:

 

6 August 1992

APPLIANCE:

Model:

 

Jetmaster Zero Clearance Fireplace

Manufactured by:

 

Jetmaster (Vic) Pty Ltd

FLUE SYSTEM:

Ventilated single casting flue system

HEARTH:

6mm thick sheet of fibre cement with a layer of 100mm thick clay bricks on top which extended 300mm 
in front and 200mm either side of the firebox opening.

TEST INSTALLATION:

The appliance was installed in accordance with the manufacturer’s specifications, Jetmaster drawing 
numbers ZC8/92/1 and ZC8/92/2.

The minimum appliance/flue casing clearance from combustible materials was 25mm.

CONCLUSION:

When installed as described above

 the appliance tested complied with the requirements of AS 2918:1990.

Investigation and Report by:          Michael J Greenwood

For  William V Yeo                                                   

 

Approved Signatory

Manager 

 

Michael J Greenwood

Materials Services 

 

Product Testing Officer

 

 

Laboratory Registration

 

 

                            No: 2326

 

                                   Amdel 

Limited
 

                        ACN 008 127 

802

MATERIALS SERVICES

Certified to AS 3901 / ISO 9001

31 Flemington Street           Telephone: (08) 372 2700

FREWVILLE SA 5061         Facsimile: (08) 379 6623

Summary of Contents for 400

Page 1: ...13 659 821 337 444 Swan St Richmond VIC 3121 PO Box 5051 Burnley 3121 Phone 03 9429 5573 Fax 03 9427 0031 Website www jetmastervic com au Email info jetmastervic com au INSTALLATION OPERATING I N S T...

Page 2: ...ons 2 4 Framing Specifications 5 6 OPEN WOOD FIREPLACE Minimum Flue Height 7 Open Gas Jetmaster 9 Open Wood Jetmaster 10 12 Open Gas Jetmaster Operating and Maintenance Instructions For wood burning J...

Page 3: ...rvices Product Testing Officer Laboratory Registration No 2326 FOR SOLID FUEL ONLY JETMASTER AIR VENTILATED ZERO CLEARANCE FIREPLACE JM 140 03 10 Amdel Limited A C N 008 127 802 MATERIALS SERVICES Cer...

Page 4: ...requirements c Maintain a minimum clearance between outer flue and combustible materials of 50mm d Provide flashing where flue penetrates roof and fit cowl 3 Framing a Construct timber frame laying st...

Page 5: ...t aces m e Zero Clearance Timber Construction ZERO CLEARANCE TIMBER CONSTRUCTION 3 Models 400 to 700D 26mm Models 850 to 1500 100mm...

Page 6: ...Zero Clearance Timber Construction ZERO CLEARANCE TIMBER CONSTRUCTION 4...

Page 7: ...700SH 700 900 430 725 930 850 300 250 200 700D 700 900 475 775 985 850 325 275 225 850 850 1050 525 825 1060 1000 350 300 250 1050 1050 1250 570 875 1160 1200 400 350 300 DIMENSIONS IN MILLIMETRES MOD...

Page 8: ...500 N A 850 1100 1300 550 N A 1050 1300 1400 600 N A CHART 3 ZERO CLEARANCE JETMASTER WITH RECESSED FASCIA ALLOW ADDITIONAL DEPTHS AS FOLLOWS Recessed tiled fascias 160mm Recessed arched fascias 140m...

Page 9: ...nearest part of the roof if the flue cowl is at least 510mm from a neighbouring structure If less than 510mm the flue terminal must be located at least 500mm above that structure Refer to AS5601 2004...

Page 10: ...g After installing the appliance check that the chimney flue system draws well Jetmaster recommends that all gas fires be serviced every 2 years All gas units must be fitted by a licensed gas fitter I...

Page 11: ...fires require fresh air vents as per Clause 6 10 9 5 in AS NZS5601 1 2013 One or more ventilation openings with a combined free ventilation area of not less than the equivalent cross sectional area of...

Page 12: ...cked to ensure that adequate capacity is available for the additional load Information Required Prior To Pipe Sizing The following information is required prior to pipe sizing a The type of gas includ...

Page 13: ...n close it will depend on the type of wood used and the general weather conditions Experience will soon show you how far how ever the damper should never be closed more than half way 6 When the fire h...

Page 14: ...ces Softer woods Pines etc burn fast leaving a lot of ash and creosote Hard woods Red Gum etc can be best used when mixed with medium woods and should not be used to start a fire 2 A split log will bu...

Page 15: ...13...

Page 16: ...JM 121 07 18 14 Specifications subject to change contact Jetmaster prior to commencement...

Reviews: