Rear discharge

This range hood can be vented directly out the back using the 
3¼" x 10" (8.3 cm x 25.4 cm) rectangular damper (supplied) along 
with a 3¼" x 10" (8.3 cm x 25.4 cm) rectangular vent system (not 
supplied). See “Install Range Hood” section for details for 
installing the damper.

Calculating Vent System Length

To calculate the length of the system you need, add the 
equivalent feet (meters) for each vent piece used in the system. 

3¹⁄₄

" x 10" (8.3 cm x 25.4 cm) Vent System

Example vent system

Electrical Requirements

Observe all governing codes and ordinances. 
Ensure that the electrical installation is adequate and in 
conformance with National Electrical Code, ANSI/NFPA 70 (latest 
edition), or CSA Standards C22.1-94, Canadian Electrical Code, 
Part 1 and C22.2 No. 0-M91 (latest edition) and all local codes 
and ordinances.
If codes permit and a separate ground wire is used, it is 
recommended that a qualified electrician determine that the 
ground path is adequate.
A copy of the above code standards can be obtained from:

National Fire Protection Association

1 Batterymarch Park

Quincy, MA 02169-7471

CSA International

8501 East Pleasant Valley Road

Cleveland, OH 44131-5575

A 120 volt, 60 Hz., AC only, 15-amp, fused electrical circuit 
is required.

If the house has aluminum wiring, follow the procedure 
below:

1.

Connect a section of solid copper wire to the pigtail 
leads.

2.

Connect the aluminum wiring to the added section of 
copper wire using special connectors and/or tools 
designed and UL listed for joining copper to aluminum.

Follow the electrical connector manufacturer's recommended 
procedure. Aluminum/copper connection must conform with 
local codes and industry accepted wiring practices.

Wire sizes and connections must conform with the rating of 
the appliance as specified on the model/serial/rating plate. 
The model/serial/rating plate is located behind the left filter 
on the rear wall of the range hood.

Wire sizes must conform to the requirements of the National 
Electrical Code, ANSI/NFPA 70 (latest edition), or CSA 
Standards C22. 1-94, Canadian Electrical Code, Part 1 
and C22.2 No. 0-M91 (latest edition) and all local codes 
and ordinances.

Roof Venting

Wall Venting

(top or rear discharge)

A. Roof cap
B. 3

¹⁄₄

" x 10" (8.3 x 25.4 cm) 

rectangular metal vent

A. Wall cap
B. 3

¹⁄₄

" x 10" (8.3 x 25.4 cm) 

rectangular metal vent

Vent Piece

3

¹⁄₄

" x 10" (8.3 cm x 25.4 cm)

90° elbow

5.0 ft
(1.5 m) 

3

¹⁄₄

" x 10" (8.3 cm x 25.4 cm) 

flat elbow

12.0 ft
(3.7 m)

3

¹⁄₄

" x 10" (8.3 cm x 25.4 cm) 

wall cap

0.0 ft
(0.0 m)

A

B

A

B

Maximum Recommended Length

= 35 ft (10.7 m)

1 - 90° elbow

= 5.0 ft (1.5 m)

8 ft (2.4 m) straight

= 8.0 ft (2.4 m)

1 - wall cap

= 0.0 ft (0.0 m)

Length of 3

¹⁄₄

" x 10" (8.3 cm x 25.4 cm) 

system

= 13.0 ft (3.9 m)

Wall cap

 

   

3

¹⁄₄

" x 10"

(8.3 x 25.4 cm) 

elbow

2 ft

(0.6 m)

6 ft (1.8 m)

Summary of Contents for JXU9130WP

Page 1: ...536 6247 or visit our website at www jennair com In Canada call 1 800 JENNAIR 1 800 536 6247 or visit our website at www jennair ca Instructions d installation et Guide d utilisation et d entretien A...

Page 2: ...TTE 25 Nettoyage 25 SCH MA DE C BLAGE 26 ASSISTANCE OU SERVICE 27 Au Canada 27 Accessoires 27 GARANTIE 28 RANGE HOOD SAFETY You can be killed or seriously injured if you don t immediately You can be k...

Page 3: ...3 IMPORTANT SAFETY INSTRUCTIONS READ AND SAVE THESE INSTRUCTIONS...

Page 4: ...installer s responsibility to comply with installation clearances specified on the model serial rating plate The model serial rating plate is located behind the left filter on the rear wall of the ve...

Page 5: ...as close as possible to where the vent system enters the heated portion of the house Makeup Air Local building codes may require the use of makeup air systems when using ventilation systems greater th...

Page 6: ...aluminum wiring follow the procedure below 1 Connect a section of solid copper wire to the pigtail leads 2 Connect the aluminum wiring to the added section of copper wire using special connectors and...

Page 7: ...g access hole See Step 2 for wiring hole location instructions 1 Determine and clearly mark a vertical centerline on the wall and cabinet in the area the vent opening will be made 2 To wire through to...

Page 8: ...2 cm and a suggested maximum of 36 91 4 cm above the range to the bottom of the hood Mark a reference line on the wall 3 Using 2 or more people center the hood on the vertical centerline then align th...

Page 9: ...e damper and the wall cap do not interfere with each other Remove the damper from the 3 x 10 8 3 x 25 4 cm rectangular vent connector if they interfere 5 Using 2 or more people lift the hood into fina...

Page 10: ...minutes after the cooking is complete to clear all smoke and odors from the kitchen The hood controls are located on the right hand underside of the range hood Range Hood Controls Operating the light...

Page 11: ...l grease filters as needed in a dishwasher or hand wash in a hot detergent solution to clean To Reinstall Metal Grease Filters 1 Grasp filter handles and place rear of filter into rear track 2 Push do...

Page 12: ...12 WIRING DIAGRAM VARISTOR BK BK BK BK BK WH WH WH WH BU BK GY RD WH BU BK WH WH BU BU GY GY BK BK RD RD YL YL BR BR YL GN YL GN WH BK WH BK YL GN BK BK WH WH YL GN YL GN WH BK BU...

Page 13: ...iances with any questions or concerns at Jenn Air Brand Home Appliances Customer eXperience Center 553 Benson Road Benton Harbor MI 49022 2692 Please include a daytime phone number in your corresponde...

Page 14: ...rs preservation solutions etc 5 Defects or damage caused by the use of non genuine Jenn Air parts or accessories 6 Conversion of products from natural gas or L P gas 7 Damage from accident misuse abus...

Page 15: ...re appareil m nager Assurez vous de toujours lire tous les messages de s curit et de vous y conformer AVERTISSEMENT DANGER Voici le symbole d alerte de s curit Ce symbole d alerte de s curit vous sign...

Page 16: ...ue d incendie et vacuer ad quatement les gaz veiller acheminer l air aspir par un conduit jusqu l ext rieur ne pas d charger l air aspir dans un espace vide du b timent comme une cavit murale un plafo...

Page 17: ...s dispositions de tous les codes et r glements en vigueur Confier l installation de la hotte un technicien qualifi C est l installateur qu incombe la responsabilit de respecter les distances de s para...

Page 18: ...les brides de serrage Le circuit d vacuation doit comporter un clapet anti reflux Si la bouche de d charge murale ou par le toit comporte un clapet ne pas utiliser le clapet fourni avec la hotte de cu...

Page 19: ...rs un mur Voir la section Installation de la hotte pour les d tails pour l installation d un clapet anti reflux REMARQUE On d conseille l emploi d un conduit flexible Un conduit flexible peut susciter...

Page 20: ...ique de l appareil est situ e derri re le filtre sur la paroi arri re de la hotte Le calibre des conducteurs doit tre conforme aux exigences du National Electrical Code de la plus r cente dition de la...

Page 21: ...une scie guichet pour d couper l ouverture rectangulaire pour le passage du conduit d vacuation 4 R p ter les tapes 1 3 pour la face inf rieure du sommet du placard D charge travers le mur sous un pla...

Page 22: ...u circuit d vacuation Installer le syst me d vacuation avant la hotte Voir la section Exigences concernant l vacuation Achever la pr paration 1 D terminer la hauteur appropri e pour le cordon d alimen...

Page 23: ...pour un montage sur le mur pour que les vis soient dans la partie troite des trous de fixation des vis Serrer les vis de montage en s assurant que les vis sont dans la partie troite des trous de fixat...

Page 24: ...eurs minutes apr s l ach vement d une cuisson pour pouvoir vacuer de la cuisine toute trace d odeur de cuisson vapeur ou fum e Les commandes de la hotte sont situ es sous celle ci du c t droit Command...

Page 25: ...tergent chaude pour les nettoyer R installation des filtres graisse m talliques 1 Saisir les poign es du filtre et ins rer l arri re du filtre dans la rainure arri re 2 Tirer sur la poign e arri re et...

Page 26: ...LAGE JA VE N JA VE BL JA VE BL N BL N N BL N BU BU BU GRIS GRIS N N R R BL BL JA JA MAR MAR JA VE JA VE N BL N N BL BL BL N N BL CONTACTEUR LAMPE CONTACTEUR MOTEUR BU N BU N GRIS R BL VARISTANCE Bo ti...

Page 27: ...n Air sont form s pour remplir la garantie des produits et fournir un service apr s la garantie partout au Canada Caract ristiques et sp cifications de notre gamme compl te d appareils m nagers R f re...

Page 28: ...lisation de pi ces ou accessoires Jenn Air non authentiques 6 Conversion de votre produit du gaz naturel ou du gaz de p trole liqu fi 7 Dommages caus s par accident m susage abus incendie inondations...

Reviews: