RS T4F Diesel Generator | G70RS – G125RS
15
This button places the module into its AUTO MODE. This mode allows the module to
control the function of the generator automatically. The module monitors numerous
start requests via digital input, PLC and MSC link and when one has been made, the set is
automatically started. Once the generator is available, the module automatically instructs
the generator to synchronise and once in sync, to be place the generator on load (‘Close
Generator Output’ becomes active). Upon removal of the starting signal, the module
starts the Return Delay Timer and once expired, the load is automatically ramped off the
generator and then it is taken off load (‘Close Generator Output’ becomes inactive). The
generator then continues to run for the duration of the Cooling Timer until it stops. The
module then waits for the next start event.
This button is only active in the STOP/RESET mode, MANUAL mode. Pressing the Start
button in Stop/Reset Mode powers up the engine’s ECU but does not start the engine. This
can be used to check the status of the CAN communication and to prime the fuel system.
Used for navigating the instrumentation, event log and configuration screens.
Used to silences the audible alarm in the controller, de-activates the audible alarm output
(if configured) and illuminates all of the LED on the module’s facia as a lamp test function.