SECTION 4-1: CONFIGURE PROGRAMMER
Push <1> from the CONFIG-TUNE-CALIBRATE Menu.
Page 1: COMPUTER INTERFACE.
Line 1: Display only
Line 2: Select Interface Type.
RS232 (not address sensitive)
RS422 and Address #
488 and Address # (optional interface)
Line 3: Select FRONT PANEL (LCL) or
EXT_COMPUTER (RMT)
EXT_RAMP_SOAK
(RSR)
Note: Unit must be in STP mode to make changes.
Line 4: RS232 or RS422 MODE:
Field 1 BAUD Rate: Select 300, 600, 1200, 2400, 4800, 9600, 19200 or 38400.
Field 2 PARITY: Select 8BIT NONE, 7 BIT EVEN, 7 BIT ODD, 7 BIT MARK, 7 BIT SPEC.
Factory Defaults: 9600 Baud, 8 BIT NONE>
488 MODE
(IEEE-488): Select END OF LINE: LF or CR/LF. Factory Default LF
Page 2: CONFIGURE PROGRAMMER.
Line 1: Display Only
Line 2: Select
TWO CHANNEL
SINGLE
CHANNEL
FASTTRAC_PASSTHRU
FASTTRAC_STANDARD
Lines 3 & 4
Blank in Two and Single Channel
Modes.
Lines 3 & 4 in FASTTRAC_PASSTHRU and
FASTTRAC_STANDARD
Modes:
Select the LO and HI Temp Limits.
These values represent the lowest and highest setpoints
CH2 will receive from CH1, regardless of the Setpoint
value entered for CH1.
Applies to both Program and Manual Modes of
FastTRAC operation.
FASTRACK_TEMP_LIMIT values entered in the Standard or PassThru mode are common to both modes.