Recalibration

Each gauge is individually tested and calibrated prior to  shipment. Due 

to its sensitivity, the gauge may need to be  “zeroed in” prior to usage.

Adjusting Gauge Recalibration to Zero

1.  For 2-1/2”: remove lens or for 3-1/8”: remove lens plug
2.  Turn recalibration screw 

slightly

 in the opposite direction that 

 pointer is to be moved. Maximum recalibration screw adjustment 

is half turn. Over adjustment will permanently destroy calibration.

3.  Replace lens/lens plug

Gauges are sensitive instruments—over adjustment  and/or being subjected to pressures 

over dial range  are not covered under warranty terms.

Evacuation/Charging

CAUTION: 

Always consult 

manufacturer service manual 

or instruction sheet for 

recommended procedures

MANIFOLD

COMPRESSOR

A

B

C

D

E

F

LOW SIDE HIGH SIDE

EVACUATION 

PORT

CHARGING 

PORT

DISCHARGE 

SERVICE VALVE

SUCTION 

SERVICE VALVE

BLUE

RED

BLACK

YELLOW

RED

BLUE

To observe operating pressures

Closed

Closed

Closed

Closed

  Back seated and     

  cracked open

  Back seated and  

  cracked open

To charge refrigerant through 

suction valves

Open

Closed

Closed

Open

  Back seated and  

  cracked open

  Front seated

To charge oil through suction 

valve

Open

Closed

Open

Closed

  Back seated

  Front seated

To charge liquid refrigerant 

through discharge valve

Closed

Open

Closed

Open

  Midway open

To build low pressure; for 

control setting or leak detecting

Open

Open

Closed

Closed

  Back seated and  

  cracked open

  Midway open

To purge refrigerant from 

discharge valve

Closed

Open

Closed

Open

  Back seated and  

  cracked open

To evacuate with auxiliary 

vacuum pump

Open

Open

Open

Closed

  Midway open

  Midway open