Technical specifications
IP 24
20
16
12
8
JÄSPI Inverter Nordic – 3x400V
Heating
Output data according to EN 14511, partial load
1)
13.50/4.70/2.87
10.13/3.33/3.04
7.35/2.43/3.02
5.17/1.72/3.00
kW/kW/-
-7/35 Capacity / Power input / COP
EN 14511
9.95/2.36/4.22
7.80/1.79/4.36
5.21/1.22/4.27
4.03/0.91/4.43
kW/kW/-
2/35 Capacity / Power input / COP
EN 14511
10.41/2.88/3.61
7.97/2.24/3.56
5.27/1.49/3.54
4.07/1.16/3.51
kW/kW/-
2/45 Capacity / Power input / COP
EN 14511
5.17/1.01/5.11
5.17/1.01/5.11
3.54/0.69/5.12
3.57/0.78/4.57
kW/kW/-
7/35 Capacity / Power input / COP
EN 14511
5.49/1.33/4.14
5.49/1.33/4.14
3.64/0.91/4.00
3.66/0.98/3.74
kW/kW/-
7/45 Capacity / Power input / COP
EN 14511
Max
Max
Max
Max
Outd. temp: / Sup-
ply temp.
Cooling
8.10/3.50/2.31
7.09/2.72/2.61
4.69/1.70/2.76
3.80/1.28/2.97
35 / 7 °C
Output data according to EN 14511
Δ
T5K
Capacity/power input/EER
9.26/3.64/2.54
8.19/2.83/2.90
5.44/1.73/3.15
5.10/1.37/3.73
35 / 18 °C
Electrical data
400V 3N ~ 50Hz
Rated voltage
11
9.5
7
6
A
rms
Max operating current, heat pump
10
8.5
6
5
A
rms
Max operating current, compressor
80
68
45
40
W
Max output, fan
13
10
10
10
A
rms
Fuse
IP24
Enclosure class
Refrigerant circuit
R410A
Type of refrigerant
2,088
GWP refrigerant
Scroll
Type of compressor
3
3
2.6
2.4
kg
Volume
6.26
6.26
5.43
5.01
t
CO
2
-equivalent (The cooling circuit is hermetically sealed.)
4.5
MPa
Cut-out value pressure switch HP (BP1)
0.7
MPa
Difference pressostat HP
0.12
MPa
Cut-out value pressostat LP
0.7
MPa
Difference pressostat LP
Brine
4,500
4,150
3,400
2,400
m
3
/h
Max airflow
-25 / 43
°C
Min/Max air temp, max
reverse cycle
Defrosting system
Heating medium
0.45 (4.5 bar)
MPa
Max system pressure heating medium
0.19/0.75
0.15/0.60
0.11/0.44
0.08/0.32
l/s
Min/Max flow
0.48
0.38
0.35
0.27
l/s
Min flow defrosting (100 % pump speed)
26 / 65
°C
Min/Max HM temp continuous operation
G1 1/4" external thread
Connection heating medium JÄSPI Inverter Nordic
G1 1/4" external thread
G1 external thread
Connection heating medium flex pipe
Dimensions and weight
1,280
1,130
mm
Width
612
610
mm
Depth
1,165
1,070
mm
Height with stand
183
177
167
kg
Weight (excl. packaging)
Miscellaneous
536 01 76
536 01 75
536 01 74
536 01 73
Part no.: JÄSPI INVERTER NORDIC
43
Chapter 11 |
Technical data
JÄSPI Inverter Nordic