Connection as a Releasing Module
• 

In the case of using a solenoid valve of NN100 system, connect wires to wiring cable #1 and #3 of 

the valve, and the soak time setting of the relevant address shall be configured as “5” seconds on 

the program.

•  Only one Releasing Device can be connected per MOM-4 module. 

•  The Manual Release Function immediately activates the Suppression System in the same zone. It 

overrides Delay Time and Abort Functions for that zone.

Figure 3: Output Connected to a Releasing Device

Before connecting an output device, connect the module to the SLC loop and reset it with the 

FACP. This is necessary to ensure that the internal relay is unlatched. Connection of the module 

with this relay in the latched state will activate the output device possibly causing damage.

Wiring (Continued)

Page 3 of 4

Summary of Contents for MOM-4

Page 1: ...When the output is activated the LED will turn on constantly In case of trouble the LED will turn off Since the system allows maximum 13 LEDs on devices to turn on constantly if system already has 13 lighted LEDs on devices MOM 4 will not turn on the LED and keep flashing even if the output of MOM 4 is activated P N 99239 24 VDC Monitored Output Control 5 1k ohm EOL NAC or Releasing Control LED in...

Page 2: ...of each other and be enclosed within conduit or equivalently protected against mechanical injury When NACs are connected to MOM 4 module each MOM 4 module shall be separated by short circuit isolators SCI to avoid influence from a short circuit of the SLC Signal Line Circuit Wiring Diagram Setting the Address Figure 2 Output Connected to a Notification Appliance Circuit Page 2 of 4 SLC loop wiring...

Page 3: ... 4 module The Manual Release Function immediately activates the Suppression System in the same zone It overrides Delay Time and Abort Functions for that zone Figure 3 Output Connected to a Releasing Device Before connecting an output device connect the module to the SLC loop and reset it with the FACP This is necessary to ensure that the internal relay is unlatched Connection of the module with th...

Page 4: ...ated in the seller s sales contract or sales acknowledgment form Every attempt is made to keep our product information up to date and accurate All specific applications cannot be covered nor can all requirements be anticipated All specifications are subject to change without notice Note Approvals Listings maintained by and manufactured by Potter Electric Signal Company Ordering Information Model N...

Reviews: