REX K-1-9 and REX K-3-9 – Standalone or access controller
3/2015
Black line
www.jantar.si
After 8. beep
Press 8 and
Sound is OFF
Tamper is OFF
Door status switch input- normally opened (NO)
Time is set in minutes
After 9. beep
Press 9 and
Sound is ON
Tamper is OFF
Door status switch input- normally opened (NO)
Time is set in minutes
After 10. beep
Press 10 and
Sound is OFF
Tamper is ON
Door status switch input- normally opened (NO)
Time is set in minutes
After 11. beep
Press 11 and
Sound is ON
Tamper is ON
Door status switch input- normally opened (NO)
Time is set in minutes
After 12. beep
Press 12 and
Sound is OFF
Tamper is OFF
Door status switch input- normally closed (NC)
Time is set in minutes
After 13. beep
Press 13 and
Sound is ON
Tamper is OFF
Door status switch input- normally closed (NC)
Time is set in minutes
After 14. beep
Press 14 and
Sound is OFF
Tamper is ON
Door status switch input- normally closed (NC)
Time is set in minutes
After 15. beep
Press 15 and
Sound is ON
Tamper is ON
Door status switch input- normally closed (NC)
Time is set in minutes
Function 16) Reset
“HARD” reset. Use it instead off manual reset (power off/on).
Reset with master card:
Approach the master card and remove it after 16 double beeps. The
controller will start to beep every second. Approach a user card after three
beeps.
Reset with master code:
Enter the master code and press
. Press 16 and
. Press 3 and
.
AS AN ACCESS CONTROLLER
As an access controller, it is intended for controlling entries, exits and passes
of users in the system and controlling sliding doors, ramp, el. strike, turning
alarm on/off… It needs to be set with JantarV7, BLOCKER or CODEKS
software.
The controller switches to access controller when tables are sent by
the software or when it is set to mode 4 with function 9. Change the
controller’s address from 255 to any number between 1 and 254. If
you have more controllers on the communication line, don’t duplicate
addresses.
Add them one by one on the communication line, because every
controller has address 255 by default.
Communication
Connect the controller to the computer, with one of the power supplies, with
communication converter, from the Spider family: Spider W5-USB, Spider
W5-NET, Spider W40+NET.
The RS485 communication bus is used between the controllers and Jantar
software. Up to 128 controllers can be lined up into one communication line.
The maximum length of the communication line is 1000 cable meters. It is
recommended that you use an FTP or S-FTP cable. Only a serial connection
of controllers in a single communication line is allowed.
Star (parallel)
connection is not allowed
.
All shields of S-FTP cables must be wired together and at
one point
connected to the earth. Individual connections to the earth are not allowed.
Do not connect the shield of the cable to the ground of the controller.
In the event of problems in communication, a termination resistor
needs to be added. We recommend using 120 Ohm resistors on each
side of the cable. Converters are, on the RS485 side, protected with
slow-blow fuses and transient voltage suppressors.
Changing back to standalone controller from access controller:
In the Codeks Device Manager software do the “Brainwash” of the
controller. Address of the controller’s switches back to 255.
ORDERING CODES
REX
[box]-[card]-[software]
Box:
K
Card:
1
– reading frequency 125kHz (cards)
3
– reading frequency 13.56MHz (cards)
Software:
9
– BLOCKER, CODEKS (support for V7 min.7.995.6.1032)
Code
Description
REX K-1-9
Standalone or access controller in
K
box, Frequency
125kHz, for JantarV7, BLOCKER or CODEKS software
REX K-3-9
Standalone or access controller in
K
box, Frequency
13.56MHz, for JantarV7, BLOCKER or CODEKS software
OTHER
Warranty only applies when the controller Rex is used with power supply
or/and communication converter from the Spider family.
Please read through our warranty and disclaimer statements.
Connection scheme and additional support for the use of this product can be