10 / 12
General
1
2
Doc. no. 2.040.119.1.a
Part no. 33.03.306
Power Analyser
UMG 96 RM
Installation manual
Installation
Device settings
Deutsche V
ersion:
siehe V
or
derseite
3
8
16
17
12
14
5
6
The device
• is only approved for measuring current with a
current transformer.
• is intended for connecting current
transformers with secondary currents of
../1 A and ../5 A.
• has the current transformer ratio 5/5 A set as
standard.
7
Voltage measurement
The device has 3 voltage measurement inputs
and is suitable for different connection variants.
11
Power Analyser
C
NOTE!
Changes are only applied after exiting
programming mode.
C
NOTE!
• The following section contains an
explanation of the most important
programming menus
current
transformer, voltage transformer
and
parameter list.
• More detailed information on the
operation, display and button
functions for your device can be found
in the user manual.
10
9
4
15
2
Safety
Safety information
The Installation manual is not a complete
directory of all safety measures required to
operate the device.
Special operating conditions may require further
measures. The Installation manual contains
instructions that must be observed to ensure
your personal safety and to prevent damage to
property.
Symbols used:
c
This symbol is an addition to the
safety instructions and indicates
an electrical hazard.
m
This symbol is an addition to the
safety instructions and indicates
a potential hazard.
C
This symbol with the word
NOTE!
describes:
• Procedures that do not pose
any risks of injures.
• Important information,
procedures or handling steps.
Safety information is highlighted by a warning
triangle and is indicated as follows depending
on the degree of danger:
m
DANGER!
Indicates an imminent danger that
causes severe or fatal injuries.
m
WARNING!
Indicates a potentially hazardous
situation that can cause severe
injuries or death.
m
CAUTION!
Indicates a potentially hazardous
situation that can cause minor
injuries or damage to property.
Safety measures
When operating electrical devices, certain parts
of these devices are invariably subjected to
hazardous voltage. Therefore, severe bodily
injuries or damage to property can occur if they
are not handled properly:
• Before connecting connections, earth the
device at the ground wire connection if
present.
• Hazardous voltages may be present in all
switching parts that are connected to the
power supply.
• Hazardous voltages may also be present
in the device even after disconnecting the
supply voltage (capacitor storage).
• Do not operate equipment with current
transformer circuits while open.
• Do not exceed the threshold values specified
in the user manual and on the rating plate.
Also adhere to this when inspecting and
commissioning.
• Observe the safety and warning instructions in
the documents that belong to the device!
Qualified staff
In order to prevent personal injuries and damage
to property, only qualified staff with electrical
training may work on the device, with knowledge
of
• the national accident prevention regulations
• the safety engineering standards
• installing, commissioning and operating the
device.
Proper use
The device is
• intended for installation in switch cabinets
and small installation distributors. It can be
installed in any mounting position (please
observe step 3 "Assembly").
• not intended for installation in vehicles!
The use of the device in mobile equipment
is considered to be non-standard
environmental conditions and is therefore
only permitted after separate agreement.
• not intended for installation in environments
with hazardous oils, acids, gases, vapours,
dusts, radiation, etc.
The prerequisites of faultless, safe operation
of this device are proper transport and proper
storage, set-up, installation, operation and
maintenance.
The UMG 96 RM is a multi-functional network
analyser, which:
• Measures and calculates electrical
variables such as voltage, current,
frequency, power, energy, harmonics
(up to the 40th harmonic), etc. in building
installations, on distribution units, circuit
breakers and busbar trunking systems.
• displays and saves measurement results
and transmits them via interfaces.
Device short description
Install the UMG 96 RM in the weatherproof front
panel of switch cabinets.
Cut-out size:
92
+0.8
x 92
+0.8
mm
Ensure!
Adequate ventilation
• install the device vertically!
• adhere to clearances from
neighbouring components!
Fig. Installation situation,
rear view UMG 96
Assembly
Connecting the supply voltage
The supply voltage level for your device is specified
on the rating plate.
After connecting the supply voltage, an indication
is shown on the display. If no indication appears,
check whether the supply voltage is within the
rated voltage range.
c
WARNING!
Risk of injury due
to electric voltage!
Serious bodily injury or death can result from:
• Contact with bare or stripped live wires.
• Device inputs that are dangerous to touch.
De-energise your device before starting
work! Check that it is de-energised.
Fuse
N
L
Fig. Connecting supply voltage.
Circuit breaker
m
CAUTION!
Damage to property due to
disregard of the connection
conditions or impermissible
voltage swells
Your device can be damaged or destroyed
by a failure to comply with the connection
conditions or by exceeding the permissible
voltage range.
Before connecting the device to the supply
voltage, please check:
•
Voltage and frequency correspond to the
details on the ratings plate! Threshold
values stipulated in the user manual
have been complied with!
•
In building installations, the supply
voltage must be protected with a UL/IEC
approved circuit breaker / a fuse!
•
The circuit breaker
-
must be easily accessible for the user
and be installed close to the device.
-
must be labelled for the relevant device.
•
Do not connect the supply voltage to the
voltage transformers.
•
Provide a fuse for the neutral conductor
if the source's neutral conductor
connection is not earthed.
Network systems
Suitable network systems and maximum rated voltages (DIN EN 61010-1/A1):
Three-phase four-conductor systems
with earthed neutral conductor
Three-phase four-conductor systems
with non-earthed neutral conductor
(IT networks)
Three-phase, three-conductor systems
Not earthed
Three-phase, three-conductor systems
with earthed phase
L1
L2
L3
E
E
N
E
L1
L2
L3
E
N
R
L1
L2
L3
E
E
L1
L2
E
E
L
N
E
E
L1
L2
L3
E
E
L1
L2
N
E
E
L1
L2
L3
E
E
N
E
L1
L2
L3
E
N
R
L1
L2
L3
E
E
L1
L2
E
E
L
N
E
E
L1
L2
L3
E
E
L1
L2
N
E
E
L1
L2
L3
E
E
N
E
L1
L2
L3
E
N
R
L1
L2
L3
E
E
L1
L2
E
E
L
N
E
E
L1
L2
L3
E
E
L1
L2
N
E
E
L1
L2
L3
E
E
N
E
L1
L2
L3
E
N
R
L1
L2
L3
E
E
L1
L2
E
E
L
N
E
E
L1
L2
L3
E
E
L1
L2
N
E
E
U
L-N
/ U
L-L
277 VLN / 480 VLL
U
L-N
/ U
L-L
277 VLN / 480 VLL
U
L-L
480 VLL
U
L-L
240 VLL
Single-phase two-conductor systems
with earthed neutral conductor
Separated single-phase,
three-conductor systems
with earthed neutral conductor
The device can be used in
• 2, 3 and 4 conductor
networks (TN, TT and
IT networks)
• Residential and
industrial applications
L1
L2
L3
E
E
N
E
L1
L2
L3
E
N
R
L1
L2
L3
E
E
L1
L2
E
E
L
N
E
E
L1
L2
L3
E
E
L1
L2
N
E
E
L1
L2
L3
E
E
N
E
L1
L2
L3
E
N
R
L1
L2
L3
E
E
L1
L2
E
E
L
N
E
E
L1
L2
L3
E
E
L1
L2
N
E
E
U
L-N
230 VLN
U
L-N
/ U
L-L
240 VLN / 480 VLL
m
CAUTION!
Risk of injuries or
damage to the device
Disregard of the connection conditions for
the voltage measurement inputs can result in
injuries or to the device being damaged.
Therefore, note the following:
•
The voltage measurement inputs
-
must not be occupied with DC voltage.
-
must be provided with a suitable,
labelled fuse that is positioned close by
and a circuit breaker (alternatively:
a line safety switch).
-
are dangerous to touch.
•
Voltages that exceed the allowed network
rated voltages must be connected via
a voltage transformer.
•
Measured voltages and currents must
derive from the same network.
C
NOTE!
As an alternative to the fuse and circuit
breaker, you can use a line safety switch.
Circuit breaker
Fuse (UL/IEC listed)
L2
L3
N
L1
Voltage measurement connection variant
3p 4w
(Addr. 509 = 0, standard setting)
C
NOTE!
With measurement range exceeding,
the measurement device display shows
"EEE". Further information on this can
be found in the user manual.
Voltage measurement connection variants
3p 4w
(Addr. 509 = 0, standard setting)
3p 4wu
(Addr. 509 = 1)
3p 4u
(Addr. 509 = 2)
3p 2u
(Addr. 509 = 5)
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
V1
V2
V3
V
N
L1
L2
L3
V1
V2
V3
V
N
L1
N
V1
V2
V3
V
N
L1
L2
V1
V2
V3
V
N
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
L1
L2
L3
L1
L2
L3
V1
V2
V3
V
N
N
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
V1
V2
V3
V
N
L1
L2
L3
V1
V2
V3
V
N
L1
N
V1
V2
V3
V
N
L1
L2
V1
V2
V3
V
N
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
L1
L2
L3
L1
L2
L3
V1
V2
V3
V
N
N
Measurement with 3 phase
conductors and neutral conductor.
Measurement via voltage
transformer with 3 phase
conductors and a neutral
conductor.
Measurement with 3 phase
conductors without neutral
conductor. Measured values which
require an N, use a calculated N.
Measurement via voltage
transformer with 3 phase
conductors without neutral
conductor. Measured values which
require an N, use a calculated N.
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
V1
V2
V3
V
N
L1
L2
L3
V1
V2
V3
V
N
L1
N
V1
V2
V3
V
N
L1
L2
V1
V2
V3
V
N
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
L1
L2
L3
L1
L2
L3
V1
V2
V3
V
N
N
1p 2w1
(Addr. 509 = 4)
2p 4w
(Addr. 509 = 3)
1p 2w
(Addr. 509 = 6)
3p 1w
(Addr. 509 = 7)
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
V1
V2
V3
V
N
L1
L2
L3
V1
V2
V3
V
N
L1
N
V1
V2
V3
V
N
L1
L2
V1
V2
V3
V
N
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
L1
L2
L3
L1
L2
L3
V1
V2
V3
V
N
N
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
V1
V2
V3
V
N
L1
L2
L3
V1
V2
V3
V
N
L1
N
V1
V2
V3
V
N
L1
L2
V1
V2
V3
V
N
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
L1
L2
L3
L1
L2
L3
V1
V2
V3
V
N
N
Measured values derived from
voltage measurement inputs V2
and V3 are taken to be 0 and are
not calculated.
System with equal loading of the
phases. The measured values of
the voltage measurement input V2
are calculated.
TN-C system with 1-phase, three-
conductor connection. Measured
values derived from voltage
measurement input V3 are taken
to be 0 and are not calculated.
3 systems with equal loading of
the phases. The measured values
for the phases that are not created
(L2/L3, L1/L3, L1/L2) for the
relevant systems are calculated.
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
V1
V2
V3
V
N
L1
L2
L3
V1
V2
V3
V
N
L1
N
V1
V2
V3
V
N
L1
L2
V1
V2
V3
V
N
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
L1
L2
L3
L1
L2
L3
V1
V2
V3
V
N
N
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
V1
V2
V3
V
N
L1
L2
L3
V1
V2
V3
V
N
L1
N
V1
V2
V3
V
N
L1
L2
V1
V2
V3
V
N
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
L1
L2
L3
L1
L2
L3
V1
V2
V3
V
N
N
c
WARNING!
Risk of injury due
to electric voltage!
Serious bodily injury or death can result from:
• Contact with bare or stripped live wires.
• Current measurement inputs that are
dangerous to touch on the device and on
the current transformers.
De-energise your device before starting
work! Check that it is de-energised.
Earth the system. Use the earth connection
points with earthing symbols for this!
Earth the secondary windings of current
transformers and all of the metal parts of
the transformer that could be touched!
L2
L3
N
L1
Load
Connection variant
3p 4w current measurement
(I1, I2, I3) via current transformer
(Addr. 510 = 0,
standard setting).
Current measurement I1, I2, I3
Connection variants for current measurement I1, I2, I3
3p 2i
(Addr. 510 = 1)
3p 2i0
(Addr. 510 = 2)
3p 3w3
(Addr. 510 = 3)
3p 3w
(Addr. 510 = 4)
L1
L2
L3
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
I1
I2
I3
I1
I2
I3
L1
L2
L1
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
I1
I2
I3
L1
L2
L3
L1
L2
L3
L1
L2
L3
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
I1
I2
I3
I1
I2
I3
L1
L2
L1
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
I1
I2
I3
L1
L2
L3
L1
L2
L3
System with equal loading of the
phases. The measured values for
current measurement input I2 are
calculated.
The measured values for current
measurement input I2 are
calculated.
Measurement in the 3-phase
network with unequal loading.
Measurement in the 3-phase
network with equal loading.
The measured values for current
measurement inputs I2 and I3 are
calculated.
L1
L2
L3
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
I1
I2
I3
I1
I2
I3
L1
L2
L1
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
I1
I2
I3
L1
L2
L3
L1
L2
L3
L1
L2
L3
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
I1
I2
I3
I1
I2
I3
L1
L2
L1
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
I1
I2
I3
L1
L2
L3
L1
L2
L3
2p 4w
(Addr. 510 = 5)
1p 2i
(Addr. 510 = 6)
1p 2w
(Addr. 510 = 7)
3p 1w
(Addr. 510 = 8)
L1
L2
L3
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
I1
I2
I3
I1
I2
I3
L1
L2
L1
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
I1
I2
I3
L1
L2
L3
L1
L2
L3
L1
L2
L3
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
I1
I2
I3
I1
I2
I3
L1
L2
L1
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
I1
I2
I3
L1
L2
L3
L1
L2
L3
System with equal loading of the
phases. The measured values for
current measurement input I2 are
calculated.
Measured values derived from
current measurement input I3
are taken to be 0 and are not
calculated.
Measured values derived from
current measurement inputs I2 and
I3 are taken to be 0 and are not
calculated.
3 systems with equal loading of
the phases. The measured values
for the phases that are not created
(L2/L3, L1/L3, L1/L2) for the
relevant systems are calculated.
L1
L2
L3
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
I1
I2
I3
I1
I2
I3
L1
L2
L1
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
I1
I2
I3
L1
L2
L3
L1
L2
L3
L1
L2
L3
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
I1
I2
I3
I1
I2
I3
L1
L2
L1
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
I1
I2
I3
L1
L2
L3
L1
L2
L3
c
WARNING!
Risk of injury due to
large currents and high
electric voltages!
Current transformers operating with an open
secondary circuit (high voltage peaks) can
result in serious or even fatal injuries.
Avoid open operation of the current transformers -
short-circuit unloaded transformers!
13
C
NOTE!
With measurement range exceeding,
the measurement device display shows
"EEE". Further information on this can
be found in the user manual.
User manual:
The voltage measurement inputs are designed for
measurements in low voltage networks, in which
rated voltages of up to
• 277 V phase to earth and 480 V phase to phase
in the 4-conductor system or
• 480 V phase to phase in the 3-conductor system
occur.
The measurement and surge voltages meet over-
voltage category 300 V CATIII.
m
CAUTION!
Damage to property due to
disregard of the installation
instructions
Failing to observe the installation instructions
can damage or destroy your device.
Ensure that there is adequate air circulation in your
installation environment; if the ambient temperatures
are high, ensure there is adequate cooling if required.
C
NOTE!
For further information on device functions, data and assembly, see the user manual.
Programming parameters
1. Switch to programming mode.
2. The symbols for programming mode
PRG and
for the current transformer
CT appear.
3. Press button 2 twice to change to the
programming mode for the parameter list.
4. The input area of the parameter list appears.
Parameter address
Programming mode
Parameter setting
Fig. "Parameter list"
input field
C
NOTE!
• A detailed parameter list with setting
areas and pre-settings can be found
in the user manual or the Modbus
address list on our website.
• The parameter addresses of the
device address (000) and the Baud
rate (001) are explained in the
following.
5. Confirm with button 1 - the first digit of the
parameter address flashes.
6. Use button 2 to select the value of the
1st digit.
7. Continue the process for the next digits of
the parameter address and for the parameter
settings.
8. Exit programming mode by simultaneously
pressing button 1 and 2 (1 second).
Use button 2 to change back to the input
field for the current transformer.
Set the device address (parameter address 000)
In a Master-Slave network via the RS485 interface,
a master device can distinguish between the UMGs
on the basis of the device address.
In the case of devices within this network, for the
parameter address 000 please note
• you must assign different device addresses.
• the parameter setting of the parameter address
000 must lie within the range of 1 to 247
(0 and 248 to 255 are reserved).
Set the Baud rate (parameter address 001)
In a Master-Slave network via the RS485 interface, for
each device:
• select a uniform Baud rate (parameter address 001)
(for settings see the user manual).
• select the number of stop bits (parameter
address 003) (0=1 Bit, 1=2 Bits).
Data bits (8) and parity (none) are pre-set.
The device is operated with buttons 1 and 2,
whereby the following distinctions are made:
• Short press (button 1 or 2):
Next step (+1).
• Long press (button 1 or 2):
previous step (-1).
The device differentiates between display and
programming mode.
Display mode
• You can use buttons 1 and 2 to scroll between
the measured value indications.
• The measured value indication shows up to
3 measured values.
• A time for an automatic indication change
between the measured value indications can
be configured in the GridVis® software.
Programming mode
• Press and hold buttons 1 and 2 simultaneously
for 1 second to switch between
display mode
and
programming mode
. The text
PRG
appears in the display.
• Configure the necessary settings for the
operation of the device in programming mode.
Operation and button functions
Fig. Display UMG 96 RM
Button 1
Button 2
Export
Mean value
CT: Current
transformer
VT:
Voltage
transformer
K1: Output 1
K2: Output 2
Password
Phase conductor-
Phase conductor
Summation
measurement
Programming
mode
Min. value NT/export
Max. value, HT/reference
• The programming mode can be protected with
a user password.
• Button 2 switches between the programming
menus:
1.
Current transformer
2.
Voltage transformer
3.
Parameter list
To switch from
programming mode
to
display mode
,
• press buttons 1 and 2 simultaneously for 1 second.
• do not press any buttons for 60 seconds (automatic).
Programming the current transformer
1. Switch to programming mode.
2. The symbols for programming mode
PRG
and for the current transformer
CT appear.
3. Press button 1 - the first digit of the input
field for the primary current flashes.
4. Use button 2 to select the value for the
1st digit.
5. Use button 1 to move to the 2nd. digit.
6. Use button 2 to select the value of the
2nd digit.
7. Use button 1 to move to the 3rd digit.
8. Use button 2 to select the value of the
3rd digit.
9. Confirm with button 1.
10. The complete number flashes.
11. Use button 2 to select the decimal place and
thus the unit of the primary current.
12. Confirm with button 1.
13. The input range of the secondary current
flashes.
14. Use button 2 to set the secondary current
(value 1 A or 5 A).
15. Confirm with button 1.
16. Pressing buttons 1 and 2 simultaneously
(1. sec.) exits the programming mode.
Use button 2 to change to the input field for
the voltage transformer.
Current transformer
symbol
Unit indicator
Current transformer,
primary
Programming mode
Current transformer,
secondary
C
NOTE!
• Changes are only applied after exiting
programming mode.
• For further information on current
transformers and current transformer
ratios, see the user manual.
Fig. "Current transformer" input area
Programming voltage transformers
1. Switch to programming mode.
2. The symbols for programming mode
PRG
and for the current transformer
CT appear.
3. Use button 2 to change to programming
mode for the voltage transformer.
4. The symbols for Programming mode
PRG,
and for the voltage transformer
VT appear.
5. Press button 1 to confirm - the first digit
of the input area for the primary voltage
flashes.
6. Use button 2 to select the value of the
1st. digit.
7. Use button 1 to move to the 2nd. digit.
8. Use button 2 to select the value of the
2nd digit.
9. Use button 1 to move to the 3rd digit.
10. Use button 2 to select the value of the
3rd digit.
11. Confirm with button 1.
12. The complete number flashes.
13. Use button 2 to select the decimal place and
thus the unit of the primary voltage.
14. Confirm with button 1.
15. The input range of the secondary voltage
flashes.
16. Set the secondary voltage with button 2.
17. Confirm with button 1.
18. Pressing buttons 1 and 2 simultaneously
(1. sec.) exits the programming mode. Use
button 2 to change to the programming
mode for the parameter list.
C
NOTE!
• Changes are only applied after exiting
programming mode.
• Further information on voltage trans-
formers and voltage transformer ra-
tios can be found in the user manual.
Unit indicator
Voltage transformer,
primary
Programming mode
Voltage transformer,
secondary
Voltage transformer
symbol
Fig. "Voltage transformer" input area
www
.janitza.com
Janitza electronics GmbH
Vor dem Polstück 6
D-35633 Lahnau / Germany
Support tel. +49 6441 9642-22
Fax +49 6441 9642-30
e-mail: [email protected]
Website: http://www.janitza.com
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
V1
V2
V3
V
N
L1
L2
L3
V1
V2
V3
V
N
L1
N
V1
V2
V3
V
N
L1
L2
V1
V2
V3
V
N
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
L1
L2
L3
L1
L2
L3
V1
V2
V3
V
N
N
Disclaimer
The observance of the information products for
the devices is a prerequisite for safe operation
and to achieve the stipulated performance
characteristics and product characteristics.
Janitza electronics GmbH accepts no liability
for injuries to personnel, property damage
or financial losses arising due to a failure to
comply with the information products. Ensure
that your information products are accessible
and legible.
Further information can be found on our web-
site www.janitza.com at Support > Downloads.
Copyright notice
© 2016 - Janitza electronics GmbH - Lahnau.
All rights reserved. Duplication, editing,
distribution and any form of exploitation, also
as excerpts, is prohibited.
Subject to technical amendments
• Make sure that your device agrees with the
installation manual.
• Read and understand first product-related
documents.
• Keep product supporting documentation
throughout the life available and, where ap-
propriate, to pass on to subsequent users.
• Please inform yourself about device revisi-
ons and the associated adjustments to the
product-related documentation on
www.janitza.com.
Disposal
Please observe national regulations!
If disposing of individual parts, please dispose
of them in accordance with their nature and
existing country-specific regulations, for
example as:
• Electrical scrap
• Plastics
• Metals
Or, task a certified disposal business with the
scrapping.
Relevant laws, applied standards and
directives
The laws, standards and directives for the
device applied by Janitza electronic GmbH
can be found in the declaration of conformity
on our website.
Technical data
Voltage measurement
3-phase 4-conductor
systems with rated
voltages of up to
277 V/480 V (+-10%)
3-phase 3-conductor
systems, not earthed, with
rated voltages of up to
IT 480 V (+-10%)
Overvoltage category
300 V CAT III
Rated surge voltage
4 kV
Protection
of voltage measurement
1 - 10 A
(with IEC-/UL approval)
Metering range L-N
0
1)
to 300 Vrms
(max. overvoltage 520 Vrms )
Metering range L-L
0
1)
to 520 Vrms
(max. overvoltage 900 Vrms )
Resolution
0.01 V
Crest factor
2.45 (based on metering range)
Impedance
4 MOhm / phase
Power consumption
approx. 0.1 VA
Sampling rate
21.33 kHz (50 Hz),
25.6 kHz (60 Hz)
for each measurement channel
Frequency range of the
fundamental oscillation -
resolution
45 Hz to 65 Hz
0.01 Hz
1) ... The device determines measured values only if the Voltage
measurement input V1 voltage L1-N greater than 20 Vrms
(4-wire measurement) or a voltage L1-L2 of larger 34 Vrms
(3-wire measurement) is applied.
Current measurement I1 - I4
Nominal current
5 A
Metering range
0 to 6 Arms
Crest factor
1.98
Resolution
0.1 mA (display 0.01 A)
Overvoltage category
300 V CAT II
Rated surge voltage
2 kV
Power consumption
approx. 0.2 VA (Ri = 5 mOhm)
Overload for 1 sec.
120 A (sinusoidal)
Sampling rate
21.33 kHz (50 Hz),
25.6 kHz (60 Hz)
for each measurement channel
C
NOTE!
Further technical data can be found in the
use manual for the device.
Supply voltage
Nominal range
Option 230 V:
AC 90 V - 277 V (50/60 Hz) or
DC 90 V - 250 V, 300 V CATIII
Option 24 V:
AC 24 V - 90 V (50/60 Hz) or
DC 24 V - 90 V, 150 V CATIII
Operating range
+-10% of the nominal range
Power consumption
Option 230 V: max. 5,5 VA / 3 W
Option 24 V: max. 4,5 VA / 3 W
Internal fuse,
not replaceable
Type T1A / 250 VDC / 277 VAC
according to IEC 60127
Recommended over-
current protection device for
the line protection
Option 230 V: 6-16 A
Option 24 V: 1-6 A
(Char. B)
(IEC/UL approval)
Establish the connection to the PC
The most common connections for
communication between the PC and the device:
1.
m
CAUTION!
Damage to property due to
incorrect network settings
Incorrect network settings can cause faults in
the IT network!
Obtain information from your network
administrator about the correct Ethernet
network settings for your device.
More details on device configuration and
communication can be found from section 11.
2.
(gedrehtes Patchkabel)
PC
RS232 RS232
RS485
UMG 96 RM
UMG 96 RM
Connection of the UMG 96 RM
via interface converter.
(gedrehtes Patchkabel)
PC
UMG 604
Connection of the UMG 96 RM
via a UMG 604 as a gateway.
Ethernet
UMG 96 RM
Fig. Rear side
UMG 96 RM
UMG 96 RM
RS485
RS485
RS485
RS485
Example: PC connection via RS485 interface and UMG 604 as gateway
Correct
Incorrect
Terminal strip (switch cabinet).
Device with RS485 interface
(without termination resistor).
Device with RS485 interface
(termination resistor on the
device).
RS485 bus
e.g. connection
of further
Slave devices
A
B
RS485 interface
2 pin plug contact
with termination resistor
120 Ω,
0.25 W
RS485 bus
Connection to
the UMG 604
as gateway (Master)
e.g. connection
of further
Slave devices
A
B
RS485 interface
2 pin plug contact
The UMG 96 RM communicates with a PC via
the serial RS485 interface and a UMG 604 as
gateway:
C
NOTE!
In order to include the UMG 96 RM in an RS485
bus structure (master-slave principle) with
UMG 604 as a master device, first
• enter a
1 in address 203 of the UMG 604
(Modbus RTU/master)!
C
NOTE!
For further information on parameter lists,
device addresses and Baud rates, see the
user manual.
RS485 bus structure
• In an RS485 bus structure (line), connect
all devices according to the master-slave
principle.
• One segment in an RS485 bus structure can
contain up to 32 participants/devices.
• Terminate the cable at the start and the end of
a segment with termination resistors (120 Ω,
0.25 W). The UMG 96 RM does not contain
any termination resistors.
• With more than 32 subscribers, repeaters
must be used to connect segments.
Procedure in the event of faults
Possible fault
Cause
Remedy
No display
External fusing for the power supply voltage has
tripped.
Replace fuse.
No current display
Measurement voltage is not connected.
Connect the measuring-circuit voltage.
Measurement current is not connected.
Connect measuring-circuit current.
Current displayed is too large
or too small.
Current measurement in the wrong phase.
Check connection and correct if necessary.
Current transformer factor is incorrectly programmed. Read out and program the current transformer trans-
formation ratio at the current transformer.
The current peak value at the measurement input
was exceeded by harmonic components.
Install current transformer with a larger transforma-
tion ratio.
The current at the measurement input fell short of.
Install current transformer with a suitable transfor-
mation ratio.
Voltage displayed is too large
or too small.
Measurement in the wrong phase.
Check connection and correct if necessary.
Voltage transformer incorrectly programmed.
Read out and program the voltage transformer trans-
formation ratio at the voltage transformer.
Voltage displayed is too
small.
Overrange.
Install voltage transformers.
The peak voltage value at the measurement input has
been exceeded by harmonic components.
Caution! Ensure the measurement inputs are not
overloaded.
"EEE" in the display
See „error messages“ in the user manual.
Device still does not work
despite the above measures.
Device defective.
Send the device to the manufacturer for inspection
and testing along with an accurate fault description.
Digital outputs
2 digital outputs, semiconductor relays, not short-circuit proof.
Switching voltage
max. 33 V AC, 60 V DC
Switching current
max. 50 mAeff AC/DC
Response time
10/12 p 10 ms *
Pulse output (energy pulse)
max. 50 Hz
* Response time e.g. at 50 Hz: 200 ms + 10 ms = 210 ms
Serial interface
RS485 - Modbus RTU/Slave
9.6 kbps, 19.2 kbps,
38.4 kbps, 57.6 kbps,
115.2 kbps
Stripping length
7 mm
Terminal connection capacity (power supply voltage)
Conductors to be connected.
Only one conductor can be connected per terminal!
Single core, multi-core,
fine-stranded
0.2 - 2.5 mm
2
, AWG 26 - 12
Terminal pins, core end sheath
0.2 - 2.5 mm
2
Tightening torque
0.4 - 0.5 Nm
Stripping length
7 mm
Terminal connection capacity (digital outputs)
Single core, multi-core,
fine-stranded
0.2 - 1.5 mm
2
, AWG 28-16
Terminal pins, core end sheath
0.2 - 1.5 mm
2
Tightening torque
0.2 - 0.25 Nm
Stripping length
7 mm
Terminal connection capacity (current measurement)
Conductors to be connected.
Only one conductor can be connected per terminal!
Single core, multi-core,
fine-stranded
0.2 - 2.5 mm
2
, AWG 26-12
Terminal pins, core end sheath
0.2 - 2.5 mm
2
Tightening torque
0.4 - 0.5 Nm
Stripping length
7 mm
Terminal connection capacity (serial interface)
Single core, multi-core,
fine-stranded
0.2 - 1.5 mm
2
, AWG 28 - 16
Terminal pins, core end sheath
0.2 - 1.5 mm
2
Tightening torque
0.2 - 0.25 Nm
Stripping length
7 mm
Terminal connection capacity (voltage measurement)
Conductors to be connected.
Only one conductor can be connected per terminal!
Single core, multi-core,
fine-stranded
0.08 - 4.0 mm
2
, AWG 28-12
Terminal pins, core end sheath
0.2 - 2.5 mm
2
Tightening torque
0.4 - 0.5 Nm
Stripping length
7 mm
General information
Net weight
(with attached connectors)
approx. 265 g
Packaging weight
(including accessories)
approx. 300 g
Service life of
background lighting
40000 h
(after this period of time
the background lighting
efficiency will reduce by
approx. 50%)
Transport and storage
The following information applies to devices which are trans-
ported or stored in the original packaging.
Free fall
1 m
Temperature
K55 (-25° C to +70° C)
Relative humidity
0 to 90% RH
Ambient coditions during operation
The device is intended for weather-protected, stationary use.
Protection class II i.a.w. IEC 60536 (VDE 0106, Part 1).
Operating temperature range
K55 (-10° C .. +55° C)
Relative humidity
0 to 75% RH
Operating altitude
0 .. 2000 m above sea level
Degree of pollution
2
Mounting position
vertical
Ventilation
Forced ventilation is
not required.
Protection against ingress
of solid foreign bodies and
water
- Front side
- Rear side
- Front with seal
IP40 i.a.w. EN60529
IP20 i.a.w. EN60529
IP54 i.a.w. EN60529
General
1
2
Doc. no. 2.040.119.1.a
Part no. 33.03.306
Power Analyser
UMG 96 RM
Installation manual
Installation
Device settings
Deutsche V
ersion:
siehe V
or
derseite
3
8
16
17
12
14
5
6
The device
• is only approved for measuring current with a
current transformer.
• is intended for connecting current
transformers with secondary currents of
../1 A and ../5 A.
• has the current transformer ratio 5/5 A set as
standard.
7
Voltage measurement
The device has 3 voltage measurement inputs
and is suitable for different connection variants.
11
Power Analyser
C
NOTE!
Changes are only applied after exiting
programming mode.
C
NOTE!
• The following section contains an
explanation of the most important
programming menus
current
transformer, voltage transformer
and
parameter list.
• More detailed information on the
operation, display and button
functions for your device can be found
in the user manual.
10
9
4
15
2
Safety
Safety information
The Installation manual is not a complete
directory of all safety measures required to
operate the device.
Special operating conditions may require further
measures. The Installation manual contains
instructions that must be observed to ensure
your personal safety and to prevent damage to
property.
Symbols used:
c
This symbol is an addition to the
safety instructions and indicates
an electrical hazard.
m
This symbol is an addition to the
safety instructions and indicates
a potential hazard.
C
This symbol with the word
NOTE!
describes:
• Procedures that do not pose
any risks of injures.
• Important information,
procedures or handling steps.
Safety information is highlighted by a warning
triangle and is indicated as follows depending
on the degree of danger:
m
DANGER!
Indicates an imminent danger that
causes severe or fatal injuries.
m
WARNING!
Indicates a potentially hazardous
situation that can cause severe
injuries or death.
m
CAUTION!
Indicates a potentially hazardous
situation that can cause minor
injuries or damage to property.
Safety measures
When operating electrical devices, certain parts
of these devices are invariably subjected to
hazardous voltage. Therefore, severe bodily
injuries or damage to property can occur if they
are not handled properly:
• Before connecting connections, earth the
device at the ground wire connection if
present.
• Hazardous voltages may be present in all
switching parts that are connected to the
power supply.
• Hazardous voltages may also be present
in the device even after disconnecting the
supply voltage (capacitor storage).
• Do not operate equipment with current
transformer circuits while open.
• Do not exceed the threshold values specified
in the user manual and on the rating plate.
Also adhere to this when inspecting and
commissioning.
• Observe the safety and warning instructions in
the documents that belong to the device!
Qualified staff
In order to prevent personal injuries and damage
to property, only qualified staff with electrical
training may work on the device, with knowledge
of
• the national accident prevention regulations
• the safety engineering standards
• installing, commissioning and operating the
device.
Proper use
The device is
• intended for installation in switch cabinets
and small installation distributors. It can be
installed in any mounting position (please
observe step 3 "Assembly").
• not intended for installation in vehicles!
The use of the device in mobile equipment
is considered to be non-standard
environmental conditions and is therefore
only permitted after separate agreement.
• not intended for installation in environments
with hazardous oils, acids, gases, vapours,
dusts, radiation, etc.
The prerequisites of faultless, safe operation
of this device are proper transport and proper
storage, set-up, installation, operation and
maintenance.
The UMG 96 RM is a multi-functional network
analyser, which:
• Measures and calculates electrical
variables such as voltage, current,
frequency, power, energy, harmonics
(up to the 40th harmonic), etc. in building
installations, on distribution units, circuit
breakers and busbar trunking systems.
• displays and saves measurement results
and transmits them via interfaces.
Device short description
Install the UMG 96 RM in the weatherproof front
panel of switch cabinets.
Cut-out size:
92
+0.8
x 92
+0.8
mm
Ensure!
Adequate ventilation
• install the device vertically!
• adhere to clearances from
neighbouring components!
Fig. Installation situation,
rear view UMG 96
Assembly
Connecting the supply voltage
The supply voltage level for your device is specified
on the rating plate.
After connecting the supply voltage, an indication
is shown on the display. If no indication appears,
check whether the supply voltage is within the
rated voltage range.
c
WARNING!
Risk of injury due
to electric voltage!
Serious bodily injury or death can result from:
• Contact with bare or stripped live wires.
• Device inputs that are dangerous to touch.
De-energise your device before starting
work! Check that it is de-energised.
Fuse
N
L
Fig. Connecting supply voltage.
Circuit breaker
m
CAUTION!
Damage to property due to
disregard of the connection
conditions or impermissible
voltage swells
Your device can be damaged or destroyed
by a failure to comply with the connection
conditions or by exceeding the permissible
voltage range.
Before connecting the device to the supply
voltage, please check:
•
Voltage and frequency correspond to the
details on the ratings plate! Threshold
values stipulated in the user manual
have been complied with!
•
In building installations, the supply
voltage must be protected with a UL/IEC
approved circuit breaker / a fuse!
•
The circuit breaker
-
must be easily accessible for the user
and be installed close to the device.
-
must be labelled for the relevant device.
•
Do not connect the supply voltage to the
voltage transformers.
•
Provide a fuse for the neutral conductor
if the source's neutral conductor
connection is not earthed.
Network systems
Suitable network systems and maximum rated voltages (DIN EN 61010-1/A1):
Three-phase four-conductor systems
with earthed neutral conductor
Three-phase four-conductor systems
with non-earthed neutral conductor
(IT networks)
Three-phase, three-conductor systems
Not earthed
Three-phase, three-conductor systems
with earthed phase
L1
L2
L3
E
E
N
E
L1
L2
L3
E
N
R
L1
L2
L3
E
E
L1
L2
E
E
L
N
E
E
L1
L2
L3
E
E
L1
L2
N
E
E
L1
L2
L3
E
E
N
E
L1
L2
L3
E
N
R
L1
L2
L3
E
E
L1
L2
E
E
L
N
E
E
L1
L2
L3
E
E
L1
L2
N
E
E
L1
L2
L3
E
E
N
E
L1
L2
L3
E
N
R
L1
L2
L3
E
E
L1
L2
E
E
L
N
E
E
L1
L2
L3
E
E
L1
L2
N
E
E
L1
L2
L3
E
E
N
E
L1
L2
L3
E
N
R
L1
L2
L3
E
E
L1
L2
E
E
L
N
E
E
L1
L2
L3
E
E
L1
L2
N
E
E
U
L-N
/ U
L-L
277 VLN / 480 VLL
U
L-N
/ U
L-L
277 VLN / 480 VLL
U
L-L
480 VLL
U
L-L
240 VLL
Single-phase two-conductor systems
with earthed neutral conductor
Separated single-phase,
three-conductor systems
with earthed neutral conductor
The device can be used in
• 2, 3 and 4 conductor
networks (TN, TT and
IT networks)
• Residential and
industrial applications
L1
L2
L3
E
E
N
E
L1
L2
L3
E
N
R
L1
L2
L3
E
E
L1
L2
E
E
L
N
E
E
L1
L2
L3
E
E
L1
L2
N
E
E
L1
L2
L3
E
E
N
E
L1
L2
L3
E
N
R
L1
L2
L3
E
E
L1
L2
E
E
L
N
E
E
L1
L2
L3
E
E
L1
L2
N
E
E
U
L-N
230 VLN
U
L-N
/ U
L-L
240 VLN / 480 VLL
m
CAUTION!
Risk of injuries or
damage to the device
Disregard of the connection conditions for
the voltage measurement inputs can result in
injuries or to the device being damaged.
Therefore, note the following:
•
The voltage measurement inputs
-
must not be occupied with DC voltage.
-
must be provided with a suitable,
labelled fuse that is positioned close by
and a circuit breaker (alternatively:
a line safety switch).
-
are dangerous to touch.
•
Voltages that exceed the allowed network
rated voltages must be connected via
a voltage transformer.
•
Measured voltages and currents must
derive from the same network.
C
NOTE!
As an alternative to the fuse and circuit
breaker, you can use a line safety switch.
Circuit breaker
Fuse (UL/IEC listed)
L2
L3
N
L1
Voltage measurement connection variant
3p 4w
(Addr. 509 = 0, standard setting)
C
NOTE!
With measurement range exceeding,
the measurement device display shows
"EEE". Further information on this can
be found in the user manual.
Voltage measurement connection variants
3p 4w
(Addr. 509 = 0, standard setting)
3p 4wu
(Addr. 509 = 1)
3p 4u
(Addr. 509 = 2)
3p 2u
(Addr. 509 = 5)
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
V1
V2
V3
V
N
L1
L2
L3
V1
V2
V3
V
N
L1
N
V1
V2
V3
V
N
L1
L2
V1
V2
V3
V
N
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
L1
L2
L3
L1
L2
L3
V1
V2
V3
V
N
N
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
V1
V2
V3
V
N
L1
L2
L3
V1
V2
V3
V
N
L1
N
V1
V2
V3
V
N
L1
L2
V1
V2
V3
V
N
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
L1
L2
L3
L1
L2
L3
V1
V2
V3
V
N
N
Measurement with 3 phase
conductors and neutral conductor.
Measurement via voltage
transformer with 3 phase
conductors and a neutral
conductor.
Measurement with 3 phase
conductors without neutral
conductor. Measured values which
require an N, use a calculated N.
Measurement via voltage
transformer with 3 phase
conductors without neutral
conductor. Measured values which
require an N, use a calculated N.
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
V1
V2
V3
V
N
L1
L2
L3
V1
V2
V3
V
N
L1
N
V1
V2
V3
V
N
L1
L2
V1
V2
V3
V
N
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
L1
L2
L3
L1
L2
L3
V1
V2
V3
V
N
N
1p 2w1
(Addr. 509 = 4)
2p 4w
(Addr. 509 = 3)
1p 2w
(Addr. 509 = 6)
3p 1w
(Addr. 509 = 7)
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
V1
V2
V3
V
N
L1
L2
L3
V1
V2
V3
V
N
L1
N
V1
V2
V3
V
N
L1
L2
V1
V2
V3
V
N
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
L1
L2
L3
L1
L2
L3
V1
V2
V3
V
N
N
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
V1
V2
V3
V
N
L1
L2
L3
V1
V2
V3
V
N
L1
N
V1
V2
V3
V
N
L1
L2
V1
V2
V3
V
N
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
L1
L2
L3
L1
L2
L3
V1
V2
V3
V
N
N
Measured values derived from
voltage measurement inputs V2
and V3 are taken to be 0 and are
not calculated.
System with equal loading of the
phases. The measured values of
the voltage measurement input V2
are calculated.
TN-C system with 1-phase, three-
conductor connection. Measured
values derived from voltage
measurement input V3 are taken
to be 0 and are not calculated.
3 systems with equal loading of
the phases. The measured values
for the phases that are not created
(L2/L3, L1/L3, L1/L2) for the
relevant systems are calculated.
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
V1
V2
V3
V
N
L1
L2
L3
V1
V2
V3
V
N
L1
N
V1
V2
V3
V
N
L1
L2
V1
V2
V3
V
N
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
L1
L2
L3
L1
L2
L3
V1
V2
V3
V
N
N
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
V1
V2
V3
V
N
L1
L2
L3
V1
V2
V3
V
N
L1
N
V1
V2
V3
V
N
L1
L2
V1
V2
V3
V
N
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
L1
L2
L3
L1
L2
L3
V1
V2
V3
V
N
N
c
WARNING!
Risk of injury due
to electric voltage!
Serious bodily injury or death can result from:
• Contact with bare or stripped live wires.
• Current measurement inputs that are
dangerous to touch on the device and on
the current transformers.
De-energise your device before starting
work! Check that it is de-energised.
Earth the system. Use the earth connection
points with earthing symbols for this!
Earth the secondary windings of current
transformers and all of the metal parts of
the transformer that could be touched!
L2
L3
N
L1
Load
Connection variant
3p 4w current measurement
(I1, I2, I3) via current transformer
(Addr. 510 = 0,
standard setting).
Current measurement I1, I2, I3
Connection variants for current measurement I1, I2, I3
3p 2i
(Addr. 510 = 1)
3p 2i0
(Addr. 510 = 2)
3p 3w3
(Addr. 510 = 3)
3p 3w
(Addr. 510 = 4)
L1
L2
L3
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
I1
I2
I3
I1
I2
I3
L1
L2
L1
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
I1
I2
I3
L1
L2
L3
L1
L2
L3
L1
L2
L3
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
I1
I2
I3
I1
I2
I3
L1
L2
L1
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
I1
I2
I3
L1
L2
L3
L1
L2
L3
System with equal loading of the
phases. The measured values for
current measurement input I2 are
calculated.
The measured values for current
measurement input I2 are
calculated.
Measurement in the 3-phase
network with unequal loading.
Measurement in the 3-phase
network with equal loading.
The measured values for current
measurement inputs I2 and I3 are
calculated.
L1
L2
L3
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
I1
I2
I3
I1
I2
I3
L1
L2
L1
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
I1
I2
I3
L1
L2
L3
L1
L2
L3
L1
L2
L3
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
I1
I2
I3
I1
I2
I3
L1
L2
L1
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
I1
I2
I3
L1
L2
L3
L1
L2
L3
2p 4w
(Addr. 510 = 5)
1p 2i
(Addr. 510 = 6)
1p 2w
(Addr. 510 = 7)
3p 1w
(Addr. 510 = 8)
L1
L2
L3
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
I1
I2
I3
I1
I2
I3
L1
L2
L1
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
I1
I2
I3
L1
L2
L3
L1
L2
L3
L1
L2
L3
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
I1
I2
I3
I1
I2
I3
L1
L2
L1
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
I1
I2
I3
L1
L2
L3
L1
L2
L3
System with equal loading of the
phases. The measured values for
current measurement input I2 are
calculated.
Measured values derived from
current measurement input I3
are taken to be 0 and are not
calculated.
Measured values derived from
current measurement inputs I2 and
I3 are taken to be 0 and are not
calculated.
3 systems with equal loading of
the phases. The measured values
for the phases that are not created
(L2/L3, L1/L3, L1/L2) for the
relevant systems are calculated.
L1
L2
L3
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
I1
I2
I3
I1
I2
I3
L1
L2
L1
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
I1
I2
I3
L1
L2
L3
L1
L2
L3
L1
L2
L3
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
I1
I2
I3
I1
I2
I3
L1
L2
L1
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
I1
I2
I3
L1
L2
L3
L1
L2
L3
c
WARNING!
Risk of injury due to
large currents and high
electric voltages!
Current transformers operating with an open
secondary circuit (high voltage peaks) can
result in serious or even fatal injuries.
Avoid open operation of the current transformers -
short-circuit unloaded transformers!
13
C
NOTE!
With measurement range exceeding,
the measurement device display shows
"EEE". Further information on this can
be found in the user manual.
User manual:
The voltage measurement inputs are designed for
measurements in low voltage networks, in which
rated voltages of up to
• 277 V phase to earth and 480 V phase to phase
in the 4-conductor system or
• 480 V phase to phase in the 3-conductor system
occur.
The measurement and surge voltages meet over-
voltage category 300 V CATIII.
m
CAUTION!
Damage to property due to
disregard of the installation
instructions
Failing to observe the installation instructions
can damage or destroy your device.
Ensure that there is adequate air circulation in your
installation environment; if the ambient temperatures
are high, ensure there is adequate cooling if required.
C
NOTE!
For further information on device functions, data and assembly, see the user manual.
Programming parameters
1. Switch to programming mode.
2. The symbols for programming mode
PRG and
for the current transformer
CT appear.
3. Press button 2 twice to change to the
programming mode for the parameter list.
4. The input area of the parameter list appears.
Parameter address
Programming mode
Parameter setting
Fig. "Parameter list"
input field
C
NOTE!
• A detailed parameter list with setting
areas and pre-settings can be found
in the user manual or the Modbus
address list on our website.
• The parameter addresses of the
device address (000) and the Baud
rate (001) are explained in the
following.
5. Confirm with button 1 - the first digit of the
parameter address flashes.
6. Use button 2 to select the value of the
1st digit.
7. Continue the process for the next digits of
the parameter address and for the parameter
settings.
8. Exit programming mode by simultaneously
pressing button 1 and 2 (1 second).
Use button 2 to change back to the input
field for the current transformer.
Set the device address (parameter address 000)
In a Master-Slave network via the RS485 interface,
a master device can distinguish between the UMGs
on the basis of the device address.
In the case of devices within this network, for the
parameter address 000 please note
• you must assign different device addresses.
• the parameter setting of the parameter address
000 must lie within the range of 1 to 247
(0 and 248 to 255 are reserved).
Set the Baud rate (parameter address 001)
In a Master-Slave network via the RS485 interface, for
each device:
• select a uniform Baud rate (parameter address 001)
(for settings see the user manual).
• select the number of stop bits (parameter
address 003) (0=1 Bit, 1=2 Bits).
Data bits (8) and parity (none) are pre-set.
The device is operated with buttons 1 and 2,
whereby the following distinctions are made:
• Short press (button 1 or 2):
Next step (+1).
• Long press (button 1 or 2):
previous step (-1).
The device differentiates between display and
programming mode.
Display mode
• You can use buttons 1 and 2 to scroll between
the measured value indications.
• The measured value indication shows up to
3 measured values.
• A time for an automatic indication change
between the measured value indications can
be configured in the GridVis® software.
Programming mode
• Press and hold buttons 1 and 2 simultaneously
for 1 second to switch between
display mode
and
programming mode
. The text
PRG
appears in the display.
• Configure the necessary settings for the
operation of the device in programming mode.
Operation and button functions
Fig. Display UMG 96 RM
Button 1
Button 2
Export
Mean value
CT: Current
transformer
VT:
Voltage
transformer
K1: Output 1
K2: Output 2
Password
Phase conductor-
Phase conductor
Summation
measurement
Programming
mode
Min. value NT/export
Max. value, HT/reference
• The programming mode can be protected with
a user password.
• Button 2 switches between the programming
menus:
1.
Current transformer
2.
Voltage transformer
3.
Parameter list
To switch from
programming mode
to
display mode
,
• press buttons 1 and 2 simultaneously for 1 second.
• do not press any buttons for 60 seconds (automatic).
Programming the current transformer
1. Switch to programming mode.
2. The symbols for programming mode
PRG
and for the current transformer
CT appear.
3. Press button 1 - the first digit of the input
field for the primary current flashes.
4. Use button 2 to select the value for the
1st digit.
5. Use button 1 to move to the 2nd. digit.
6. Use button 2 to select the value of the
2nd digit.
7. Use button 1 to move to the 3rd digit.
8. Use button 2 to select the value of the
3rd digit.
9. Confirm with button 1.
10. The complete number flashes.
11. Use button 2 to select the decimal place and
thus the unit of the primary current.
12. Confirm with button 1.
13. The input range of the secondary current
flashes.
14. Use button 2 to set the secondary current
(value 1 A or 5 A).
15. Confirm with button 1.
16. Pressing buttons 1 and 2 simultaneously
(1. sec.) exits the programming mode.
Use button 2 to change to the input field for
the voltage transformer.
Current transformer
symbol
Unit indicator
Current transformer,
primary
Programming mode
Current transformer,
secondary
C
NOTE!
• Changes are only applied after exiting
programming mode.
• For further information on current
transformers and current transformer
ratios, see the user manual.
Fig. "Current transformer" input area
Programming voltage transformers
1. Switch to programming mode.
2. The symbols for programming mode
PRG
and for the current transformer
CT appear.
3. Use button 2 to change to programming
mode for the voltage transformer.
4. The symbols for Programming mode
PRG,
and for the voltage transformer
VT appear.
5. Press button 1 to confirm - the first digit
of the input area for the primary voltage
flashes.
6. Use button 2 to select the value of the
1st. digit.
7. Use button 1 to move to the 2nd. digit.
8. Use button 2 to select the value of the
2nd digit.
9. Use button 1 to move to the 3rd digit.
10. Use button 2 to select the value of the
3rd digit.
11. Confirm with button 1.
12. The complete number flashes.
13. Use button 2 to select the decimal place and
thus the unit of the primary voltage.
14. Confirm with button 1.
15. The input range of the secondary voltage
flashes.
16. Set the secondary voltage with button 2.
17. Confirm with button 1.
18. Pressing buttons 1 and 2 simultaneously
(1. sec.) exits the programming mode. Use
button 2 to change to the programming
mode for the parameter list.
C
NOTE!
• Changes are only applied after exiting
programming mode.
• Further information on voltage trans-
formers and voltage transformer ra-
tios can be found in the user manual.
Unit indicator
Voltage transformer,
primary
Programming mode
Voltage transformer,
secondary
Voltage transformer
symbol
Fig. "Voltage transformer" input area
www
.janitza.com
Janitza electronics GmbH
Vor dem Polstück 6
D-35633 Lahnau / Germany
Support tel. +49 6441 9642-22
Fax +49 6441 9642-30
e-mail: [email protected]
Website: http://www.janitza.com
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
V1
V2
V3
V
N
L1
L2
L3
V1
V2
V3
V
N
L1
N
V1
V2
V3
V
N
L1
L2
V1
V2
V3
V
N
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
L1
L2
L3
L1
L2
L3
V1
V2
V3
V
N
N
Disclaimer
The observance of the information products for
the devices is a prerequisite for safe operation
and to achieve the stipulated performance
characteristics and product characteristics.
Janitza electronics GmbH accepts no liability
for injuries to personnel, property damage
or financial losses arising due to a failure to
comply with the information products. Ensure
that your information products are accessible
and legible.
Further information can be found on our web-
site www.janitza.com at Support > Downloads.
Copyright notice
© 2016 - Janitza electronics GmbH - Lahnau.
All rights reserved. Duplication, editing,
distribution and any form of exploitation, also
as excerpts, is prohibited.
Subject to technical amendments
• Make sure that your device agrees with the
installation manual.
• Read and understand first product-related
documents.
• Keep product supporting documentation
throughout the life available and, where ap-
propriate, to pass on to subsequent users.
• Please inform yourself about device revisi-
ons and the associated adjustments to the
product-related documentation on
www.janitza.com.
Disposal
Please observe national regulations!
If disposing of individual parts, please dispose
of them in accordance with their nature and
existing country-specific regulations, for
example as:
• Electrical scrap
• Plastics
• Metals
Or, task a certified disposal business with the
scrapping.
Relevant laws, applied standards and
directives
The laws, standards and directives for the
device applied by Janitza electronic GmbH
can be found in the declaration of conformity
on our website.
Technical data
Voltage measurement
3-phase 4-conductor
systems with rated
voltages of up to
277 V/480 V (+-10%)
3-phase 3-conductor
systems, not earthed, with
rated voltages of up to
IT 480 V (+-10%)
Overvoltage category
300 V CAT III
Rated surge voltage
4 kV
Protection
of voltage measurement
1 - 10 A
(with IEC-/UL approval)
Metering range L-N
0
1)
to 300 Vrms
(max. overvoltage 520 Vrms )
Metering range L-L
0
1)
to 520 Vrms
(max. overvoltage 900 Vrms )
Resolution
0.01 V
Crest factor
2.45 (based on metering range)
Impedance
4 MOhm / phase
Power consumption
approx. 0.1 VA
Sampling rate
21.33 kHz (50 Hz),
25.6 kHz (60 Hz)
for each measurement channel
Frequency range of the
fundamental oscillation -
resolution
45 Hz to 65 Hz
0.01 Hz
1) ... The device determines measured values only if the Voltage
measurement input V1 voltage L1-N greater than 20 Vrms
(4-wire measurement) or a voltage L1-L2 of larger 34 Vrms
(3-wire measurement) is applied.
Current measurement I1 - I4
Nominal current
5 A
Metering range
0 to 6 Arms
Crest factor
1.98
Resolution
0.1 mA (display 0.01 A)
Overvoltage category
300 V CAT II
Rated surge voltage
2 kV
Power consumption
approx. 0.2 VA (Ri = 5 mOhm)
Overload for 1 sec.
120 A (sinusoidal)
Sampling rate
21.33 kHz (50 Hz),
25.6 kHz (60 Hz)
for each measurement channel
C
NOTE!
Further technical data can be found in the
use manual for the device.
Supply voltage
Nominal range
Option 230 V:
AC 90 V - 277 V (50/60 Hz) or
DC 90 V - 250 V, 300 V CATIII
Option 24 V:
AC 24 V - 90 V (50/60 Hz) or
DC 24 V - 90 V, 150 V CATIII
Operating range
+-10% of the nominal range
Power consumption
Option 230 V: max. 5,5 VA / 3 W
Option 24 V: max. 4,5 VA / 3 W
Internal fuse,
not replaceable
Type T1A / 250 VDC / 277 VAC
according to IEC 60127
Recommended over-
current protection device for
the line protection
Option 230 V: 6-16 A
Option 24 V: 1-6 A
(Char. B)
(IEC/UL approval)
Establish the connection to the PC
The most common connections for
communication between the PC and the device:
1.
m
CAUTION!
Damage to property due to
incorrect network settings
Incorrect network settings can cause faults in
the IT network!
Obtain information from your network
administrator about the correct Ethernet
network settings for your device.
More details on device configuration and
communication can be found from section 11.
2.
(gedrehtes Patchkabel)
PC
RS232 RS232
RS485
UMG 96 RM
UMG 96 RM
Connection of the UMG 96 RM
via interface converter.
(gedrehtes Patchkabel)
PC
UMG 604
Connection of the UMG 96 RM
via a UMG 604 as a gateway.
Ethernet
UMG 96 RM
Fig. Rear side
UMG 96 RM
UMG 96 RM
RS485
RS485
RS485
RS485
Example: PC connection via RS485 interface and UMG 604 as gateway
Correct
Incorrect
Terminal strip (switch cabinet).
Device with RS485 interface
(without termination resistor).
Device with RS485 interface
(termination resistor on the
device).
RS485 bus
e.g. connection
of further
Slave devices
A
B
RS485 interface
2 pin plug contact
with termination resistor
120 Ω,
0.25 W
RS485 bus
Connection to
the UMG 604
as gateway (Master)
e.g. connection
of further
Slave devices
A
B
RS485 interface
2 pin plug contact
The UMG 96 RM communicates with a PC via
the serial RS485 interface and a UMG 604 as
gateway:
C
NOTE!
In order to include the UMG 96 RM in an RS485
bus structure (master-slave principle) with
UMG 604 as a master device, first
• enter a
1 in address 203 of the UMG 604
(Modbus RTU/master)!
C
NOTE!
For further information on parameter lists,
device addresses and Baud rates, see the
user manual.
RS485 bus structure
• In an RS485 bus structure (line), connect
all devices according to the master-slave
principle.
• One segment in an RS485 bus structure can
contain up to 32 participants/devices.
• Terminate the cable at the start and the end of
a segment with termination resistors (120 Ω,
0.25 W). The UMG 96 RM does not contain
any termination resistors.
• With more than 32 subscribers, repeaters
must be used to connect segments.
Procedure in the event of faults
Possible fault
Cause
Remedy
No display
External fusing for the power supply voltage has
tripped.
Replace fuse.
No current display
Measurement voltage is not connected.
Connect the measuring-circuit voltage.
Measurement current is not connected.
Connect measuring-circuit current.
Current displayed is too large
or too small.
Current measurement in the wrong phase.
Check connection and correct if necessary.
Current transformer factor is incorrectly programmed. Read out and program the current transformer trans-
formation ratio at the current transformer.
The current peak value at the measurement input
was exceeded by harmonic components.
Install current transformer with a larger transforma-
tion ratio.
The current at the measurement input fell short of.
Install current transformer with a suitable transfor-
mation ratio.
Voltage displayed is too large
or too small.
Measurement in the wrong phase.
Check connection and correct if necessary.
Voltage transformer incorrectly programmed.
Read out and program the voltage transformer trans-
formation ratio at the voltage transformer.
Voltage displayed is too
small.
Overrange.
Install voltage transformers.
The peak voltage value at the measurement input has
been exceeded by harmonic components.
Caution! Ensure the measurement inputs are not
overloaded.
"EEE" in the display
See „error messages“ in the user manual.
Device still does not work
despite the above measures.
Device defective.
Send the device to the manufacturer for inspection
and testing along with an accurate fault description.
Digital outputs
2 digital outputs, semiconductor relays, not short-circuit proof.
Switching voltage
max. 33 V AC, 60 V DC
Switching current
max. 50 mAeff AC/DC
Response time
10/12 p 10 ms *
Pulse output (energy pulse)
max. 50 Hz
* Response time e.g. at 50 Hz: 200 ms + 10 ms = 210 ms
Serial interface
RS485 - Modbus RTU/Slave
9.6 kbps, 19.2 kbps,
38.4 kbps, 57.6 kbps,
115.2 kbps
Stripping length
7 mm
Terminal connection capacity (power supply voltage)
Conductors to be connected.
Only one conductor can be connected per terminal!
Single core, multi-core,
fine-stranded
0.2 - 2.5 mm
2
, AWG 26 - 12
Terminal pins, core end sheath
0.2 - 2.5 mm
2
Tightening torque
0.4 - 0.5 Nm
Stripping length
7 mm
Terminal connection capacity (digital outputs)
Single core, multi-core,
fine-stranded
0.2 - 1.5 mm
2
, AWG 28-16
Terminal pins, core end sheath
0.2 - 1.5 mm
2
Tightening torque
0.2 - 0.25 Nm
Stripping length
7 mm
Terminal connection capacity (current measurement)
Conductors to be connected.
Only one conductor can be connected per terminal!
Single core, multi-core,
fine-stranded
0.2 - 2.5 mm
2
, AWG 26-12
Terminal pins, core end sheath
0.2 - 2.5 mm
2
Tightening torque
0.4 - 0.5 Nm
Stripping length
7 mm
Terminal connection capacity (serial interface)
Single core, multi-core,
fine-stranded
0.2 - 1.5 mm
2
, AWG 28 - 16
Terminal pins, core end sheath
0.2 - 1.5 mm
2
Tightening torque
0.2 - 0.25 Nm
Stripping length
7 mm
Terminal connection capacity (voltage measurement)
Conductors to be connected.
Only one conductor can be connected per terminal!
Single core, multi-core,
fine-stranded
0.08 - 4.0 mm
2
, AWG 28-12
Terminal pins, core end sheath
0.2 - 2.5 mm
2
Tightening torque
0.4 - 0.5 Nm
Stripping length
7 mm
General information
Net weight
(with attached connectors)
approx. 265 g
Packaging weight
(including accessories)
approx. 300 g
Service life of
background lighting
40000 h
(after this period of time
the background lighting
efficiency will reduce by
approx. 50%)
Transport and storage
The following information applies to devices which are trans-
ported or stored in the original packaging.
Free fall
1 m
Temperature
K55 (-25° C to +70° C)
Relative humidity
0 to 90% RH
Ambient coditions during operation
The device is intended for weather-protected, stationary use.
Protection class II i.a.w. IEC 60536 (VDE 0106, Part 1).
Operating temperature range
K55 (-10° C .. +55° C)
Relative humidity
0 to 75% RH
Operating altitude
0 .. 2000 m above sea level
Degree of pollution
2
Mounting position
vertical
Ventilation
Forced ventilation is
not required.
Protection against ingress
of solid foreign bodies and
water
- Front side
- Rear side
- Front with seal
IP40 i.a.w. EN60529
IP20 i.a.w. EN60529
IP54 i.a.w. EN60529
General
1
2
Doc. no. 2.040.119.1.a
Part no. 33.03.306
Power Analyser
UMG 96 RM
Installation manual
Installation
Device settings
Deutsche V
ersion:
siehe V
or
derseite
3
8
16
17
12
14
5
6
The device
• is only approved for measuring current with a
current transformer.
• is intended for connecting current
transformers with secondary currents of
../1 A and ../5 A.
• has the current transformer ratio 5/5 A set as
standard.
7
Voltage measurement
The device has 3 voltage measurement inputs
and is suitable for different connection variants.
11
Power Analyser
C
NOTE!
Changes are only applied after exiting
programming mode.
C
NOTE!
• The following section contains an
explanation of the most important
programming menus
current
transformer, voltage transformer
and
parameter list.
• More detailed information on the
operation, display and button
functions for your device can be found
in the user manual.
10
9
4
15
2
Safety
Safety information
The Installation manual is not a complete
directory of all safety measures required to
operate the device.
Special operating conditions may require further
measures. The Installation manual contains
instructions that must be observed to ensure
your personal safety and to prevent damage to
property.
Symbols used:
c
This symbol is an addition to the
safety instructions and indicates
an electrical hazard.
m
This symbol is an addition to the
safety instructions and indicates
a potential hazard.
C
This symbol with the word
NOTE!
describes:
• Procedures that do not pose
any risks of injures.
• Important information,
procedures or handling steps.
Safety information is highlighted by a warning
triangle and is indicated as follows depending
on the degree of danger:
m
DANGER!
Indicates an imminent danger that
causes severe or fatal injuries.
m
WARNING!
Indicates a potentially hazardous
situation that can cause severe
injuries or death.
m
CAUTION!
Indicates a potentially hazardous
situation that can cause minor
injuries or damage to property.
Safety measures
When operating electrical devices, certain parts
of these devices are invariably subjected to
hazardous voltage. Therefore, severe bodily
injuries or damage to property can occur if they
are not handled properly:
• Before connecting connections, earth the
device at the ground wire connection if
present.
• Hazardous voltages may be present in all
switching parts that are connected to the
power supply.
• Hazardous voltages may also be present
in the device even after disconnecting the
supply voltage (capacitor storage).
• Do not operate equipment with current
transformer circuits while open.
• Do not exceed the threshold values specified
in the user manual and on the rating plate.
Also adhere to this when inspecting and
commissioning.
• Observe the safety and warning instructions in
the documents that belong to the device!
Qualified staff
In order to prevent personal injuries and damage
to property, only qualified staff with electrical
training may work on the device, with knowledge
of
• the national accident prevention regulations
• the safety engineering standards
• installing, commissioning and operating the
device.
Proper use
The device is
• intended for installation in switch cabinets
and small installation distributors. It can be
installed in any mounting position (please
observe step 3 "Assembly").
• not intended for installation in vehicles!
The use of the device in mobile equipment
is considered to be non-standard
environmental conditions and is therefore
only permitted after separate agreement.
• not intended for installation in environments
with hazardous oils, acids, gases, vapours,
dusts, radiation, etc.
The prerequisites of faultless, safe operation
of this device are proper transport and proper
storage, set-up, installation, operation and
maintenance.
The UMG 96 RM is a multi-functional network
analyser, which:
• Measures and calculates electrical
variables such as voltage, current,
frequency, power, energy, harmonics
(up to the 40th harmonic), etc. in building
installations, on distribution units, circuit
breakers and busbar trunking systems.
• displays and saves measurement results
and transmits them via interfaces.
Device short description
Install the UMG 96 RM in the weatherproof front
panel of switch cabinets.
Cut-out size:
92
+0.8
x 92
+0.8
mm
Ensure!
Adequate ventilation
• install the device vertically!
• adhere to clearances from
neighbouring components!
Fig. Installation situation,
rear view UMG 96
Assembly
Connecting the supply voltage
The supply voltage level for your device is specified
on the rating plate.
After connecting the supply voltage, an indication
is shown on the display. If no indication appears,
check whether the supply voltage is within the
rated voltage range.
c
WARNING!
Risk of injury due
to electric voltage!
Serious bodily injury or death can result from:
• Contact with bare or stripped live wires.
• Device inputs that are dangerous to touch.
De-energise your device before starting
work! Check that it is de-energised.
Fuse
N
L
Fig. Connecting supply voltage.
Circuit breaker
m
CAUTION!
Damage to property due to
disregard of the connection
conditions or impermissible
voltage swells
Your device can be damaged or destroyed
by a failure to comply with the connection
conditions or by exceeding the permissible
voltage range.
Before connecting the device to the supply
voltage, please check:
•
Voltage and frequency correspond to the
details on the ratings plate! Threshold
values stipulated in the user manual
have been complied with!
•
In building installations, the supply
voltage must be protected with a UL/IEC
approved circuit breaker / a fuse!
•
The circuit breaker
-
must be easily accessible for the user
and be installed close to the device.
-
must be labelled for the relevant device.
•
Do not connect the supply voltage to the
voltage transformers.
•
Provide a fuse for the neutral conductor
if the source's neutral conductor
connection is not earthed.
Network systems
Suitable network systems and maximum rated voltages (DIN EN 61010-1/A1):
Three-phase four-conductor systems
with earthed neutral conductor
Three-phase four-conductor systems
with non-earthed neutral conductor
(IT networks)
Three-phase, three-conductor systems
Not earthed
Three-phase, three-conductor systems
with earthed phase
L1
L2
L3
E
E
N
E
L1
L2
L3
E
N
R
L1
L2
L3
E
E
L1
L2
E
E
L
N
E
E
L1
L2
L3
E
E
L1
L2
N
E
E
L1
L2
L3
E
E
N
E
L1
L2
L3
E
N
R
L1
L2
L3
E
E
L1
L2
E
E
L
N
E
E
L1
L2
L3
E
E
L1
L2
N
E
E
L1
L2
L3
E
E
N
E
L1
L2
L3
E
N
R
L1
L2
L3
E
E
L1
L2
E
E
L
N
E
E
L1
L2
L3
E
E
L1
L2
N
E
E
L1
L2
L3
E
E
N
E
L1
L2
L3
E
N
R
L1
L2
L3
E
E
L1
L2
E
E
L
N
E
E
L1
L2
L3
E
E
L1
L2
N
E
E
U
L-N
/ U
L-L
277 VLN / 480 VLL
U
L-N
/ U
L-L
277 VLN / 480 VLL
U
L-L
480 VLL
U
L-L
240 VLL
Single-phase two-conductor systems
with earthed neutral conductor
Separated single-phase,
three-conductor systems
with earthed neutral conductor
The device can be used in
• 2, 3 and 4 conductor
networks (TN, TT and
IT networks)
• Residential and
industrial applications
L1
L2
L3
E
E
N
E
L1
L2
L3
E
N
R
L1
L2
L3
E
E
L1
L2
E
E
L
N
E
E
L1
L2
L3
E
E
L1
L2
N
E
E
L1
L2
L3
E
E
N
E
L1
L2
L3
E
N
R
L1
L2
L3
E
E
L1
L2
E
E
L
N
E
E
L1
L2
L3
E
E
L1
L2
N
E
E
U
L-N
230 VLN
U
L-N
/ U
L-L
240 VLN / 480 VLL
m
CAUTION!
Risk of injuries or
damage to the device
Disregard of the connection conditions for
the voltage measurement inputs can result in
injuries or to the device being damaged.
Therefore, note the following:
•
The voltage measurement inputs
-
must not be occupied with DC voltage.
-
must be provided with a suitable,
labelled fuse that is positioned close by
and a circuit breaker (alternatively:
a line safety switch).
-
are dangerous to touch.
•
Voltages that exceed the allowed network
rated voltages must be connected via
a voltage transformer.
•
Measured voltages and currents must
derive from the same network.
C
NOTE!
As an alternative to the fuse and circuit
breaker, you can use a line safety switch.
Circuit breaker
Fuse (UL/IEC listed)
L2
L3
N
L1
Voltage measurement connection variant
3p 4w
(Addr. 509 = 0, standard setting)
C
NOTE!
With measurement range exceeding,
the measurement device display shows
"EEE". Further information on this can
be found in the user manual.
Voltage measurement connection variants
3p 4w
(Addr. 509 = 0, standard setting)
3p 4wu
(Addr. 509 = 1)
3p 4u
(Addr. 509 = 2)
3p 2u
(Addr. 509 = 5)
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
V1
V2
V3
V
N
L1
L2
L3
V1
V2
V3
V
N
L1
N
V1
V2
V3
V
N
L1
L2
V1
V2
V3
V
N
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
L1
L2
L3
L1
L2
L3
V1
V2
V3
V
N
N
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
V1
V2
V3
V
N
L1
L2
L3
V1
V2
V3
V
N
L1
N
V1
V2
V3
V
N
L1
L2
V1
V2
V3
V
N
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
L1
L2
L3
L1
L2
L3
V1
V2
V3
V
N
N
Measurement with 3 phase
conductors and neutral conductor.
Measurement via voltage
transformer with 3 phase
conductors and a neutral
conductor.
Measurement with 3 phase
conductors without neutral
conductor. Measured values which
require an N, use a calculated N.
Measurement via voltage
transformer with 3 phase
conductors without neutral
conductor. Measured values which
require an N, use a calculated N.
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
V1
V2
V3
V
N
L1
L2
L3
V1
V2
V3
V
N
L1
N
V1
V2
V3
V
N
L1
L2
V1
V2
V3
V
N
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
L1
L2
L3
L1
L2
L3
V1
V2
V3
V
N
N
1p 2w1
(Addr. 509 = 4)
2p 4w
(Addr. 509 = 3)
1p 2w
(Addr. 509 = 6)
3p 1w
(Addr. 509 = 7)
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
V1
V2
V3
V
N
L1
L2
L3
V1
V2
V3
V
N
L1
N
V1
V2
V3
V
N
L1
L2
V1
V2
V3
V
N
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
L1
L2
L3
L1
L2
L3
V1
V2
V3
V
N
N
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
V1
V2
V3
V
N
L1
L2
L3
V1
V2
V3
V
N
L1
N
V1
V2
V3
V
N
L1
L2
V1
V2
V3
V
N
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
L1
L2
L3
L1
L2
L3
V1
V2
V3
V
N
N
Measured values derived from
voltage measurement inputs V2
and V3 are taken to be 0 and are
not calculated.
System with equal loading of the
phases. The measured values of
the voltage measurement input V2
are calculated.
TN-C system with 1-phase, three-
conductor connection. Measured
values derived from voltage
measurement input V3 are taken
to be 0 and are not calculated.
3 systems with equal loading of
the phases. The measured values
for the phases that are not created
(L2/L3, L1/L3, L1/L2) for the
relevant systems are calculated.
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
V1
V2
V3
V
N
L1
L2
L3
V1
V2
V3
V
N
L1
N
V1
V2
V3
V
N
L1
L2
V1
V2
V3
V
N
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
L1
L2
L3
L1
L2
L3
V1
V2
V3
V
N
N
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
V1
V2
V3
V
N
L1
L2
L3
V1
V2
V3
V
N
L1
N
V1
V2
V3
V
N
L1
L2
V1
V2
V3
V
N
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
L1
L2
L3
L1
L2
L3
V1
V2
V3
V
N
N
c
WARNING!
Risk of injury due
to electric voltage!
Serious bodily injury or death can result from:
• Contact with bare or stripped live wires.
• Current measurement inputs that are
dangerous to touch on the device and on
the current transformers.
De-energise your device before starting
work! Check that it is de-energised.
Earth the system. Use the earth connection
points with earthing symbols for this!
Earth the secondary windings of current
transformers and all of the metal parts of
the transformer that could be touched!
L2
L3
N
L1
Load
Connection variant
3p 4w current measurement
(I1, I2, I3) via current transformer
(Addr. 510 = 0,
standard setting).
Current measurement I1, I2, I3
Connection variants for current measurement I1, I2, I3
3p 2i
(Addr. 510 = 1)
3p 2i0
(Addr. 510 = 2)
3p 3w3
(Addr. 510 = 3)
3p 3w
(Addr. 510 = 4)
L1
L2
L3
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
I1
I2
I3
I1
I2
I3
L1
L2
L1
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
I1
I2
I3
L1
L2
L3
L1
L2
L3
L1
L2
L3
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
I1
I2
I3
I1
I2
I3
L1
L2
L1
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
I1
I2
I3
L1
L2
L3
L1
L2
L3
System with equal loading of the
phases. The measured values for
current measurement input I2 are
calculated.
The measured values for current
measurement input I2 are
calculated.
Measurement in the 3-phase
network with unequal loading.
Measurement in the 3-phase
network with equal loading.
The measured values for current
measurement inputs I2 and I3 are
calculated.
L1
L2
L3
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
I1
I2
I3
I1
I2
I3
L1
L2
L1
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
I1
I2
I3
L1
L2
L3
L1
L2
L3
L1
L2
L3
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
I1
I2
I3
I1
I2
I3
L1
L2
L1
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
I1
I2
I3
L1
L2
L3
L1
L2
L3
2p 4w
(Addr. 510 = 5)
1p 2i
(Addr. 510 = 6)
1p 2w
(Addr. 510 = 7)
3p 1w
(Addr. 510 = 8)
L1
L2
L3
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
I1
I2
I3
I1
I2
I3
L1
L2
L1
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
I1
I2
I3
L1
L2
L3
L1
L2
L3
L1
L2
L3
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
I1
I2
I3
I1
I2
I3
L1
L2
L1
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
I1
I2
I3
L1
L2
L3
L1
L2
L3
System with equal loading of the
phases. The measured values for
current measurement input I2 are
calculated.
Measured values derived from
current measurement input I3
are taken to be 0 and are not
calculated.
Measured values derived from
current measurement inputs I2 and
I3 are taken to be 0 and are not
calculated.
3 systems with equal loading of
the phases. The measured values
for the phases that are not created
(L2/L3, L1/L3, L1/L2) for the
relevant systems are calculated.
L1
L2
L3
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
I1
I2
I3
I1
I2
I3
L1
L2
L1
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
I1
I2
I3
L1
L2
L3
L1
L2
L3
L1
L2
L3
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
I1
I2
I3
I1
I2
I3
L1
L2
L1
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
I1
I2
I3
L1
L2
L3
L1
L2
L3
c
WARNING!
Risk of injury due to
large currents and high
electric voltages!
Current transformers operating with an open
secondary circuit (high voltage peaks) can
result in serious or even fatal injuries.
Avoid open operation of the current transformers -
short-circuit unloaded transformers!
13
C
NOTE!
With measurement range exceeding,
the measurement device display shows
"EEE". Further information on this can
be found in the user manual.
User manual:
The voltage measurement inputs are designed for
measurements in low voltage networks, in which
rated voltages of up to
• 277 V phase to earth and 480 V phase to phase
in the 4-conductor system or
• 480 V phase to phase in the 3-conductor system
occur.
The measurement and surge voltages meet over-
voltage category 300 V CATIII.
m
CAUTION!
Damage to property due to
disregard of the installation
instructions
Failing to observe the installation instructions
can damage or destroy your device.
Ensure that there is adequate air circulation in your
installation environment; if the ambient temperatures
are high, ensure there is adequate cooling if required.
C
NOTE!
For further information on device functions, data and assembly, see the user manual.
Programming parameters
1. Switch to programming mode.
2. The symbols for programming mode
PRG and
for the current transformer
CT appear.
3. Press button 2 twice to change to the
programming mode for the parameter list.
4. The input area of the parameter list appears.
Parameter address
Programming mode
Parameter setting
Fig. "Parameter list"
input field
C
NOTE!
• A detailed parameter list with setting
areas and pre-settings can be found
in the user manual or the Modbus
address list on our website.
• The parameter addresses of the
device address (000) and the Baud
rate (001) are explained in the
following.
5. Confirm with button 1 - the first digit of the
parameter address flashes.
6. Use button 2 to select the value of the
1st digit.
7. Continue the process for the next digits of
the parameter address and for the parameter
settings.
8. Exit programming mode by simultaneously
pressing button 1 and 2 (1 second).
Use button 2 to change back to the input
field for the current transformer.
Set the device address (parameter address 000)
In a Master-Slave network via the RS485 interface,
a master device can distinguish between the UMGs
on the basis of the device address.
In the case of devices within this network, for the
parameter address 000 please note
• you must assign different device addresses.
• the parameter setting of the parameter address
000 must lie within the range of 1 to 247
(0 and 248 to 255 are reserved).
Set the Baud rate (parameter address 001)
In a Master-Slave network via the RS485 interface, for
each device:
• select a uniform Baud rate (parameter address 001)
(for settings see the user manual).
• select the number of stop bits (parameter
address 003) (0=1 Bit, 1=2 Bits).
Data bits (8) and parity (none) are pre-set.
The device is operated with buttons 1 and 2,
whereby the following distinctions are made:
• Short press (button 1 or 2):
Next step (+1).
• Long press (button 1 or 2):
previous step (-1).
The device differentiates between display and
programming mode.
Display mode
• You can use buttons 1 and 2 to scroll between
the measured value indications.
• The measured value indication shows up to
3 measured values.
• A time for an automatic indication change
between the measured value indications can
be configured in the GridVis® software.
Programming mode
• Press and hold buttons 1 and 2 simultaneously
for 1 second to switch between
display mode
and
programming mode
. The text
PRG
appears in the display.
• Configure the necessary settings for the
operation of the device in programming mode.
Operation and button functions
Fig. Display UMG 96 RM
Button 1
Button 2
Export
Mean value
CT: Current
transformer
VT:
Voltage
transformer
K1: Output 1
K2: Output 2
Password
Phase conductor-
Phase conductor
Summation
measurement
Programming
mode
Min. value NT/export
Max. value, HT/reference
• The programming mode can be protected with
a user password.
• Button 2 switches between the programming
menus:
1.
Current transformer
2.
Voltage transformer
3.
Parameter list
To switch from
programming mode
to
display mode
,
• press buttons 1 and 2 simultaneously for 1 second.
• do not press any buttons for 60 seconds (automatic).
Programming the current transformer
1. Switch to programming mode.
2. The symbols for programming mode
PRG
and for the current transformer
CT appear.
3. Press button 1 - the first digit of the input
field for the primary current flashes.
4. Use button 2 to select the value for the
1st digit.
5. Use button 1 to move to the 2nd. digit.
6. Use button 2 to select the value of the
2nd digit.
7. Use button 1 to move to the 3rd digit.
8. Use button 2 to select the value of the
3rd digit.
9. Confirm with button 1.
10. The complete number flashes.
11. Use button 2 to select the decimal place and
thus the unit of the primary current.
12. Confirm with button 1.
13. The input range of the secondary current
flashes.
14. Use button 2 to set the secondary current
(value 1 A or 5 A).
15. Confirm with button 1.
16. Pressing buttons 1 and 2 simultaneously
(1. sec.) exits the programming mode.
Use button 2 to change to the input field for
the voltage transformer.
Current transformer
symbol
Unit indicator
Current transformer,
primary
Programming mode
Current transformer,
secondary
C
NOTE!
• Changes are only applied after exiting
programming mode.
• For further information on current
transformers and current transformer
ratios, see the user manual.
Fig. "Current transformer" input area
Programming voltage transformers
1. Switch to programming mode.
2. The symbols for programming mode
PRG
and for the current transformer
CT appear.
3. Use button 2 to change to programming
mode for the voltage transformer.
4. The symbols for Programming mode
PRG,
and for the voltage transformer
VT appear.
5. Press button 1 to confirm - the first digit
of the input area for the primary voltage
flashes.
6. Use button 2 to select the value of the
1st. digit.
7. Use button 1 to move to the 2nd. digit.
8. Use button 2 to select the value of the
2nd digit.
9. Use button 1 to move to the 3rd digit.
10. Use button 2 to select the value of the
3rd digit.
11. Confirm with button 1.
12. The complete number flashes.
13. Use button 2 to select the decimal place and
thus the unit of the primary voltage.
14. Confirm with button 1.
15. The input range of the secondary voltage
flashes.
16. Set the secondary voltage with button 2.
17. Confirm with button 1.
18. Pressing buttons 1 and 2 simultaneously
(1. sec.) exits the programming mode. Use
button 2 to change to the programming
mode for the parameter list.
C
NOTE!
• Changes are only applied after exiting
programming mode.
• Further information on voltage trans-
formers and voltage transformer ra-
tios can be found in the user manual.
Unit indicator
Voltage transformer,
primary
Programming mode
Voltage transformer,
secondary
Voltage transformer
symbol
Fig. "Voltage transformer" input area
www
.janitza.com
Janitza electronics GmbH
Vor dem Polstück 6
D-35633 Lahnau / Germany
Support tel. +49 6441 9642-22
Fax +49 6441 9642-30
e-mail: [email protected]
Website: http://www.janitza.com
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
V1
V2
V3
V
N
L1
L2
L3
V1
V2
V3
V
N
L1
N
V1
V2
V3
V
N
L1
L2
V1
V2
V3
V
N
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
L1
L2
L3
L1
L2
L3
V1
V2
V3
V
N
N
Disclaimer
The observance of the information products for
the devices is a prerequisite for safe operation
and to achieve the stipulated performance
characteristics and product characteristics.
Janitza electronics GmbH accepts no liability
for injuries to personnel, property damage
or financial losses arising due to a failure to
comply with the information products. Ensure
that your information products are accessible
and legible.
Further information can be found on our web-
site www.janitza.com at Support > Downloads.
Copyright notice
© 2016 - Janitza electronics GmbH - Lahnau.
All rights reserved. Duplication, editing,
distribution and any form of exploitation, also
as excerpts, is prohibited.
Subject to technical amendments
• Make sure that your device agrees with the
installation manual.
• Read and understand first product-related
documents.
• Keep product supporting documentation
throughout the life available and, where ap-
propriate, to pass on to subsequent users.
• Please inform yourself about device revisi-
ons and the associated adjustments to the
product-related documentation on
www.janitza.com.
Disposal
Please observe national regulations!
If disposing of individual parts, please dispose
of them in accordance with their nature and
existing country-specific regulations, for
example as:
• Electrical scrap
• Plastics
• Metals
Or, task a certified disposal business with the
scrapping.
Relevant laws, applied standards and
directives
The laws, standards and directives for the
device applied by Janitza electronic GmbH
can be found in the declaration of conformity
on our website.
Technical data
Voltage measurement
3-phase 4-conductor
systems with rated
voltages of up to
277 V/480 V (+-10%)
3-phase 3-conductor
systems, not earthed, with
rated voltages of up to
IT 480 V (+-10%)
Overvoltage category
300 V CAT III
Rated surge voltage
4 kV
Protection
of voltage measurement
1 - 10 A
(with IEC-/UL approval)
Metering range L-N
0
1)
to 300 Vrms
(max. overvoltage 520 Vrms )
Metering range L-L
0
1)
to 520 Vrms
(max. overvoltage 900 Vrms )
Resolution
0.01 V
Crest factor
2.45 (based on metering range)
Impedance
4 MOhm / phase
Power consumption
approx. 0.1 VA
Sampling rate
21.33 kHz (50 Hz),
25.6 kHz (60 Hz)
for each measurement channel
Frequency range of the
fundamental oscillation -
resolution
45 Hz to 65 Hz
0.01 Hz
1) ... The device determines measured values only if the Voltage
measurement input V1 voltage L1-N greater than 20 Vrms
(4-wire measurement) or a voltage L1-L2 of larger 34 Vrms
(3-wire measurement) is applied.
Current measurement I1 - I4
Nominal current
5 A
Metering range
0 to 6 Arms
Crest factor
1.98
Resolution
0.1 mA (display 0.01 A)
Overvoltage category
300 V CAT II
Rated surge voltage
2 kV
Power consumption
approx. 0.2 VA (Ri = 5 mOhm)
Overload for 1 sec.
120 A (sinusoidal)
Sampling rate
21.33 kHz (50 Hz),
25.6 kHz (60 Hz)
for each measurement channel
C
NOTE!
Further technical data can be found in the
use manual for the device.
Supply voltage
Nominal range
Option 230 V:
AC 90 V - 277 V (50/60 Hz) or
DC 90 V - 250 V, 300 V CATIII
Option 24 V:
AC 24 V - 90 V (50/60 Hz) or
DC 24 V - 90 V, 150 V CATIII
Operating range
+-10% of the nominal range
Power consumption
Option 230 V: max. 5,5 VA / 3 W
Option 24 V: max. 4,5 VA / 3 W
Internal fuse,
not replaceable
Type T1A / 250 VDC / 277 VAC
according to IEC 60127
Recommended over-
current protection device for
the line protection
Option 230 V: 6-16 A
Option 24 V: 1-6 A
(Char. B)
(IEC/UL approval)
Establish the connection to the PC
The most common connections for
communication between the PC and the device:
1.
m
CAUTION!
Damage to property due to
incorrect network settings
Incorrect network settings can cause faults in
the IT network!
Obtain information from your network
administrator about the correct Ethernet
network settings for your device.
More details on device configuration and
communication can be found from section 11.
2.
(gedrehtes Patchkabel)
PC
RS232 RS232
RS485
UMG 96 RM
UMG 96 RM
Connection of the UMG 96 RM
via interface converter.
(gedrehtes Patchkabel)
PC
UMG 604
Connection of the UMG 96 RM
via a UMG 604 as a gateway.
Ethernet
UMG 96 RM
Fig. Rear side
UMG 96 RM
UMG 96 RM
RS485
RS485
RS485
RS485
Example: PC connection via RS485 interface and UMG 604 as gateway
Correct
Incorrect
Terminal strip (switch cabinet).
Device with RS485 interface
(without termination resistor).
Device with RS485 interface
(termination resistor on the
device).
RS485 bus
e.g. connection
of further
Slave devices
A
B
RS485 interface
2 pin plug contact
with termination resistor
120 Ω,
0.25 W
RS485 bus
Connection to
the UMG 604
as gateway (Master)
e.g. connection
of further
Slave devices
A
B
RS485 interface
2 pin plug contact
The UMG 96 RM communicates with a PC via
the serial RS485 interface and a UMG 604 as
gateway:
C
NOTE!
In order to include the UMG 96 RM in an RS485
bus structure (master-slave principle) with
UMG 604 as a master device, first
• enter a
1 in address 203 of the UMG 604
(Modbus RTU/master)!
C
NOTE!
For further information on parameter lists,
device addresses and Baud rates, see the
user manual.
RS485 bus structure
• In an RS485 bus structure (line), connect
all devices according to the master-slave
principle.
• One segment in an RS485 bus structure can
contain up to 32 participants/devices.
• Terminate the cable at the start and the end of
a segment with termination resistors (120 Ω,
0.25 W). The UMG 96 RM does not contain
any termination resistors.
• With more than 32 subscribers, repeaters
must be used to connect segments.
Procedure in the event of faults
Possible fault
Cause
Remedy
No display
External fusing for the power supply voltage has
tripped.
Replace fuse.
No current display
Measurement voltage is not connected.
Connect the measuring-circuit voltage.
Measurement current is not connected.
Connect measuring-circuit current.
Current displayed is too large
or too small.
Current measurement in the wrong phase.
Check connection and correct if necessary.
Current transformer factor is incorrectly programmed. Read out and program the current transformer trans-
formation ratio at the current transformer.
The current peak value at the measurement input
was exceeded by harmonic components.
Install current transformer with a larger transforma-
tion ratio.
The current at the measurement input fell short of.
Install current transformer with a suitable transfor-
mation ratio.
Voltage displayed is too large
or too small.
Measurement in the wrong phase.
Check connection and correct if necessary.
Voltage transformer incorrectly programmed.
Read out and program the voltage transformer trans-
formation ratio at the voltage transformer.
Voltage displayed is too
small.
Overrange.
Install voltage transformers.
The peak voltage value at the measurement input has
been exceeded by harmonic components.
Caution! Ensure the measurement inputs are not
overloaded.
"EEE" in the display
See „error messages“ in the user manual.
Device still does not work
despite the above measures.
Device defective.
Send the device to the manufacturer for inspection
and testing along with an accurate fault description.
Digital outputs
2 digital outputs, semiconductor relays, not short-circuit proof.
Switching voltage
max. 33 V AC, 60 V DC
Switching current
max. 50 mAeff AC/DC
Response time
10/12 p 10 ms *
Pulse output (energy pulse)
max. 50 Hz
* Response time e.g. at 50 Hz: 200 ms + 10 ms = 210 ms
Serial interface
RS485 - Modbus RTU/Slave
9.6 kbps, 19.2 kbps,
38.4 kbps, 57.6 kbps,
115.2 kbps
Stripping length
7 mm
Terminal connection capacity (power supply voltage)
Conductors to be connected.
Only one conductor can be connected per terminal!
Single core, multi-core,
fine-stranded
0.2 - 2.5 mm
2
, AWG 26 - 12
Terminal pins, core end sheath
0.2 - 2.5 mm
2
Tightening torque
0.4 - 0.5 Nm
Stripping length
7 mm
Terminal connection capacity (digital outputs)
Single core, multi-core,
fine-stranded
0.2 - 1.5 mm
2
, AWG 28-16
Terminal pins, core end sheath
0.2 - 1.5 mm
2
Tightening torque
0.2 - 0.25 Nm
Stripping length
7 mm
Terminal connection capacity (current measurement)
Conductors to be connected.
Only one conductor can be connected per terminal!
Single core, multi-core,
fine-stranded
0.2 - 2.5 mm
2
, AWG 26-12
Terminal pins, core end sheath
0.2 - 2.5 mm
2
Tightening torque
0.4 - 0.5 Nm
Stripping length
7 mm
Terminal connection capacity (serial interface)
Single core, multi-core,
fine-stranded
0.2 - 1.5 mm
2
, AWG 28 - 16
Terminal pins, core end sheath
0.2 - 1.5 mm
2
Tightening torque
0.2 - 0.25 Nm
Stripping length
7 mm
Terminal connection capacity (voltage measurement)
Conductors to be connected.
Only one conductor can be connected per terminal!
Single core, multi-core,
fine-stranded
0.08 - 4.0 mm
2
, AWG 28-12
Terminal pins, core end sheath
0.2 - 2.5 mm
2
Tightening torque
0.4 - 0.5 Nm
Stripping length
7 mm
General information
Net weight
(with attached connectors)
approx. 265 g
Packaging weight
(including accessories)
approx. 300 g
Service life of
background lighting
40000 h
(after this period of time
the background lighting
efficiency will reduce by
approx. 50%)
Transport and storage
The following information applies to devices which are trans-
ported or stored in the original packaging.
Free fall
1 m
Temperature
K55 (-25° C to +70° C)
Relative humidity
0 to 90% RH
Ambient coditions during operation
The device is intended for weather-protected, stationary use.
Protection class II i.a.w. IEC 60536 (VDE 0106, Part 1).
Operating temperature range
K55 (-10° C .. +55° C)
Relative humidity
0 to 75% RH
Operating altitude
0 .. 2000 m above sea level
Degree of pollution
2
Mounting position
vertical
Ventilation
Forced ventilation is
not required.
Protection against ingress
of solid foreign bodies and
water
- Front side
- Rear side
- Front with seal
IP40 i.a.w. EN60529
IP20 i.a.w. EN60529
IP54 i.a.w. EN60529
General
1
2
Doc. no. 2.040.119.1.a
Part no. 33.03.306
Power Analyser
UMG 96 RM
Installation manual
Installation
Device settings
Deutsche V
ersion:
siehe V
or
derseite
3
8
16
17
12
14
5
6
The device
• is only approved for measuring current with a
current transformer.
• is intended for connecting current
transformers with secondary currents of
../1 A and ../5 A.
• has the current transformer ratio 5/5 A set as
standard.
7
Voltage measurement
The device has 3 voltage measurement inputs
and is suitable for different connection variants.
11
Power Analyser
C
NOTE!
Changes are only applied after exiting
programming mode.
C
NOTE!
• The following section contains an
explanation of the most important
programming menus
current
transformer, voltage transformer
and
parameter list.
• More detailed information on the
operation, display and button
functions for your device can be found
in the user manual.
10
9
4
15
2
Safety
Safety information
The Installation manual is not a complete
directory of all safety measures required to
operate the device.
Special operating conditions may require further
measures. The Installation manual contains
instructions that must be observed to ensure
your personal safety and to prevent damage to
property.
Symbols used:
c
This symbol is an addition to the
safety instructions and indicates
an electrical hazard.
m
This symbol is an addition to the
safety instructions and indicates
a potential hazard.
C
This symbol with the word
NOTE!
describes:
• Procedures that do not pose
any risks of injures.
• Important information,
procedures or handling steps.
Safety information is highlighted by a warning
triangle and is indicated as follows depending
on the degree of danger:
m
DANGER!
Indicates an imminent danger that
causes severe or fatal injuries.
m
WARNING!
Indicates a potentially hazardous
situation that can cause severe
injuries or death.
m
CAUTION!
Indicates a potentially hazardous
situation that can cause minor
injuries or damage to property.
Safety measures
When operating electrical devices, certain parts
of these devices are invariably subjected to
hazardous voltage. Therefore, severe bodily
injuries or damage to property can occur if they
are not handled properly:
• Before connecting connections, earth the
device at the ground wire connection if
present.
• Hazardous voltages may be present in all
switching parts that are connected to the
power supply.
• Hazardous voltages may also be present
in the device even after disconnecting the
supply voltage (capacitor storage).
• Do not operate equipment with current
transformer circuits while open.
• Do not exceed the threshold values specified
in the user manual and on the rating plate.
Also adhere to this when inspecting and
commissioning.
• Observe the safety and warning instructions in
the documents that belong to the device!
Qualified staff
In order to prevent personal injuries and damage
to property, only qualified staff with electrical
training may work on the device, with knowledge
of
• the national accident prevention regulations
• the safety engineering standards
• installing, commissioning and operating the
device.
Proper use
The device is
• intended for installation in switch cabinets
and small installation distributors. It can be
installed in any mounting position (please
observe step 3 "Assembly").
• not intended for installation in vehicles!
The use of the device in mobile equipment
is considered to be non-standard
environmental conditions and is therefore
only permitted after separate agreement.
• not intended for installation in environments
with hazardous oils, acids, gases, vapours,
dusts, radiation, etc.
The prerequisites of faultless, safe operation
of this device are proper transport and proper
storage, set-up, installation, operation and
maintenance.
The UMG 96 RM is a multi-functional network
analyser, which:
• Measures and calculates electrical
variables such as voltage, current,
frequency, power, energy, harmonics
(up to the 40th harmonic), etc. in building
installations, on distribution units, circuit
breakers and busbar trunking systems.
• displays and saves measurement results
and transmits them via interfaces.
Device short description
Install the UMG 96 RM in the weatherproof front
panel of switch cabinets.
Cut-out size:
92
+0.8
x 92
+0.8
mm
Ensure!
Adequate ventilation
• install the device vertically!
• adhere to clearances from
neighbouring components!
Fig. Installation situation,
rear view UMG 96
Assembly
Connecting the supply voltage
The supply voltage level for your device is specified
on the rating plate.
After connecting the supply voltage, an indication
is shown on the display. If no indication appears,
check whether the supply voltage is within the
rated voltage range.
c
WARNING!
Risk of injury due
to electric voltage!
Serious bodily injury or death can result from:
• Contact with bare or stripped live wires.
• Device inputs that are dangerous to touch.
De-energise your device before starting
work! Check that it is de-energised.
Fuse
N
L
Fig. Connecting supply voltage.
Circuit breaker
m
CAUTION!
Damage to property due to
disregard of the connection
conditions or impermissible
voltage swells
Your device can be damaged or destroyed
by a failure to comply with the connection
conditions or by exceeding the permissible
voltage range.
Before connecting the device to the supply
voltage, please check:
•
Voltage and frequency correspond to the
details on the ratings plate! Threshold
values stipulated in the user manual
have been complied with!
•
In building installations, the supply
voltage must be protected with a UL/IEC
approved circuit breaker / a fuse!
•
The circuit breaker
-
must be easily accessible for the user
and be installed close to the device.
-
must be labelled for the relevant device.
•
Do not connect the supply voltage to the
voltage transformers.
•
Provide a fuse for the neutral conductor
if the source's neutral conductor
connection is not earthed.
Network systems
Suitable network systems and maximum rated voltages (DIN EN 61010-1/A1):
Three-phase four-conductor systems
with earthed neutral conductor
Three-phase four-conductor systems
with non-earthed neutral conductor
(IT networks)
Three-phase, three-conductor systems
Not earthed
Three-phase, three-conductor systems
with earthed phase
L1
L2
L3
E
E
N
E
L1
L2
L3
E
N
R
L1
L2
L3
E
E
L1
L2
E
E
L
N
E
E
L1
L2
L3
E
E
L1
L2
N
E
E
L1
L2
L3
E
E
N
E
L1
L2
L3
E
N
R
L1
L2
L3
E
E
L1
L2
E
E
L
N
E
E
L1
L2
L3
E
E
L1
L2
N
E
E
L1
L2
L3
E
E
N
E
L1
L2
L3
E
N
R
L1
L2
L3
E
E
L1
L2
E
E
L
N
E
E
L1
L2
L3
E
E
L1
L2
N
E
E
L1
L2
L3
E
E
N
E
L1
L2
L3
E
N
R
L1
L2
L3
E
E
L1
L2
E
E
L
N
E
E
L1
L2
L3
E
E
L1
L2
N
E
E
U
L-N
/ U
L-L
277 VLN / 480 VLL
U
L-N
/ U
L-L
277 VLN / 480 VLL
U
L-L
480 VLL
U
L-L
240 VLL
Single-phase two-conductor systems
with earthed neutral conductor
Separated single-phase,
three-conductor systems
with earthed neutral conductor
The device can be used in
• 2, 3 and 4 conductor
networks (TN, TT and
IT networks)
• Residential and
industrial applications
L1
L2
L3
E
E
N
E
L1
L2
L3
E
N
R
L1
L2
L3
E
E
L1
L2
E
E
L
N
E
E
L1
L2
L3
E
E
L1
L2
N
E
E
L1
L2
L3
E
E
N
E
L1
L2
L3
E
N
R
L1
L2
L3
E
E
L1
L2
E
E
L
N
E
E
L1
L2
L3
E
E
L1
L2
N
E
E
U
L-N
230 VLN
U
L-N
/ U
L-L
240 VLN / 480 VLL
m
CAUTION!
Risk of injuries or
damage to the device
Disregard of the connection conditions for
the voltage measurement inputs can result in
injuries or to the device being damaged.
Therefore, note the following:
•
The voltage measurement inputs
-
must not be occupied with DC voltage.
-
must be provided with a suitable,
labelled fuse that is positioned close by
and a circuit breaker (alternatively:
a line safety switch).
-
are dangerous to touch.
•
Voltages that exceed the allowed network
rated voltages must be connected via
a voltage transformer.
•
Measured voltages and currents must
derive from the same network.
C
NOTE!
As an alternative to the fuse and circuit
breaker, you can use a line safety switch.
Circuit breaker
Fuse (UL/IEC listed)
L2
L3
N
L1
Voltage measurement connection variant
3p 4w
(Addr. 509 = 0, standard setting)
C
NOTE!
With measurement range exceeding,
the measurement device display shows
"EEE". Further information on this can
be found in the user manual.
Voltage measurement connection variants
3p 4w
(Addr. 509 = 0, standard setting)
3p 4wu
(Addr. 509 = 1)
3p 4u
(Addr. 509 = 2)
3p 2u
(Addr. 509 = 5)
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
V1
V2
V3
V
N
L1
L2
L3
V1
V2
V3
V
N
L1
N
V1
V2
V3
V
N
L1
L2
V1
V2
V3
V
N
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
L1
L2
L3
L1
L2
L3
V1
V2
V3
V
N
N
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
V1
V2
V3
V
N
L1
L2
L3
V1
V2
V3
V
N
L1
N
V1
V2
V3
V
N
L1
L2
V1
V2
V3
V
N
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
L1
L2
L3
L1
L2
L3
V1
V2
V3
V
N
N
Measurement with 3 phase
conductors and neutral conductor.
Measurement via voltage
transformer with 3 phase
conductors and a neutral
conductor.
Measurement with 3 phase
conductors without neutral
conductor. Measured values which
require an N, use a calculated N.
Measurement via voltage
transformer with 3 phase
conductors without neutral
conductor. Measured values which
require an N, use a calculated N.
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
V1
V2
V3
V
N
L1
L2
L3
V1
V2
V3
V
N
L1
N
V1
V2
V3
V
N
L1
L2
V1
V2
V3
V
N
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
L1
L2
L3
L1
L2
L3
V1
V2
V3
V
N
N
1p 2w1
(Addr. 509 = 4)
2p 4w
(Addr. 509 = 3)
1p 2w
(Addr. 509 = 6)
3p 1w
(Addr. 509 = 7)
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
V1
V2
V3
V
N
L1
L2
L3
V1
V2
V3
V
N
L1
N
V1
V2
V3
V
N
L1
L2
V1
V2
V3
V
N
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
L1
L2
L3
L1
L2
L3
V1
V2
V3
V
N
N
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
V1
V2
V3
V
N
L1
L2
L3
V1
V2
V3
V
N
L1
N
V1
V2
V3
V
N
L1
L2
V1
V2
V3
V
N
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
L1
L2
L3
L1
L2
L3
V1
V2
V3
V
N
N
Measured values derived from
voltage measurement inputs V2
and V3 are taken to be 0 and are
not calculated.
System with equal loading of the
phases. The measured values of
the voltage measurement input V2
are calculated.
TN-C system with 1-phase, three-
conductor connection. Measured
values derived from voltage
measurement input V3 are taken
to be 0 and are not calculated.
3 systems with equal loading of
the phases. The measured values
for the phases that are not created
(L2/L3, L1/L3, L1/L2) for the
relevant systems are calculated.
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
V1
V2
V3
V
N
L1
L2
L3
V1
V2
V3
V
N
L1
N
V1
V2
V3
V
N
L1
L2
V1
V2
V3
V
N
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
L1
L2
L3
L1
L2
L3
V1
V2
V3
V
N
N
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
V1
V2
V3
V
N
L1
L2
L3
V1
V2
V3
V
N
L1
N
V1
V2
V3
V
N
L1
L2
V1
V2
V3
V
N
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
L1
L2
L3
L1
L2
L3
V1
V2
V3
V
N
N
c
WARNING!
Risk of injury due
to electric voltage!
Serious bodily injury or death can result from:
• Contact with bare or stripped live wires.
• Current measurement inputs that are
dangerous to touch on the device and on
the current transformers.
De-energise your device before starting
work! Check that it is de-energised.
Earth the system. Use the earth connection
points with earthing symbols for this!
Earth the secondary windings of current
transformers and all of the metal parts of
the transformer that could be touched!
L2
L3
N
L1
Load
Connection variant
3p 4w current measurement
(I1, I2, I3) via current transformer
(Addr. 510 = 0,
standard setting).
Current measurement I1, I2, I3
Connection variants for current measurement I1, I2, I3
3p 2i
(Addr. 510 = 1)
3p 2i0
(Addr. 510 = 2)
3p 3w3
(Addr. 510 = 3)
3p 3w
(Addr. 510 = 4)
L1
L2
L3
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
I1
I2
I3
I1
I2
I3
L1
L2
L1
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
I1
I2
I3
L1
L2
L3
L1
L2
L3
L1
L2
L3
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
I1
I2
I3
I1
I2
I3
L1
L2
L1
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
I1
I2
I3
L1
L2
L3
L1
L2
L3
System with equal loading of the
phases. The measured values for
current measurement input I2 are
calculated.
The measured values for current
measurement input I2 are
calculated.
Measurement in the 3-phase
network with unequal loading.
Measurement in the 3-phase
network with equal loading.
The measured values for current
measurement inputs I2 and I3 are
calculated.
L1
L2
L3
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
I1
I2
I3
I1
I2
I3
L1
L2
L1
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
I1
I2
I3
L1
L2
L3
L1
L2
L3
L1
L2
L3
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
I1
I2
I3
I1
I2
I3
L1
L2
L1
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
I1
I2
I3
L1
L2
L3
L1
L2
L3
2p 4w
(Addr. 510 = 5)
1p 2i
(Addr. 510 = 6)
1p 2w
(Addr. 510 = 7)
3p 1w
(Addr. 510 = 8)
L1
L2
L3
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
I1
I2
I3
I1
I2
I3
L1
L2
L1
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
I1
I2
I3
L1
L2
L3
L1
L2
L3
L1
L2
L3
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
I1
I2
I3
I1
I2
I3
L1
L2
L1
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
I1
I2
I3
L1
L2
L3
L1
L2
L3
System with equal loading of the
phases. The measured values for
current measurement input I2 are
calculated.
Measured values derived from
current measurement input I3
are taken to be 0 and are not
calculated.
Measured values derived from
current measurement inputs I2 and
I3 are taken to be 0 and are not
calculated.
3 systems with equal loading of
the phases. The measured values
for the phases that are not created
(L2/L3, L1/L3, L1/L2) for the
relevant systems are calculated.
L1
L2
L3
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
I1
I2
I3
I1
I2
I3
L1
L2
L1
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
I1
I2
I3
L1
L2
L3
L1
L2
L3
L1
L2
L3
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
I1
I2
I3
I1
I2
I3
L1
L2
L1
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
I1
I2
I3
L1
L2
L3
L1
L2
L3
c
WARNING!
Risk of injury due to
large currents and high
electric voltages!
Current transformers operating with an open
secondary circuit (high voltage peaks) can
result in serious or even fatal injuries.
Avoid open operation of the current transformers -
short-circuit unloaded transformers!
13
C
NOTE!
With measurement range exceeding,
the measurement device display shows
"EEE". Further information on this can
be found in the user manual.
User manual:
The voltage measurement inputs are designed for
measurements in low voltage networks, in which
rated voltages of up to
• 277 V phase to earth and 480 V phase to phase
in the 4-conductor system or
• 480 V phase to phase in the 3-conductor system
occur.
The measurement and surge voltages meet over-
voltage category 300 V CATIII.
m
CAUTION!
Damage to property due to
disregard of the installation
instructions
Failing to observe the installation instructions
can damage or destroy your device.
Ensure that there is adequate air circulation in your
installation environment; if the ambient temperatures
are high, ensure there is adequate cooling if required.
C
NOTE!
For further information on device functions, data and assembly, see the user manual.
Programming parameters
1. Switch to programming mode.
2. The symbols for programming mode
PRG and
for the current transformer
CT appear.
3. Press button 2 twice to change to the
programming mode for the parameter list.
4. The input area of the parameter list appears.
Parameter address
Programming mode
Parameter setting
Fig. "Parameter list"
input field
C
NOTE!
• A detailed parameter list with setting
areas and pre-settings can be found
in the user manual or the Modbus
address list on our website.
• The parameter addresses of the
device address (000) and the Baud
rate (001) are explained in the
following.
5. Confirm with button 1 - the first digit of the
parameter address flashes.
6. Use button 2 to select the value of the
1st digit.
7. Continue the process for the next digits of
the parameter address and for the parameter
settings.
8. Exit programming mode by simultaneously
pressing button 1 and 2 (1 second).
Use button 2 to change back to the input
field for the current transformer.
Set the device address (parameter address 000)
In a Master-Slave network via the RS485 interface,
a master device can distinguish between the UMGs
on the basis of the device address.
In the case of devices within this network, for the
parameter address 000 please note
• you must assign different device addresses.
• the parameter setting of the parameter address
000 must lie within the range of 1 to 247
(0 and 248 to 255 are reserved).
Set the Baud rate (parameter address 001)
In a Master-Slave network via the RS485 interface, for
each device:
• select a uniform Baud rate (parameter address 001)
(for settings see the user manual).
• select the number of stop bits (parameter
address 003) (0=1 Bit, 1=2 Bits).
Data bits (8) and parity (none) are pre-set.
The device is operated with buttons 1 and 2,
whereby the following distinctions are made:
• Short press (button 1 or 2):
Next step (+1).
• Long press (button 1 or 2):
previous step (-1).
The device differentiates between display and
programming mode.
Display mode
• You can use buttons 1 and 2 to scroll between
the measured value indications.
• The measured value indication shows up to
3 measured values.
• A time for an automatic indication change
between the measured value indications can
be configured in the GridVis® software.
Programming mode
• Press and hold buttons 1 and 2 simultaneously
for 1 second to switch between
display mode
and
programming mode
. The text
PRG
appears in the display.
• Configure the necessary settings for the
operation of the device in programming mode.
Operation and button functions
Fig. Display UMG 96 RM
Button 1
Button 2
Export
Mean value
CT: Current
transformer
VT:
Voltage
transformer
K1: Output 1
K2: Output 2
Password
Phase conductor-
Phase conductor
Summation
measurement
Programming
mode
Min. value NT/export
Max. value, HT/reference
• The programming mode can be protected with
a user password.
• Button 2 switches between the programming
menus:
1.
Current transformer
2.
Voltage transformer
3.
Parameter list
To switch from
programming mode
to
display mode
,
• press buttons 1 and 2 simultaneously for 1 second.
• do not press any buttons for 60 seconds (automatic).
Programming the current transformer
1. Switch to programming mode.
2. The symbols for programming mode
PRG
and for the current transformer
CT appear.
3. Press button 1 - the first digit of the input
field for the primary current flashes.
4. Use button 2 to select the value for the
1st digit.
5. Use button 1 to move to the 2nd. digit.
6. Use button 2 to select the value of the
2nd digit.
7. Use button 1 to move to the 3rd digit.
8. Use button 2 to select the value of the
3rd digit.
9. Confirm with button 1.
10. The complete number flashes.
11. Use button 2 to select the decimal place and
thus the unit of the primary current.
12. Confirm with button 1.
13. The input range of the secondary current
flashes.
14. Use button 2 to set the secondary current
(value 1 A or 5 A).
15. Confirm with button 1.
16. Pressing buttons 1 and 2 simultaneously
(1. sec.) exits the programming mode.
Use button 2 to change to the input field for
the voltage transformer.
Current transformer
symbol
Unit indicator
Current transformer,
primary
Programming mode
Current transformer,
secondary
C
NOTE!
• Changes are only applied after exiting
programming mode.
• For further information on current
transformers and current transformer
ratios, see the user manual.
Fig. "Current transformer" input area
Programming voltage transformers
1. Switch to programming mode.
2. The symbols for programming mode
PRG
and for the current transformer
CT appear.
3. Use button 2 to change to programming
mode for the voltage transformer.
4. The symbols for Programming mode
PRG,
and for the voltage transformer
VT appear.
5. Press button 1 to confirm - the first digit
of the input area for the primary voltage
flashes.
6. Use button 2 to select the value of the
1st. digit.
7. Use button 1 to move to the 2nd. digit.
8. Use button 2 to select the value of the
2nd digit.
9. Use button 1 to move to the 3rd digit.
10. Use button 2 to select the value of the
3rd digit.
11. Confirm with button 1.
12. The complete number flashes.
13. Use button 2 to select the decimal place and
thus the unit of the primary voltage.
14. Confirm with button 1.
15. The input range of the secondary voltage
flashes.
16. Set the secondary voltage with button 2.
17. Confirm with button 1.
18. Pressing buttons 1 and 2 simultaneously
(1. sec.) exits the programming mode. Use
button 2 to change to the programming
mode for the parameter list.
C
NOTE!
• Changes are only applied after exiting
programming mode.
• Further information on voltage trans-
formers and voltage transformer ra-
tios can be found in the user manual.
Unit indicator
Voltage transformer,
primary
Programming mode
Voltage transformer,
secondary
Voltage transformer
symbol
Fig. "Voltage transformer" input area
www
.janitza.com
Janitza electronics GmbH
Vor dem Polstück 6
D-35633 Lahnau / Germany
Support tel. +49 6441 9642-22
Fax +49 6441 9642-30
e-mail: [email protected]
Website: http://www.janitza.com
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
V1
V2
V3
V
N
L1
L2
L3
V1
V2
V3
V
N
L1
N
V1
V2
V3
V
N
L1
L2
V1
V2
V3
V
N
L1
L2
L3
N
V1
V2
V3
V
N
L1
L2
L3
L1
L2
L3
L1
L2
L3
V1
V2
V3
V
N
N
Disclaimer
The observance of the information products for
the devices is a prerequisite for safe operation
and to achieve the stipulated performance
characteristics and product characteristics.
Janitza electronics GmbH accepts no liability
for injuries to personnel, property damage
or financial losses arising due to a failure to
comply with the information products. Ensure
that your information products are accessible
and legible.
Further information can be found on our web-
site www.janitza.com at Support > Downloads.
Copyright notice
© 2016 - Janitza electronics GmbH - Lahnau.
All rights reserved. Duplication, editing,
distribution and any form of exploitation, also
as excerpts, is prohibited.
Subject to technical amendments
• Make sure that your device agrees with the
installation manual.
• Read and understand first product-related
documents.
• Keep product supporting documentation
throughout the life available and, where ap-
propriate, to pass on to subsequent users.
• Please inform yourself about device revisi-
ons and the associated adjustments to the
product-related documentation on
www.janitza.com.
Disposal
Please observe national regulations!
If disposing of individual parts, please dispose
of them in accordance with their nature and
existing country-specific regulations, for
example as:
• Electrical scrap
• Plastics
• Metals
Or, task a certified disposal business with the
scrapping.
Relevant laws, applied standards and
directives
The laws, standards and directives for the
device applied by Janitza electronic GmbH
can be found in the declaration of conformity
on our website.
Technical data
Voltage measurement
3-phase 4-conductor
systems with rated
voltages of up to
277 V/480 V (+-10%)
3-phase 3-conductor
systems, not earthed, with
rated voltages of up to
IT 480 V (+-10%)
Overvoltage category
300 V CAT III
Rated surge voltage
4 kV
Protection
of voltage measurement
1 - 10 A
(with IEC-/UL approval)
Metering range L-N
0
1)
to 300 Vrms
(max. overvoltage 520 Vrms )
Metering range L-L
0
1)
to 520 Vrms
(max. overvoltage 900 Vrms )
Resolution
0.01 V
Crest factor
2.45 (based on metering range)
Impedance
4 MOhm / phase
Power consumption
approx. 0.1 VA
Sampling rate
21.33 kHz (50 Hz),
25.6 kHz (60 Hz)
for each measurement channel
Frequency range of the
fundamental oscillation -
resolution
45 Hz to 65 Hz
0.01 Hz
1) ... The device determines measured values only if the Voltage
measurement input V1 voltage L1-N greater than 20 Vrms
(4-wire measurement) or a voltage L1-L2 of larger 34 Vrms
(3-wire measurement) is applied.
Current measurement I1 - I4
Nominal current
5 A
Metering range
0 to 6 Arms
Crest factor
1.98
Resolution
0.1 mA (display 0.01 A)
Overvoltage category
300 V CAT II
Rated surge voltage
2 kV
Power consumption
approx. 0.2 VA (Ri = 5 mOhm)
Overload for 1 sec.
120 A (sinusoidal)
Sampling rate
21.33 kHz (50 Hz),
25.6 kHz (60 Hz)
for each measurement channel
C
NOTE!
Further technical data can be found in the
use manual for the device.
Supply voltage
Nominal range
Option 230 V:
AC 90 V - 277 V (50/60 Hz) or
DC 90 V - 250 V, 300 V CATIII
Option 24 V:
AC 24 V - 90 V (50/60 Hz) or
DC 24 V - 90 V, 150 V CATIII
Operating range
+-10% of the nominal range
Power consumption
Option 230 V: max. 5,5 VA / 3 W
Option 24 V: max. 4,5 VA / 3 W
Internal fuse,
not replaceable
Type T1A / 250 VDC / 277 VAC
according to IEC 60127
Recommended over-
current protection device for
the line protection
Option 230 V: 6-16 A
Option 24 V: 1-6 A
(Char. B)
(IEC/UL approval)
Establish the connection to the PC
The most common connections for
communication between the PC and the device:
1.
m
CAUTION!
Damage to property due to
incorrect network settings
Incorrect network settings can cause faults in
the IT network!
Obtain information from your network
administrator about the correct Ethernet
network settings for your device.
More details on device configuration and
communication can be found from section 11.
2.
(gedrehtes Patchkabel)
PC
RS232 RS232
RS485
UMG 96 RM
UMG 96 RM
Connection of the UMG 96 RM
via interface converter.
(gedrehtes Patchkabel)
PC
UMG 604
Connection of the UMG 96 RM
via a UMG 604 as a gateway.
Ethernet
UMG 96 RM
Fig. Rear side
UMG 96 RM
UMG 96 RM
RS485
RS485
RS485
RS485
Example: PC connection via RS485 interface and UMG 604 as gateway
Correct
Incorrect
Terminal strip (switch cabinet).
Device with RS485 interface
(without termination resistor).
Device with RS485 interface
(termination resistor on the
device).
RS485 bus
e.g. connection
of further
Slave devices
A
B
RS485 interface
2 pin plug contact
with termination resistor
120 Ω,
0.25 W
RS485 bus
Connection to
the UMG 604
as gateway (Master)
e.g. connection
of further
Slave devices
A
B
RS485 interface
2 pin plug contact
The UMG 96 RM communicates with a PC via
the serial RS485 interface and a UMG 604 as
gateway:
C
NOTE!
In order to include the UMG 96 RM in an RS485
bus structure (master-slave principle) with
UMG 604 as a master device, first
• enter a
1 in address 203 of the UMG 604
(Modbus RTU/master)!
C
NOTE!
For further information on parameter lists,
device addresses and Baud rates, see the
user manual.
RS485 bus structure
• In an RS485 bus structure (line), connect
all devices according to the master-slave
principle.
• One segment in an RS485 bus structure can
contain up to 32 participants/devices.
• Terminate the cable at the start and the end of
a segment with termination resistors (120 Ω,
0.25 W). The UMG 96 RM does not contain
any termination resistors.
• With more than 32 subscribers, repeaters
must be used to connect segments.
Procedure in the event of faults
Possible fault
Cause
Remedy
No display
External fusing for the power supply voltage has
tripped.
Replace fuse.
No current display
Measurement voltage is not connected.
Connect the measuring-circuit voltage.
Measurement current is not connected.
Connect measuring-circuit current.
Current displayed is too large
or too small.
Current measurement in the wrong phase.
Check connection and correct if necessary.
Current transformer factor is incorrectly programmed. Read out and program the current transformer trans-
formation ratio at the current transformer.
The current peak value at the measurement input
was exceeded by harmonic components.
Install current transformer with a larger transforma-
tion ratio.
The current at the measurement input fell short of.
Install current transformer with a suitable transfor-
mation ratio.
Voltage displayed is too large
or too small.
Measurement in the wrong phase.
Check connection and correct if necessary.
Voltage transformer incorrectly programmed.
Read out and program the voltage transformer trans-
formation ratio at the voltage transformer.
Voltage displayed is too
small.
Overrange.
Install voltage transformers.
The peak voltage value at the measurement input has
been exceeded by harmonic components.
Caution! Ensure the measurement inputs are not
overloaded.
"EEE" in the display
See „error messages“ in the user manual.
Device still does not work
despite the above measures.
Device defective.
Send the device to the manufacturer for inspection
and testing along with an accurate fault description.
Digital outputs
2 digital outputs, semiconductor relays, not short-circuit proof.
Switching voltage
max. 33 V AC, 60 V DC
Switching current
max. 50 mAeff AC/DC
Response time
10/12 p 10 ms *
Pulse output (energy pulse)
max. 50 Hz
* Response time e.g. at 50 Hz: 200 ms + 10 ms = 210 ms
Serial interface
RS485 - Modbus RTU/Slave
9.6 kbps, 19.2 kbps,
38.4 kbps, 57.6 kbps,
115.2 kbps
Stripping length
7 mm
Terminal connection capacity (power supply voltage)
Conductors to be connected.
Only one conductor can be connected per terminal!
Single core, multi-core,
fine-stranded
0.2 - 2.5 mm
2
, AWG 26 - 12
Terminal pins, core end sheath
0.2 - 2.5 mm
2
Tightening torque
0.4 - 0.5 Nm
Stripping length
7 mm
Terminal connection capacity (digital outputs)
Single core, multi-core,
fine-stranded
0.2 - 1.5 mm
2
, AWG 28-16
Terminal pins, core end sheath
0.2 - 1.5 mm
2
Tightening torque
0.2 - 0.25 Nm
Stripping length
7 mm
Terminal connection capacity (current measurement)
Conductors to be connected.
Only one conductor can be connected per terminal!
Single core, multi-core,
fine-stranded
0.2 - 2.5 mm
2
, AWG 26-12
Terminal pins, core end sheath
0.2 - 2.5 mm
2
Tightening torque
0.4 - 0.5 Nm
Stripping length
7 mm
Terminal connection capacity (serial interface)
Single core, multi-core,
fine-stranded
0.2 - 1.5 mm
2
, AWG 28 - 16
Terminal pins, core end sheath
0.2 - 1.5 mm
2
Tightening torque
0.2 - 0.25 Nm
Stripping length
7 mm
Terminal connection capacity (voltage measurement)
Conductors to be connected.
Only one conductor can be connected per terminal!
Single core, multi-core,
fine-stranded
0.08 - 4.0 mm
2
, AWG 28-12
Terminal pins, core end sheath
0.2 - 2.5 mm
2
Tightening torque
0.4 - 0.5 Nm
Stripping length
7 mm
General information
Net weight
(with attached connectors)
approx. 265 g
Packaging weight
(including accessories)
approx. 300 g
Service life of
background lighting
40000 h
(after this period of time
the background lighting
efficiency will reduce by
approx. 50%)
Transport and storage
The following information applies to devices which are trans-
ported or stored in the original packaging.
Free fall
1 m
Temperature
K55 (-25° C to +70° C)
Relative humidity
0 to 90% RH
Ambient coditions during operation
The device is intended for weather-protected, stationary use.
Protection class II i.a.w. IEC 60536 (VDE 0106, Part 1).
Operating temperature range
K55 (-10° C .. +55° C)
Relative humidity
0 to 75% RH
Operating altitude
0 .. 2000 m above sea level
Degree of pollution
2
Mounting position
vertical
Ventilation
Forced ventilation is
not required.
Protection against ingress
of solid foreign bodies and
water
- Front side
- Rear side
- Front with seal
IP40 i.a.w. EN60529
IP20 i.a.w. EN60529
IP54 i.a.w. EN60529