Page 70
Analog output
The UMG96S with the additional printed circuit
board 1 has 2 analog outputs. Each analog out-
put can output a current of 4-20mA. An exter-
nal 24VDC power supply unit is required for its
operation.
Four parameters must be programmed for one
analog output.
Input/Output (Add 002, 003)
Connect the analog output to the terminals of
the UMG96S.
Measured value (Add 047, 052)
The measured value which is to be output at
the analog output.
Scale start value (Add 050, 054)
The scale start value equals the measured
value at which the minimum current of 4mA is
to flow.
Scale end value (Add 048, 053)
The scale end value (full-scale value) equals
the measured value at which the maximum cur-
rent of 20mA is to flow.
UMG96S
12
13
11
R
J
1
1
s
o
c
k
e
t
TXD
GND
RXD
Input/Output 2 (003)
Pulse output Wq (003 = 0)
Digital output
(003 = 1)
Analog output (003 = 2)
Digital input
(003 = 3.5)
Remote profibus (003 = 4)
Input/Output 1 (002)
Pulse output Wp (002 = 0)
Digital output
(002 = 1)
Analog output (002 = 2)
Digital input
(002 = 3.5)
Remote profibus (002 = 4)
Clock with battery
Data memory
Additional printed
circuit board 1
C
o
m
p
a
ra
to
r
g
ro
u
p
1
C
o
m
p
a
ra
to
r
g
ro
u
p
2
Master board
RS232 (MODBUS RTU)
Interface
S
e
ri
a
l
in
te
rf
a
c
e
Analog output 2
Measured value (052)
Scale start value, 4mA (054)
Scale end value, 20mA
(053)
Analog output 1
Measured value (047)
Scale start value, 4mA (050)
Scale end value, 20mA
(048)