janitza UMG 96-S2 Datasheet Download Page 3

08/2018 / Datasheet UMG 96-S2 – 3

UMG 96-S2

TECHNICAL DATA

General information

Net weight (with attached connectors)

Approx. 250 g

Packaging weight (including accessories)

Approx. 500 g

Impact resistance

IK07 according to IEC 62262

Transport and storage

The following information applies to devices which are transported and stored in the original packaging.
Free fall

1 m

Temperature

K55 (-25 C up to +70 C)

Relative humidity

0 to 90% RH

Ambient conditions during operation

Use the UMG 96-S2 in a weather-protected, stationary application. Protection class II in accordance with IEC 60536 
(VDE 0106, Part 1).
Operating temperature range

K55 (-10 C .. +55 C)

Relative humidity

0 to 75% RH

Operating altitude

0 .. 2000 m above sea level

Degree of pollution

2

Installation position

discretionary

Ventilation

no external ventilation required

Protection against foreign bodies and water
- Front
- Rear
- Front side with sealing

 
IP40 i.a.w. EN60529
IP20 i.a.w. EN60529
IP54 i.a.w. EN60529

Supply voltage

Nominal range

AC 90 V - 265 V (50/60 Hz) or 
DC 90 V - 250 V, 300 V CATIII

Operating range

+-10% of nominal range

Power consumption

max. 1.5 VA / 0.5 W

Internal fuse, 
not exchangeable

Type T1A / 250 VDC / 277 VAC 
according to IEC 60127

Recommended overcurrent protection device 
for the line protection

6-16 A (Char. B, IEC-/UL approval)

Voltage measurement

3-phase 4-conductor systems with nominal voltages up to 230 V/400 V (+-10%) according to IEC
Overvoltage category

300 V CAT III

Measurement voltage surge

4 kV

Fuse for the 
voltage measurement

1 - 10 A 
(with IEC/UL approval)

Measuring range L-N

0

1)

 .. 300 Vrms

(max. overvoltage 400 Vrms)

Measuring range L-L

0

1)

 .. 425 Vrms

(max. overvoltage 620 Vrms)

Measurement range exceedance L-N

U

L-N

 > 300 Vrms

Resolution

0.01 V

Crest factor

1.9 (related to the measurement range)

Impedance

3 MΩ/phase

Power consumption

Approx. 0.1 VA

Sampling frequency

8 kHz

Frequency of the 
basic oscillation 
 - resolution

45 Hz .. 65 Hz
0.01 Hz

1)

 The device only determines the measured values if voltage L1-N is greater than 20 Veff (4-conductor measurement) or voltage L1-L2 

is greater than 34 Veff (3-conductor measurement) on voltage measurement input V1.