background image

8

Short button press:
• 

Scroll forwards

• 

Number/Value +1

Long button press:
• 

Scroll backwards

• 

Number/Value -1

Press and hold both buttons simultaneously for 
approx. 1 second:
• 

Switch between display mode and 
programming mode.

The UMG 604/605 is operated via but-
tons 1 and 2.

Button Functions

Button 1 and Button 2

9

Programming Mode

You can view and change the most important 
settings for operating the UMG 604/605 in 
programming mode. 
The operating manual lists the addresses for 
the most important settings. Additional settings 
are accessible using the supplied GridVis 
software.

Press button 1 and 2 simultaneously for about 
1 second to switch to programming mode after 
entering the password. 
Programming mode is identified by the 
text "PRG" on the display. The first digit of 
the address flashes.

If no button has been pressed for about 
60 seconds when you are in programming mode, 
or button 1 and 2 are pressed simultaneously for 
about 1 second, the device will switch back to 
display mode. 

Address

Contents

PRG  

Fig. Example "Programming mode" display, 
Address 000 with a contents of 5,000.

10

Fixed IP address (Adr. 205, Contents = 0)

On simple networks without a DHCP server, 
the network address (see table) must be set on 
the device itself. 

BootP (Adr. 205, Contents = 1)

BootP allows for the fully automatic integration 
of a UMG 604/605 into an existing network. 
However, BootP is an older protocol and does 
not provide the scope of functions provided by 
DHCP.

DHCP mode (Adr. 205, Contents = 2)

DHCP allows for the fully automatic integration 
of a UMG 604/605 into an existing network 
without additional configuration. When started, 
the UMG 604/605 automatically pulls the IP 
address, the network mask and the gateway 
from the DHCP server. 

The factory default for the UMG 604/605 is 
"DHCP client".

Configuring the Ethernet 

Connection

Adr.

Description

205

DHCP mode
  0 = Fixed IP 

1 = BootP

  2 = DHCP client 

3 = Zeroconf

300

IP address,  xxx  ---  ---  ---

301

IP address,  ---  xxx  ---  ---

302

IP address,   ---  ---  xxx  ---

303

IP address,   ---  ---  ---  xxx

304

IP mask,  

xxx  ---  ---  ---

305

IP mask,  

---  xxx  ---  ---

306

IP mask,  

---  ---  xxx  ---

307

IP mask,  

---  ---  ---  xxx

310

IP gateway,   xxx  ---  ---  ---

311

IP gateway,   ---  xxx  ---  ---

312

IP gateway,   ---  ---  xxx  ---

313

IP gateway,   ---  ---  ---  xxx

3

If the device is not operated 
according to the operating manual, 
protection is no longer ensured 
and hazards can be presented by 
the device.

m

The UMG 604/605 can be installed in switch 
cabinets or on small distribution boards in ac-
cordance with DIN 43880. It must be installed on 
a 35mm mounting rail in accordance with DIN EN 
60715. It can be installed in any position.

Fig. The UMG604 on a mounting rail 
in accordance with DIN EN 60715

Selecting an Installation Location

General

Please read the operating manual enclosed as 
well as all other publications that must be drawn 
upon for working with this product (in particular 
for the installation, operation or maintenance).

Follow all safety regulations and warning 
information. If you do not follow the information, 
it can result in bodily injury and/or damage to 
the product.

This device is to be operated and maintained 
exclusively by specialised personnel.

Safety Information

1

If the device is not operated 
according to the enclosed operating 
manual, protection is no longer 
ensured and hazards can be 
presented by the device.

Disconnect system and device from 
power supply before beginning 
work.

Grounding of current transformers
If a connection is provided for 
the grounding of secondary windings 
then this must be connected to 
the ground.

Measuring voltages phase to ground 
beyond 300 VAC must be connected 
via potential transformers” 

c

c
c

c

Voltages and currents outside the 
permissible measuring range can 
damage the device.

Conductors made from single wires 
must be fitted with wire-end ferrules.

The UMG 604/605 is not suitable for 
measuring DC voltages.
 

Only pluggable screw terminals 
with the same number of poles and 
the same type of construction are 
permitted to be connected together.

The digital outputs are not short-
circuit proof.

m
m

m
m

m

2

Safety Information

Connection of the UMG 604/605 to 
the ethernet may only be carried out 
after discussion with the network 
administrator!

Pay attention to the polarity of 
the supply voltage for the digital 
inputs!

Measured voltage and measured 
current must be derived from 
the same network.

Profibus, RS232, RS485 and 
temperature measurement input are 
not galvanically separated.

m

m
m
m

In the electrical installation, a 
disconnector or circuit-breaker must 
be provided for the supply voltage.
The disconnector must be installed 
near the device and easily accessible 
to the user.
The switch must be marked as 
the circuit breaker for this device.
Voltages which are over the permitted 
voltage range can destroy the device.

m

GridVis Software
Settings

Install the GridVis software on your computer 
and proceed as follows:

• 

Using the "

File

" menu, create a new project 

or open an existing project.

• 

Insert the new device into the project (e.g. 
using the menu item "

New file

" or from 

the context menu, by clicking the right 
mouse button on "

By device type

").

• 

Set the 

Connection type

 under "

Connection 

type

" to "

TCP/IP

".

• 

Enter the IP address of the UMG 604/605 (cf. 
"View the IP address on the device", step 13)

• 

Perform a 

Connection test

.

• 

Once the connection test has been 
successfully completed, the device can be 
configured via "

Configure

".

16

Fig. The context menu 

Fig. Configuring the connection

GridVis Software

Device Configuration

In the "

Projects

" window, right-click the device 

to open the context menu and select 
"

Configuration

".

• 

Under "

Identity

", assign an device name of 

your choosing. 

• 

Under "

Transformers

" set the voltage and 

current transformer ratio.

• 

Under "

Measuring variants

" set 

the connection variant for the device 
for voltage and current measuring (see 
operating manual).

• 

Under "

Nominal values

" select the mains 

frequency in accordance with the available 
grid conditions. Nominal values are required 
as a reference to identify events (over/
undervoltage and overcurrent).

17

Fig. Device configuration menu, Transformer 
settings

m

The device configuration settings 
described in this brief overview only 
represent the basic settings. Other device 
settings are advisable and required for 
some functions.

Connecting the Supply Voltage

The UMG 604/605 needs a supply voltage to op-
erate. The type and size of the required supply 
voltage is noted on the rating plate.

Before connecting the supply voltage, ensure 
that the voltage and frequency correspond to the 
details on the rating plate!

The connection cables for the supply voltage 
must be safeguarded by a UL-listed fuse 

 

(6A type C).

Supply voltage Uh

Circuit breaker

Fuse

Fig. Example connection for 
supply voltage Uh

4

The inputs for the supply voltage are 
hazardous if touched!

c

The UMG 604/605 is designed for measuring AC 
on 300 V (phase/neutral) / 480 V (phase/phase) 
networks, in which Category III overvoltages can 
occur. 
The UMG 604/605 can only determine values, if 
a measuring-circuit voltage higher than 10Veff 
is present at at least one voltage measurement 
input.

Measuring Voltages

6

Fig. Example connection: measuring voltages 
using short-circuit-resistant measuring lines

L3

N

L1

L2

Disconnectors

10A

(UL listed)

The voltage measurement inputs 
are dangerous to touch! 

c

Refer to the enclosed operating 
manual for information!

m

7

Establishing the Ethernet 
Connection

Establish a PC to device connection, either by 
means of a direct connection or via a switch/
router. 

Use of CAT5 cables is recommended.

Fig. Example connection: the UMG 604/605 and 
PC require a fixed IP address.

Switch

Patch cable

Patch cable

PC

UMG604/605

Fig. Example connection: the UMG 604/605 and 
PC are assigned the IP address automatically by a 
DHCP server.

Patch cable

Patch cable

DHCP
server

PC

UMG604/605

Switch

Ethernet port

PC

UMG604/605

Ethernet 

(Twisted patch cable)

Fig. Example connection: direct connection 
between UMG 604/605 and PC. Both devices 
require a fixed IP address.

12

If DHCP mode has been deactivated and you 
want to configure access over a fixed IP address, 
you will need to enter the device IP address, 
subnet mask and the gateway address (cf. step 
10)

Setting the device IP address
• 

Select Programming mode.

• 

Set the address 300 as described and set 
the first block of three digits of the device IP 
address (cf. table, step 10)

• 

Then set the address 301 and allocate 
the second block of the device IP address. 

• 

Complete the entries with the addresses 
302 and 303

Setting the subnet mask
• 

Set the subnet mask, using the same 
method as for configuring the device IP 
address, with addresses 304 to 307 (cf. 
table, step 10).

Setting a Fixed-IP-Address

Setting the standard gateway
• 

Set the standard gateway (if present), 
in the same way as IP address, with 
addresses 310 to 313 (cf. table, step 10).  
Note: Usually a gateway setting is not 
required for the configuration!

Example:
IP-Address:  

192.168.178.111

Subnet mask:  

255.255.255.0

In this case the Computer has to be set 
as follows:
IP-Address: 192.168.178.112
Subnet mask: 

255.255.255.0

See as well points 13 - 15 please!

13

Computer Settings

Make sure that your PC is connected to the same 
subnet as the UMG.

This means that the first three blocks of the 
IP address should be identical to the UMG 
IP address. The last three figures (xxx) of the 
address must be different from the UMG IP 
address. The subnet mask must match 100% in 
all four of the three digit blocks.

Example IP address: 192.168.211.

xxx

Subnet mask: 255.255.255.0

• 

If the UMG is being operated in DHCP 
mode, the device's IP address is assigned 
automatically (cf. step 11).

• 

In "Fixed IP address" mode, the address 
of the device must be configured manually 
using the relevant settings (cf. step 12).

Checking the connection

View the IP address on the device:

Select programming mode on the UMG. Set 
the address to 300, using button 1 and 2 and 
note down the three figures in the Contents area. 
Carry out the same step for addresses 301 to 
303 (cf. table under step 10). 

Check the device connection:

• 

Press the Windows key and open the "

DOS

window by typing "

CMD

" followed by 

the Return key 

• 

Execute the command "

ping

" followed 

by the device IP address (e.g. "

ping 

192.168.211.27

").

• 

If the device can be reached with this 
command, this represents a positive 
answer.

It is also possible to check the connection 
by entering the device IP address into a web 
browser (e.g. "

http://192.168.211.27

"), and call 

up the device's homepage.

GridVis Software

Device Configuration

• 

Under "

Recording configuration

" you 

can check/configure which recordings 
the measurement device should save. 
A record holds a measurement value or 
the mean value of the measurement value.

• 

If transient records and event records are 
to be compared with other measurement 
records, it is recommended to compare 
the time with a time server. In this case, 
activate the service and enter an NTP time 
server.

18

Fig. Device recording configuration

If changes have been made to the device 
configuration, they must be saved to 
the device using the "

Transmit

" button.

m

11

Activating DHCP mode (default)

• 

Select programming mode as described.

• 

Set the address to 205. To do so, use 
button 2 to set the first digit to the value 2. 
Then switch to the second digit with button 
1 and set it to a value of 0 with button 2. Set 
the third digit to a value of 5 in the same 
way.

• 

Once the address is set, switch to 
the setting with button 1. Use button 2 to 
set the setting to a value of 2 (cf. table, step 
10).

• 

For further settings use button 1 to go back 
and enter the next address.

Setting DHCP- or 
Fixed-IP-Mode

Activating Fixed IP address

• 

Select programming mode as described.

• 

Set the address to 205. To do so, use 
button 2 to set the first digit to the value 2. 
Then switch to the second digit with button 
1 and set it to a value of 0 with button 2. Set 
the third digit to a value of 5 in the same 
way.

• 

Once the address is set, switch to 
the setting with button 1. Use button 2 to 
set the setting to a value of 0 (cf. table, step 
10).

• 

For further settings use button 1 to go back 
and enter the next address.

To ensure correct operation, make sure that address 204 has been assigned a value of 0 
(factory setting)!

m

Fig. Example connection, current measurement 
via current transformers

5

Measuring Currents

The UMG 604/605 is intended for the connection 
of current transformers with secondary currents 
of ../1A and ../5A. Only AC currents can be 
measured - DC currents cannot.
Any of the current measurement inputs can be 
permanently loaded with max. 6A or max. 100A 
for 1 second. 

The current measurement inputs are 
dangerous to touch.

c

Refer to the enclosed operating 
manual for information!

m

Loads

L2

N

L3

L1

S

1

S

2

S

1

S

2

S

1

S

2

S

1

S

2

Janitza electronics GmbH
Vor dem Polstück 1
D-35633 Lahnau / Germany
Support tel. +49 6441 9642-22
Fax +49 6441 9642-30
e-mail: [email protected]
Website: http://www.janitza.com

www

.janitza.com

Power Analyser

UMG 604

 

/

 

UMG 605

Quick guide

Supplement to the UMG 604

 

/

 

UMG 605 Operating Instructions

 

Installation

 

Communications settings via ethernet

 

GridVis settings

Deutsche V

ersion:

siehe Rückseite

Checking the Computer's IP 
Address:

• 

Press the 

Windows key

.

• 

Open a DOS window by entering "

CMD

followed by the Return key.

• 

Enter "

Ipconfig

".

• 

The IP address and subnet mask of your PC 
are displayed.

• 

You can also view the required information 
(IP address, subnet mask) via the 

Network 

and Sharing Center

 in the Windows 

Control 

Panel

:

• 

In the 

Network and Sharing Center

, click on 

Local Area Connection

 to open the status 

window for the LAN connection.

• 

The button 

Details

 calls up the IP address 

and subnet mask.

14

How do I set a Fixed-IP-
Address for the PC? 

PCs on company networks normally use DHCP.

 

If you could like to assign a fixed IP address for 
the PC (e.g. for a direct PC to UMG 604/605 
connection), proceed as follows:

• 

Open the 

Network and Sharing Center

 in 

the Windows 

Control Panel

.

• 

Open the status window by clicking on 

Local Area Connection

.

• 

By selecting "

Properties

", it is possible to 

assign a fixed IP address to the PC.

15

Reviews: