UMG 512-PRO
www.janitza.com
22
5. Mounting
5.1
Installation location
The device is suitable for installation in stationary
and weatherproof switchboards indoors.
Provide grounding for conductive switchboards.
DANGER
Danger of electric shock!
Electric shocks lead to serious injuries, including
death.
·Disconnect your system from the power supply
before mounting and connecting the device!
·Secure it against being switched on!
·Check to be sure it is de-energized!
·Ground and short circuit!
·Cover or block off adjacent live parts!
·The installation must only be carried out by
qualified personnel with electrical training!
5.2
Mounting orientation
The cut-out dimension in the switchboard is
138
+0.8
mm x 138
+0.8
mm.
To achieve adequate ventilation, observe the fol-
lowing instructions:
·Install the device vertically.
·Maintain a minimum clearance of 50 mm to-
wards the top and bottom.
·Maintain a minimum clearance of 20 mm to-
wards the sides.
5.3
Securing
The device is fastened to the switchboard with
two fastening clips, one at the bottom and one at
the top. The fastening clips are first hooked onto
the device.
Fig. Arrangement of the fastening clips on the UMG 512-
PRO
ATTENTION
Material damage due to disregard of the instal-
lation instructions!
Disregard of the installation instructions can
damage or destroy your device.
Observe the information on the mounting
orientation in the sections „5. Mounting“ and
„15. Technical data“.
Fig. Rear view of the mounting orientation of the
UMG 512-PRO
Wall
Airflow
Airflow