www.janitza.com
103
UMG 512-PRO
15.2 Voltage and current measurement
Current measurement
Nominal current
5 A
Resolution
0.1 mA
Measuring range
0.005 .. 7 Arms
Overrange (overload)
from 8.5 Arms
Crest factor
1.41
Overvoltage category
Option 230 V: 300 V CAT III
Option 24 V: 300 V CAT II
Rated surge voltage
4 kV
Power consumption
approx. 0.2 VA (Ri=5 mOhms)
Overload for 1 s
120 A (sinusoidal)
Sampling frequency
25.6 kHz / phase
Voltage measurement
The voltage measurement inputs are suitable for measurement in the following power supply sys-
tems:
Three-phase 4-conductor systems with
rated voltages up to
417 V / 720 V (+10%)
347 V / 600 V (UL listed)
Three-phase 3-conductor systems with
rated voltages up to
600 V (+10%)
The voltage measurement inputs are designed as follows from the point of view of safety and reliabil-
ity:
Overvoltage category
600 V CAT III
Rated surge voltage
6 kV
Protection of the voltage measurement
1-10 A
Measuring range L-N
0
1)
.. 600 Vrms
Measuring range L-L
0
1)
.. 1000 Vrms
Resolution
0.01 V
Crest factor
1.6 (referred to 600 Vrms)
Impedance
4 MOhms/phase
Power consumption
approx. 0.1 VA
Sampling frequency
25.6 kHz / phase
Transients
39 µs
Udin
2)
according to EN61000-4-30
100 .. 250 V
Flicker range (dU/U)
27.5%
Frequency of the fundamental oscillation
·Resolution
15 Hz .. 440 Hz
0.001 Hz
1) The device can only determine measured values if a voltage L-N greater than 10 Vrms or a voltage L-L greater than 18 Vrms is present on at least one voltage measure-
ment input.
2) Udin = Agreed input voltage according to DIN EN 61000-4-30
Measuring accuracy, phase angle
0.075 °
Summary of Contents for UMG 512-Pro
Page 23: ...www janitza com 23 UMG 512 PRO ...
Page 27: ...www janitza com 27 UMG 512 PRO ...
Page 47: ...www janitza com 47 UMG 512 PRO ...
Page 89: ...www janitza com 89 UMG 512 PRO ...
Page 119: ...www janitza com 119 UMG 512 PRO ...