UMG 511
5
General
Type
Size
Minimum Maximum
char
8
bit
0 255
byte
8
bit
-128
127
short
16
bit
-2
15
2
15
-1
int
32
bit
-2
31
2
31
-1
uint
32
bit
0 2
32
-1
long64
64 bit
-2
63
2
63
-1
float
32 bit
IEEE 754
IEEE 754
double
64 bit
IEEE 754
IEEE 754
Number formats
Transfer parameters
The UMG511 supports the following transfer parameters:
Baud rate
: 9.6kbps, 19.2kbps, 38.4kbps, 57.6kbps, 115.2 kbps and 921.6 kbps
Data bits
: 8
Parity
:
none
Stop bits (UMG511)
: 2
Stop bits external
: 1 or 2
Byte sequence
The data in the modbus address list can be called up in the
•
Big-Endian (high-Byte before low-Byte) and in the
•
Little-Endian (low-byte before high-byte)
format.
The addresses described in this address list supply the data in the „Big-Endian“ format.
If you require the data in the „Little-Endian“ format, you must add the value 32768 to the address.
Update rate
The modbus register addresses are updated every 200ms.
C
Energy values are processed in double format.
The energy values can be read about the Modbus addresses
in float format.
Symbols and definitions
N
Total number of sample points per period
(For example, in a period of 20 ms)
k
Sample value or number of samples per period
( 0 <= k < N)
p
Number or identification of the phase conductor
(p = 1, 2 oder 3)
i
pk
Sample value k of the current of the phase conductor p
u
pNk
Sample value k of the neutral voltage of the phase
conductor p
P
p
Real power of the phase conductor p
Summary of Contents for UMG 511
Page 21: ...Address Format Designation Unit Note UMG 511 21 Modbus address list...
Page 27: ...Address Format Designation Unit Note UMG 511 27 Modbus address list...
Page 31: ...Address Format Designation Unit Note UMG 511 31 Modbus address list...
Page 43: ...Address Format Designation Unit Note UMG 511 43 Modbus address list...
Page 55: ...Address Format Designation Unit Note UMG 511 55 Modbus address list...
Page 67: ...Address Format Designation Unit Note UMG 511 67 Modbus address list...