PROFIBUS DP (Option)
The UMG 503 corresponds to the field bus norm PROFI-
BUS DP, DIN E 19245 part 3 as a slave device. The
device is listed by the PROFIBUS user organisation e.V.
with the following entries:
Device description
: UMG 503
Ident-Number
: 044C HEX
GSD
: U503044C.GSD
For transmission of measured values with the PROFI-
BUS DP protocol integer formats are used by the UMG
503 such as char, int and word.
The UMG503 is suitable for the connection to controls
of the type DP-Master Class 1 (DP M1). The maximum
baud rate is
1500kbps
.
Configuration of UMG 503
The following requirements and settings are necessary
for the operation of UMG 503 at Profibus DP:
- A RS485 interface,
- A device address,
- Protocol "05" = PROFIBUS DP
The baud rate is determined automatically between the
master (SPS) and slave (UMG503). The setting of the
device address is described in chapter "device address".
In menu
CONF
scroll
to the indication of
RS485 interface
with
key
3
.
Manufacturer's set-
tings:
Baud rate
= 38,4kbps
Protocol
= 02
CONF
C o n f i r m i n g k e y 1
twice
,
the lower indica-
tion is flashing.
The text
EDIT
appears.
The protocol can now
be changed.
CONF
EDIT
CONF
EDIT
Using
key 3
you select
Protocol "05"
.
If protocol "05" is en-
tered, the baudrate is set
to "Auto" automatical-
ly and cannot be chan-
ged.
Pressing key 1 again,
the text
EDIT
disap-
pears
.
CONF
Protocol
Hints and examples for DP can be found on our
homepage.