- 10 -

11  DISCONNECTING TIME

[ 20 ... 1000]ms

This  refers  to  the  time  between  disconnecting  the  capacitors  to  reduce  the 

momentary network capacitance.. 

Default setting:  1000 ms

Selection is performed via the 

é

 /

ê

 keys. Continue with ENTER

12  DISCHARGE TIME

[ 20 ...1000]ms

This is the time for which an individual output is blocked between connecting and 

disconnecting. This blocking time has priority over connecting and disconnecting 

times. It depends on the capacitor discharge rating and thus is specified by the 

compensation network. 

 Default setting:   200 ms

Selection is performed via the 

é

 /

ê

 keys. Continue with ENTER

13  ALARM TEMP

[ 50...85]°C

The  alarm  temperature  programmed  here  is  the  temperature  at  which  the 

capacitor stages are disconnected in steps. The controller’s 

alarm relay

 responds 

after 60 seconds.   At the same time the display shows the cause of the alarm 

(over-temperature). If the temperature drops again, the required branches are 

automatically re-connected in steps. 

The selection is performed with the 

é

 /

ê

 keys. Save and continue with ENTER.

27  

Default: 20 sec. 

28  HARMONICS (harmonic limit)

[ 7 ]%

(0.5...25.5)%

A limit for THD-V (in%) can be entered here. When this threshold is exceeded, a 

message  is  given.  THD-V  is  the  ratio  of  the  geometric  sum  of  the  uneven 

harmonics to the fundamental.

DELAY-TIME OF ERROR-MESSAGES

[ 0... 255] sec.

The delay time for error-messages in the display can be changed here.

BASIC SETTING:

[ YES / NO ]

When the selection is made with YES and confirmed with ENTER, all parameters 

are reset to the basic setting made by the PFC-system  manufacturer. 

(Optimal network values when the controller was supplied with a complete PFC-

system). If the controller is supplied from the works, this point corresponds to the 

default setting. 

CAUTION: All user settings are lost!

Programming is now completed. The controller has returned to point 1 of the 

programming menu. 

5.2  Programming  lock

The 

Prophi-6T

  is  equipped  with  a  programming  lock  to  ensure  protection  from 

unauthorized or inadvertent changes to the system parameters. The lock can be activated 

in expert mode. If the lock is active, all parameters can be checked but not changed. 

Summary of Contents for Prophi 6T

Page 1: ...Support 49 6441 9642 22 E Mail info janitza com www janitza com www janitza com Power Factor Controller Prophi 6T Manual dynamic power factor controller Prophi 6T Manual Version 6 0 D 11 2019 1 2 3 4...

Page 2: ...n 5 Programming 5 1 Program menu 8 5 2 Programming lock 10 Section 6 Manual operation Programming of fixed stages 11 Section 7 Service menu 12 Section 8 Expert mode 12 8 1 Expert mode 1 8 2 Expert mod...

Page 3: ...ctor controller Prophi 6T represents the consequent development of the Prophi series with new innovative ideas and a multitude of functions It has been especially designed to control thyristor modules...

Page 4: ...converter is required for different operating voltages Caution Voltages which exceed the allowed voltage range can damage the device Fig 1 Front view 1 2 3 4 5 6 Power Factor Controller Blindleistungs...

Page 5: ...be short circuited Care should be taken to ensure that the measuring voltage and current are in the correct phase position The measuring current circuit must be wired with copper leads of 2 2 5mm The...

Page 6: ...rrent converter in the direction of current flow If the device is connected up via sum current converters the overall conversion ratio is entered k K k K l L l L Feed 1 Feed 2 K L K L Measurement via...

Page 7: ...dditionally several messages for different operation states are generated An individual adjustment resp suppression of particular messages is possible in expert mode 2 During suppression the indicatio...

Page 8: ...URE in C F ENTER 9 HARMONICS 3 19 V I ENTER 10 THD V THD I in ENTER Software version ENTER Return to 1 The power value specifies the total power 3 phase assuming symmetrical load If no key is pressed...

Page 9: ...By setting the end stopp the number of active capacitor branches is matched to the respective capacitor bank This is done via the keys The visible symbols of the capacitors correspond to the connected...

Page 10: ...crease the momentary network capacitance It should be noted that in practical operation the real connection time is affected by the discharge time locking time Default setting 1000 ms Selection is per...

Page 11: ...d in steps The selection is performed with the keys Save and continue with ENTER 27 Default 20 sec 28 HARMONICS harmonic limit 7 0 5 25 5 A limit for THD V in can be entered here When this threshold i...

Page 12: ...on continued switching via ENTER for the following statuses OFF The output is continuously disconnected e g for temporarily disconnecting a defective capacitor The capacitor symbol for this output is...

Page 13: ...ed As a protection against mal operation this level has an access code branching out in Expert mode 1 or 2 Password Expert mode 1 6343 Expert mode 2 2244 8 1 Expert mode 1 2 BASIC SETTING NEW NO NO YE...

Page 14: ...for operation warning and error which are displayed by the Prophi 6T Here they may be deactivated separately When deactivated the indication of the message in the display as well as possible activati...

Page 15: ...nk Disadvantage This mode can only be used in control series with groups of the same stage power and long settling time as every switching step corresponds to the value of the smallest stage 3 Intelli...

Page 16: ...r is then set to automatic operation with the operating mode key It is now ready for operation Section 11 Maintenance and warranty The controller should need no maintenance if the operating conditions...

Page 17: ...g voltage and current l and k Check phase position See above Current in measuring range Line interruption Wrong current converter factor Current transformer short circuited Check current converter rat...

Page 18: ...r 40mA for triggering TSM LC Programmable Illuminated graphic display 2 x 16 characters with convenient operating level 20 1 Sequential connection loop connection or self optimized switching response...

Page 19: ...ntrol series is not available for any reason The last control series Control Series E is selected by pressing the Programming key point 4 Control series and confirmed with ENTER This leads to the inse...

Page 20: ...rating lock Phase shift U I Power 1 stage Control Default setting ENGLISH 1000 A 5 A 6 1 INTELLIGENT 25 00 kvar 0 98 IND 230 V L N NO 1 sec 1 sec 0 2 sec 55 C 20 sec AUTO 6343 2244 66 4 x smallest sta...

Page 21: ...Prophi 6T 21...

Page 22: ...GE 230 V L N 9 V CONVERTER NO 10 SWITCH IN TIME 1000 ms 11 SWITCH OFF TIME 1000 ms 12 DISCHARGE TIME 200 ms 13 ALARM TEMP 55 C 8 TEMPERATURE 25 0 C 9 HARMONICS 3 V 0 5 I 0 5 10 THD V THD I V 1 6 I 0 9...

Page 23: ...ssages is possible with next steps YES NO MEAS VOLTAGE OVERVOLTAGE OVER COMPENSAT UNDERCOMPENSAT HARMONICS OVERTEMPERATURE OVERCURRENT UNDERVOLTAGE UNDERCURRENT C1 AUTO FIXED TEST OFF C2 AUTO FIXED TE...

Page 24: ...Janitza electronics GmbH Vor dem Polst ck 6 35633 Lahnau Germany Tel 49 6441 9642 0 E Mail info janitza com info janitza com www janitza com...

Reviews: