Page 8
3.2 Attach
Labels
3.2.1 Wiring Diagram Label
The Wiring Diagram label covers the existing
wiring diagram label on the inside of the power
center door. Attach the label by removing the
backing and placing it over the existing wiring
diagram.
NOTE Be careful to only cover the wiring diagram, not
the warning label or the installation instruction
portion of the label.
3.2.2 "What The Switches Do" Label
The "What The Switches Do" label covers the
existing printing on the dead panel. Attach the label
by removing the backing and placing it over the
existing "What The Buttons Do" printing.
NOTE For the Purelink 6614AP Power Center, align
the top portion of the label with the top printed
line of the text box and fold the bottom portion
under the edge.
3.3
High Voltage Wiring
3.3.1 System
Power
Section 3. Installation
3.1
Pool Link Control System Mounting
1.
The Pool Link and Power Center should be
located at or near the equipment pad. Locate
the Pool Link and Power Center at least five
(5) feet or more away from pool/spa and
five (5) feet off the ground. All na tion al,
state, and local codes are applicable.
NOTE
For Canadian installations, the Power Center
must be at least three (3) meters (9.8 feet)
away from the pool/spa and 1.5 meters (5 feet)
above the ground.
2.
Use the mounting brackets and instructions
provided with the Standard Power Center or
Sub-Panel Power Center.
3.
Sub-Panel Power Centers have special
code requirements. Be sure to follow all
applicable local and state codes to insure
safe installation.
NOTE
The Pool Link is not to be considered as
suitable for use as Service Equipment.
Therefore, it is required to have the appropriate
means of disconnection, circuit isolation, and/or
branch circuit protection installed
upstream
of
the Power Center.
Depending on which equipment is being controlled,
run ½" or ¾" conduit from the power supply panel
to the bottom of the Pool Link Control System.
If you are using the Sub-Panel Control System,
wire power to the appropriate breakers. Pull in
ap pro pri ate wire for equipment. Each piece of
equipment requires its own high voltage relay.
Connect 120 volts to the transformer and Pool
Link Timer Motor terminals. Connect equipment
ground(s). See Figures 1 and 2.
3.3.2 3HP (Standard) Relays
For each piece of
120 volt
equipment,
connect
power to a line terminal
and
connect equipment
to a load terminal
on the same relay. Refer to the
wiring diagram on the inside of the control center
door. For common Pool Link Control installations,
refer to Figures 3 and 4.
NOTE
The following are the contact ratings for 3HP
(Standard) Relay. DO NOT exceed any ratings.
3 HP @ 240 VAC; 1½ HP @ 120 VAC; 25
Amps; 1500 Watts.
3.3.3 Bonding the Pool Link
Install a bonding lug to the Pool Link enclosure.
Do not use sheet metal screws to attach the bonding
lug; use the appropriate hardware to securely
and positively install it. Connect the bond lug,
using a #8 solid copper core wire, to an approved
earth ground (an approved ground stake, grid, or
conducting metal water pipe buried to a sufficient
depth). See Figure 5.
WARNING
Potentially high voltages in the Pool Link Control
System can create dangerous electrical hazards,
possibly causing death, serious injury or property
damage. Turn off power at the main circuit of the
Pool Link Control System to disconnect the Pool
Link from the system. To properly and safely
wire the system, be sure to carefully follow the
applicable requirements of the National Electrical
Code (NEC), NFPA 70 or the Canadian Electrical
Code (CEC), CSA C22.1. All applicable local
installation codes must also be adhered to.