Jandy Laars LT250 Installation And Operation Manual Download Page 22

Page 20

Below the Backlight indicator is an RS service

indicator, which displays ‘RS Online’ when the heater is

connected to an RS unit.

Directly below the RS Service indicator on the

bottom right hand portion of the LCD screen is the

Fahrenheit/Celsius  temperature  unit  indicator.

The 

Model LT

 does not offer these features.

3B-2. Turning the Heater On or Off

When power is supplied to the 

Model LX

 heater, the

control goes into a diagnostic mode for approximately 15

seconds before the heater can be turned to the Pool or Spa

mode. During this time the display will show "RS Online".

If there is an RS control connected to the heater, it will

sense the RS unit and remain online. If the control is not

connected to an RS unit the "RS Online" indication on the

display will disappear after the initial 15 seconds. When

the display shows "RS ONLINE" all functionality of the

control at the heater is disabled. The heater functions can

be controlled only at the RS unit. However, sensor data is

displayed at both the heater and the RS unit.

To temporarily use the heater controls when online

with an RS control unit, use a thin object to depress the

button marked "RS SERVICE". The "RS ONLINE"

indicator will disappear from the heater display. All

functionality has now been returned to the control at the

heater. In this mode the RS unit has been disabled. To

return the functionality to the RS unit, push the button

again.

 When power is first supplied to the 

Model LT

heater it also runs through a circuit board diagnosis to

make sure that the control is working correctly. Indicator

lights will flash during the 10 second diagnostic sequence.

After the initial diagnostic sequence on the 

Model

LX

, the heater can be turned to Pool or Spa mode by

pressing and releasing the top (mode) button to the right of

the LCD screen so that the selector arrow is aligned with

either the Pool or Spa setting as seen on the LCD screen.

The 

Model LT

 heater does not offer the remote

control indicator function. To turn the heater on, press and

release the button located between the "POOL" and "SPA"

indicator lights. Repeat pressing the button to achieve the

desired mode of operation, shown by the indicator lights.

When neither light is on, the heater is "OFF"

 It is now necessary to set the thermostat to the

desired pool or spa setting.

3B-3. Setting Pool and Spa Temps,

Changing from Fahrenheit to

Celsius

The 

Model LX

 heater displays temperature in

Fahrenheit units when powered-up. To switch to Celsius,

press the ‘F°/C°’ button.  Once the desired temperature

units are selected, the thermostat can be set. The left-most

button below the LCD screen, labelled "Select", will select

either the Pool or the Spa thermostat when depressed.

Either "Pool" or "Spa" will be displayed in the bottom left

corner of the LCD screen. The ‘up’ and ‘down’ buttons

will increase or decrease the thermostat setting.

The 

Model LT

 heater control is less quantitative and

not automatic. The pool or spa water temperature will need

to be monitored manually as the control is adjusted.

Temperature adjustments are made by turning the knob

assosiated with the mode labeled below it. Turning the

knob clockwise will increase the temperature setting.

Turning it counterclockwise will decrease the setting.

Once the desired setting is acheived, set the temperature

lock by loosening the screw located at the bottom of the

knob and rotating the dial stop counterclockwise until it

contacts the knob. Tighten the screw to lock the stop in

place.

When the thermostat setting exceeds the temperature

of the pool or spa, the heater will fire. The heater will fire

continuously until the pool or spa water is heated to the

selected thermostat temperature. The control will not allow

the heater to fire again for five minutes even if there is a

call for heat, unless the thermostat setting is increased. In

this case, the heater will fire within two minutes. This is to

prevent short-cycling, and thereby increase the life of the

heater.

When the 

Model LX

 heater is firing, "Heating" will

be displayed underneath the LAARS LX logo. Note that in

both the "POOL" and "SPA" thermostat settings, the

temperature cannot be raised above 104°F (40°C).

Note that if power is momentarily lost, the

thermostat settings will remain the same.

Also note that the heater should not be used to

maintain water temperatures at or below 70°F (21°C). This

will damage the heater.

3B-4. Error Status

If the heater is powered, in either pool or spa mode,

and there is a call for heat (i.e. the thermostat setting is

higher than the water temperature) the heater will fire.

The blower will come on for approximately 30 seconds,

FIGURE 22. GAS VALVE

Summary of Contents for Laars LT250

Page 1: ...t causing property damage personal injury or death Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not...

Page 2: ...ef Valve 14 2I 5 Automatic Chlorinators Chemical Feeders 15 2J Start Up and Adjustment 15 2J 1 Normal Operation 15 2J 2 Start Up 15 2J 3 Gas Pressure 16 2J 4 Adjustment of Water Pressure Switch 16 2J...

Page 3: ...uded in a plastic bag inside the heater and on the back cover of this manual The home owner should fill out the warranty registration card included in the plastic bag and return it to Waterpik Technol...

Page 4: ...roper operation 2C Heater Location 2C 1 Installation Information The LX and LT can be installed outdoors or indoors as outlined in later sections In either case location must be selected with consider...

Page 5: ...so apply such as provision of ample uncontaminated air for combustion and ventilation 2F Indoor Installation 2F 1 Preparation of Heater for Indoor Installation If the LX or LT is to be installed indoo...

Page 6: ...Codes for Gas Appliances CAN 1 B149 1 2 Undersize pipe can result in inadequate venting and oversize pipe can result in vent condensation In either case the result can be release of combustion produc...

Page 7: ...be a Category I Fan Assisted appliance They are intended for standard vertical venting per tables provided in most local codes for Category I Fan Assisted appliances If the local code does not include...

Page 8: ...ximum 10 5 2 7 14 3 5 Figure 7 The Proper Design for a Sediment Trap Drip Leg Table 4 Natural Gas Pipe Size Requirements Distance from Gas Meter 0 50 feet 50 100 feet 100 200 feet Heater 0 15 m 15 30...

Page 9: ...MP SENSOR J4 1 J4 2 0 6 1 6 1 7 5 7 5 32 5 6285 5 5 3 5 5 3 5 5 5 3 5 5 3 5 5 5 5 5 5 5 5 5 5 2 8 1 6 5 5 2 8 1 6 5 1 6 5 9 1 1 7 9 3 6 3 6 9 1 7 9 1 7 3 6 3 6 0 9 0 9 0 9 0 9 7 5 3 5 6 6 8 5 6 7 0 7...

Page 10: ...connected to either tab on the terminal block the connections are not polarity sensitive Plug the fifteen pin connector into the receptacle The connector is keyed so it will fit in only one orientatio...

Page 11: ...it A number will appear on the display for approximately 5 seconds This first number can be ignored After the first number disappears a second number will appear in the display window It will consist...

Page 12: ...r is disabled The heater functions can be controlled only at the RS unit However sensor data is displayed at both the heater and the RS unit To temporarily use the heater controls use a thin object to...

Page 13: ...ntrol panel There are quick disconnects at the end of the wires 15 Remove the inlet outlet header side cover plate located under the inlet outlet header There are four philips head screws one in each...

Page 14: ...one in each corner 26 Route the wires that attach to the temperature sensor along the copper siphon loop back to the right side of the heater Reconnect the wires to the tabs on the back of the control...

Page 15: ...e top of the heater Be careful not to pinch any wires Replace the two screws on the bottom flange to hold the cover in place 47 Replace the front panel door 2I 2 Pool Spa Piping Systems Figure 15 illu...

Page 16: ...Technologies PRV kit into the blind threaded hole on the top of the inlet outlet header 2 Using the countersink in the center of the blind hole as a guide drill a 1 4 inch hole through the plastic 3 O...

Page 17: ...ton until the indicator on the LCD screen aligns with OFF Now press and release the button again until the indicator on the LCD screen aligns with the desired setting either POOL or SPA To reset the m...

Page 18: ...f Setting the switch to close at too low of a flow can damage the appliance Do not operate this heater outdoors at temperatures below 20 degrees Fahrenheit F 7 degrees Celsius C 2J 2 Start up Confirm...

Page 19: ...ow even though flow through the filter system will vary depending on how dirty the filter is For most installations an external bypass valve is not needed in the heater water piping This is due to the...

Page 20: ...from this reading This difference is the temperature rise Refer to Table 8 If your measured temperature rise is within the range designated for your heater skip steps 6 through 8 6 Locate the bypass a...

Page 21: ...n there is water flowing through the heater the filter pump is on the water temperature is displayed in the right most of two bar graphs in the center of the screen This bar graph is labeled as Water...

Page 22: ...he heater is OFF It is now necessary to set the thermostat to the desired pool or spa setting 3B 3 Setting Pool and Spa Temps Changing from Fahrenheit to Celsius The Model LX heater displays temperatu...

Page 23: ...switch 1 Broken split pinched or disconnected fan switch tubing 1 Check tubing and replace if necessary 2 Fan not operating 2 Correct fault or replace fan Refer to qualified service personnel 3 Fan ru...

Page 24: ...lve control knob counterclockwise to ON see Figure 22 5 Replace the heater door 6 Turn on electrical power to the heater 7 Turn on the filter pump 8 Set the heater controls to the SPA position mode If...

Page 25: ...to next step 8 Turn gas control knob counterclockwise to ON A This appliance does not have a pilot light It is equipped with an ignition device which automatically lights the heater Do NOT try to lig...

Page 26: ...e week It should be reset to the 78 F 26 C level before expected usage keeping in mind to allow enough lead time for the water to reach the desired temperature 3D 2a Spa Water Chemistry Maintaining sa...

Page 27: ...ater is not going to be used for a long period of time shut it down completely following the instructions in Section 3C 2 Shutdown or the lighting and shutdown instructions posted inside the heater 3G...

Page 28: ...erature control g Control circuit fuse 6 Perform a temperature rise test in accordance with Section 2J 5 7 If the heater is equipped with a pressure relief valve clean any accumulated corrosion and ma...

Page 29: ...0444900 33 RetainerBracket Temp Sensor All 10447300 34 Screw RetainerBracket All F0009100 35 IgnitionControl All R0328800 36 Pressure Switch Assy All R0334500 37 Pressure Switch 2 psi All R0013200 38...

Page 30: ...EE NEXT PAGE FOR DETAIL 20 21 22 23 25 SEE NEXT PAGE FOR DETAIL 44 54 55 57 SEE NEXT PAGE FOR DETAIL 58 59 60 60 61 63 64 65 66 67 68 69 70 71 72 73 10 9 SEE NEXT PAGE FOR DETAIL 45 24 62 74 56 36 38...

Page 31: ...LX and LT Pool Heaters Page 29 2 3 4 5 7 8 11 11 12 16 17 15 18 19 14 35 27 29 37 42 40 41 52 53 51 32 31 30 34 33 43 43 6 5C 2 Detail View 77...

Page 32: ...orized parts or accessories in conjunction with the product s 8 Chemical contamination of combustion air or improper use of sanitizing chemicals such as introducing sanitizing chemicals upstream of th...

Reviews: