Issue: 01.05.2017
Page 5
Specifications
Unit Data
Unit Dimensions
W
D
H
W
D
JEHSD-0600-M-3
1347
561
884
946
500
Model
Overall Dimensions (mm)
Mounting Dimensions (mm)
Performance Data:
The performance data shown on pages 6 & 7 have the following criteria:
•
TE: Evaporating Temperature
•
TA: Ambient Temperature
•
HP: Approximate Compressor Horsepower
•
CC: Cooling Capacity (Watts)
•
PC: Power Consumed (Watts)
•
COP: Coefficient of Performance
•
Rating Condition: Suction Gas Superheat 10K, Sub-cooling 0K
•
Data presented in accordance with BS EN13215:2016
Swept
Volume
Oil
Charge
NC
a
MCC
b
LRC
c
FLC
Liquid Suction
(m³/h) (Litres) (Litres)
(A)
(A)
(A)
(A)
(Litres)
(Litres)
(m³/h)
(inch)
(inch)
(kgs)
dB(A)
JEHSD-0600-M-3 ZBD45KQE-TFD
17.1
1.89
0.6
A
9.3
13.5
74.0
1
0.9
7.6
7.6
4150
1/2
7/8
139
41
Unit Model
Unit
Dry
Weight
SPL @
10m
d
Compressor
Airflow
Connections
Electrical Data
Fan Motors
Type
No.
Coil
Volume
Liquid
Receiver
Compressor
Oil
Sep.
Charge
Oil
Type
Oil Type
A
= Polyolester Oil - (Copeland Ultra 22 CC, Copeland Ultra 32 CC, Copeland Ultra 32-3MAF, Mobil EAL Arctic 222CC, Uniquema Emkarate RL32CF
a
NC
= Nominal Current @ condition -10
°
C Te / +32°C Ta MT w ith R404A refrigerant
b
MCC = Maximum Continuous Current
c
LRC = Locked Rotor Current
d
Sound Pressure Level @ 10m free field at (-10/+32°C) MT conditions. Alternative conditions may produce different results
Summary of Contents for JEHSD-0600-M-3
Page 27: ...Issue 01 05 2017 Page 27 Drawings Dimensional drawing JEHSD 0600 M 3 ...
Page 28: ...Issue 01 05 2017 Page 28 Drawings Electrical Wiring Diagram JEHSD 0600 M 3 ...
Page 34: ...Issue 01 05 2017 Page 34 Technical Information Medium Version Controller ...
Page 36: ...Issue 01 05 2017 Page 36 Certification ...
Page 37: ...Issue 01 05 2017 Page 37 Certification ...
Page 38: ...Issue 01 05 2017 Page 38 Certification ...
Page 39: ...Issue 01 05 2017 Page 39 THIS PAGE IS LEFT BLANK INTENTIONALLY ...