background image

 

Section A  

…… 

cont 

 

 

 ii. 

IMPORTANT NOTES;-

 

   

a.  Do not use metal ties or straps as they can damage the    

          Detecting cable. 
   

b.  Do not over tighten the cable ties. 

   

c.  Detecting cable should never be installed between pipe-   

   

work and its insulation. It must be installed on the outside  

 

  of any insulation finish.

 

   

d.  ‘aqualarm’ WARNING LABELS (WL-1) should be fitted at    

   

5m intervals along the entire length of all cables installed.  

 

  Where cables go through walls etc. the WL-1 should be 
   

 

fitted either side of the wall.

 

 

Section B  

 1. Testing 

Installed 

Cables

 

 
  i. 

 

When all your  Leader / Detecting / Jumper cables have been 

   

installed, the total length should be Tested as follows :- 

  ii 

 

Ensure that all the cables are connected together BUT DO NOT  

  CONNECT the Leader cable to the Control Panel AT THIS STAGE. 

  iii.   

Connect the End of line resistive plug (EOL-2) to the end of the  

  last length of cable installed. 
  iv.   

Carry out the following ‘TEST’ using a Multimeter to ensure the 

   

integrity of the installed cables. 

  v.   

Set Multimeter to read a resistance above 100 ohms. Connect  

   

the Multimeter leads to the bare cores of the Leader Cable. The  

   

following should be noted:- 

 

 

 

   

CONDITION                                POSSIBLE FAULT 

   No 

resistance

  

 

 

a.     EOL-2 not fitted at end (Open 

Circuit)               
   

 

   

 

 

b.     Cable disconnected along the 

   

 

   

 

 

        installed length. 

   

Resistance reading  

 

   

below 45 ohms 

 

 

a.     Cable is damaged (Short Circuit) 

   

 

   

 

 

b.     Cable is wet (Rectify) 

 

   Resistance 

reading 

   

above 50 ohms.   

 

a.      All cables are correct. System is 

   

 

   

 

 

         ready to connect to Control Panel. 

 

 

 

 

 

   

 

   

 

 

- 4 -

 

Summary of Contents for Aqualarm LeakSense 2

Page 1: ...Tel 44 0 191 490 1547 Fax 44 0 191 477 5371 Email northernsales thorneandderrick co uk Website www heattracing co uk www thorneanderrick co uk...

Page 2: ...OL PANEL OUTPUTS 1 Relay Outputs 7 2 RS 232 8 3 RS 485 8 E CONTROL PANEL FUNCTIONS 1 Test Mute Reset Keys 9 2 View 100 Event Record Log 10 3 What to do if an Alarm Sounds 10 F MAINTENANCE CABLE CARE 1...

Page 3: ...provided and with a suitable cable gland to the terminals marked CD X ii The cores can be connected to either terminal as there is no polarity DO NOT CONNECT TO THE CONTROL PANEL YET iii The connector...

Page 4: ...be Tested as follows ii Ensure that all the cables are connected together BUT DO NOT CONNECT the Leader cable to the Control Panel AT THIS STAGE iii Connect the End of line resistive plug EOL 2 to the...

Page 5: ...itable cable entry gland iv Cause a competent qualified person to connect the Battery Back Up leads to the correct terminals of the sealed Lead Acid Batteries and the Control Panel to the Mains Power...

Page 6: ...e LCD screen will DISPLAY the following iii The Hours will be highlighted Using the buttons corresponding to the keys set the hours iv Continue using the buttons corresponding to the ARROW keys to hig...

Page 7: ...the Detecting cable into the other end of the Mapping Tool Press the button corresponding to the Reset key the LCD screen will now revert to Screen A iv Press hold down the Button on the top of the M...

Page 8: ...MARKED Water Detected Alarm Alarm N C C N O Open Circuit Alarm Network Fail N C C N O Mains Failure Alarm Mains Fail N C C N O Battery Failure Alarm Batt Fail N C C N O Service Alarm Service N C C N...

Page 9: ...e button corresponding to the RESET key This should always be used to RESET the System following the clearance of an alarm condition or Panel TEST The LCD screen will now revert to Screen A iv In TEST...

Page 10: ...to Screen A iv To remove all LOGS Press the button corresponding to the CLEAR LOGS key Then Press the button corresponding to the EXIT Sign to return to Screen A 3 What to do if an Alarm sounds a Wat...

Page 11: ...seconds display the same or similar Location Reading this will indicate that the Detecting cable has not dried or that the water is still present ix If a vastly different Location Reading is displayed...

Page 12: ...change to the following iii The Alarm Horn will sound iv Press the button corresponding to the MUTE key take NOTE of the LOCATION READING displayed check this against the System Map to locate the Ope...

Page 13: ...are working in the area of the alarm They may have caused damage to the detecting cable or opened a joint whilst carrying out other duties or works Always be aware of any works being carried out in t...

Page 14: ...intenance i Although the system is relatively maintenance free it is recommended that it should be checked fully at least ONCE each year Should an alarm occur which you cannot clear by the method desc...

Page 15: ...ders Rubble Dust All the above substances will cause an Alarm state If allowed to dry without attendance a Trace Path contamination may occur the Alarm state will not be able to be cleared or the syst...

Page 16: ...wing aqualarm equipment is available to be connected directly to the LeakSense 2i system Repeater Panel RP 1 Beacon Sounder B S 1 Touch Screen system aqualarm One Touch Auto dialler SD 1 Automatic Voi...

Page 17: ...r Cable Can be cut to Length CD x Detecting Cable 1m 2m 5m 10m WARNING WATER LEAK DETECTION CABLE WL 1 10 Pack of 10 WL 1 100 Pack of 100 Warning Labels LS MBi Mapping Box LS JC Jumper Cable Please Sp...

Page 18: ...ate When all Readings have been recorded the information should be used to prepare a System Map 18 Position Log No Cable Length Type Alarm Reading Open Circuit Reading Position Log No Cable Length Typ...

Page 19: ...HEET Project Name Date You should also photcopy pages 18 19 for your records 19 Position Log No Cable Length Type Alarm Reading Open Circuit Reading Position Log No Cable Length Type Alarm Reading Ope...

Page 20: ...20...

Page 21: ...21...

Page 22: ...22...

Page 23: ...drill bits do not penetrate far enough to touch the Printed Circuit Boards or any component You must ensure that any swarf from the drilling is completely removed from the Control Panel FAILURE to ad...

Reviews: