JSI10KTL-12KTL-15KTL User Manual
4.6
Connecting Inverter to AC Grid
Only after receiving prior approval from the utility company you can connect
the inverter to local utility grid.
The grid should meet these following requirements. Otherwise the inverter will
not work.
Grid Voltage
Grid Frequency
3*310V~3*450V
47~51.5Hz/57~61.5Hz
AC Wiring Procedure:
Step 1:
Make sure that the AC circuit breaker is switched off.
Step 2:
Dismantle the board with screwdriver.
Step 3:
Unscrew the waterproof terminal in the direction shown in the following
picture.
Step 2
Step 3
Step 4:
Insert the cables via the holes of the AC terminals.
Step 5:
Pull the cable from the other side.
Step 6:
Strip off insulation layer of all AC cables. The length of strip insulation is
approximate 10mm.