OPERATION AND MAINTENANCE MANUAL 

01-2016 

 

15

PN-EN ISO 12944-5: 2009 

Paints and varnishes. Anti-corrosion protection of steel structures by means of 
protective painting systems. Protective paint systems. 

 
 

2.7 ORDERING REGULATIONS 

 
 

Underground fire hydrants are specific purpose industrial valves, therefore orders must include:    

 

- product's catalogue number, 

 

- intended use, e.g. for fire water supply systems; 

 

  furthermore: 

 

- nominal diameter — acc. to PN-EN ISO 6708: 1998 

 

- nominal pressure, acc. to PN-89/H-02650; 

 

- type of body material — acc. to PN-EN 1563: 2012 

 

- max. operating temperature — acc. to PN-89/H — 02650. 

 
 

2.8 MANUFACTURE AND ACCEPTANCE 

 

The underground hydrants are accepted and produced in accordance with: PN-EN 1074-6:2005 (Valves for 

water  supply.  Fitness  for  purpose  requirements  and  appropriate  verification  tests.  Hydrants.)  and  PN-EN 
14339:2005 
(Underground  hydrants).  All  hydrants  (100%)  are  subject  to  tightness  testing.  The  tests  include  external  body 
tightness and closing tightness. 
 

2.9 MARKINGS 

 

The underground hydrants are marked in accordance with:  

PN-EN-19: 2005, PN-EN-1074-6: 2009 

markings on the front and back walls of the body chamber. The marking contains the following data: 

- nominal diameter  

 

 

 

 

 

 

 

 

- nominal pressure  

 

 

 

 

 

 

 

 

- type of body material 
- manufacturer trade mark  
- direction of medium flow. 

The location on the valve specified in the documentation features the nameplate which contains the 

following data:   

 - manufacturer's company name and logo 

 

 

 

- product serial number 
- sealing temperature grade 
- the Polish Building Mark "B" and/or the CE mark (as applicable) 
- product type 

 

 

3 PROTECTION, STORAGE & TRANSPORT 

 

3.1 PROTECTIVE COATINGS 

 

All inner and outer cast-iron surfaces and column pipes are protected with electro-deposited epoxy coat. The 

coat has been approved for contact with foodstuffs. 
The anti-corrosion coating layer minimum thickness is 250

µ

m. 

The casting surface is pre-treated for epoxy coating in accordance with the relevant technical documentation and 
standard PN-EN ISO 12944-5: 2009. 
The fastening bolts for external hydrant's part, if other than stainless steel grade 1.4301, should 
have corrosion protection in the form of coat, e.g. Fe/Zn5. 
 
 

3.2 PACKAGING 

 

The hydrants are placed in plastic film sleeves and additionally wrapped with stretch wrap when placed on 

pallets. 
 

Summary of Contents for 8851

Page 1: ...by President of Factory JAFAR S A Failure to comply with the guidelines and instructions in this Operation and Maintenance Manual releases the manufacturer from all obligations liability and guarantee...

Page 2: ...MENSIONS TYPE 8851 11 2 4 MATERIALS TYPE 8852 12 2 5 DIMENSIONS TYPE 8852 13 2 6 STANDARDS 14 2 7 ORDERING REGULATIONS 15 2 8 MANUFACTURE AND ACCEPTANCE 15 2 9 MARKINGS 15 3 PROTECTION STORAGE TRANSPO...

Page 3: ...ydrant clockwise closing sense of rotation The closing sense of rotation can be opposite on special order connection flanges are manufactured in accordance with PN EN 1092 2 1999 with the dimensions a...

Page 4: ...sing a hydrant the poppet lands in the seat and the water remaining in the hydrant s column is drained using the draining hole With hydrant TYPE 8852 it is possible to replace the complete internal eq...

Page 5: ...OPERATION AND MAINTENANCE MANUAL 01 2016 5 Operation diagram for hydrant TYPE 8851 DN80 8851 1 CLOSE OPEN...

Page 6: ...OPERATION AND MAINTENANCE MANUAL 01 2016 6 Operation diagram for hydrant TYPE 8851 DN80 8851 2 CLOSE OPEN...

Page 7: ...OPERATION AND MAINTENANCE MANUAL 01 2016 7 Operation diagram for hydrant TYPE 8851 DN80 8851 3 CLOSE OPEN...

Page 8: ...OPERATION AND MAINTENANCE MANUAL 01 2016 8 Operation diagram for hydrant TYPE 8852 DN80 8852 1 CLOSE OPEN...

Page 9: ...diagram for hydrant TYPE 8852 DN80 8852 2 CLOSE OPEN The order of operations during opening and closing of a hydrant type 8852 configured with a shutoff gate valve Starting 1 Open the shutoff gate va...

Page 10: ...1 4301 PN EN1563 2012 PN EN 1 503 3 2003 PN EN 10088 1 2014 4 Cover Cast iron EN GJS 400 15 EN GJS500 7 PN EN1563 2012 5 Poppet Cast iron EN GJS 400 15 EN GJS500 7 EPDM PN EN1563 2012 PN ISO1629 2005...

Page 11: ...OPERATION AND MAINTENANCE MANUAL 01 2016 11 2 3 DIMENSIONS TYPE 8851...

Page 12: ...12 4 Cover Cast iron EN GJS 400 15 EN GJS500 7 PN EN1563 2012 5 Poppet Cast iron EN GJS 400 15 EN GJS500 7 EPDM PN EN1563 2012 PN ISO1629 2005 6 Cap Cast iron EN GJS 400 15 EN GJS500 7 PN EN1563 2012...

Page 13: ...OPERATION AND MAINTENANCE MANUAL 01 2016 13 19 Seat Brass PN EN 1982 2010 20 Drainage Polypropylene PP PN EN ISO 1873 1 2000 2 5 DIMENSIONS TYPE 8852...

Page 14: ...drants PN EN 10088 1 2014 Stainless steels List of stainless steels PN 89 H 84023 07 Specific application steel Pipe steel Grades PN EN 1706 2011 Aluminium and aluminium alloys Foundings Chemical comp...

Page 15: ...ce with PN EN 19 2005 PN EN 1074 6 2009 markings on the front and back walls of the body chamber The marking contains the following data nominal diameter nominal pressure type of body material manufac...

Page 16: ...ground pipelines on horizontal systems The products described herein are designed for installation using flange on the pipeline acting as medium water supply Note that the system must not expose the h...

Page 17: ...cial documentation i e application for media and operation parameters of the pipeline in which they are to be installed Note If the product is damaged mechanically do not install it in the pipeline An...

Page 18: ...OPERATION AND MAINTENANCE MANUAL 01 2016 18 1 Hydrant 2 Pipeline connection flange 3 Gasket 4 Nut 5 Fastening bolt...

Page 19: ...iled requirements are given in applicable regulations defining the need for fire fighting water The diagram above shows an example installation method for an underground hydrant the installation metho...

Page 20: ...ecommendations for installation of water systems and devices installed in water supply stations and other facilities apply Misuse of this product is prohibited 5 GUARANTEE CONDITIONS The manufacturer...

Reviews: