2.6 MANUFACTURE AND ACCEPTANCE 

 

       Cast iron flange valves Type 7110, typ 7050 and threded Typ 7040

 are manufactured and  

commissioned according to: PN-EN 1074-4: 2002  (Valves for water supply. Fitness for purpose  
requirements and appropriate verification tests. Part 4 Air valves) and PN-EN 12266-1: 2003  
(Industrial valves. Testing of valves). All valves (100%) are tested for sealability. Outer body  
sealability is tested and closed sealability in low and high pressure.

 

 

2.7 MARKING 

 

  Valve marking is governed by standards: PN-EN-19: 2005, PN-EN-1074-1: 2002. 

 

Valve bodies have markings placed on the front and back wall of the chamber body, which  

       include the following data: 
 

 

 

- nominal diameter 

 

 

 

- nominal pressure  

 

 

 

 

 

 

 

 

 

- type of body material   
- producer trade mark   

       and a ledge to include an identification mark (e.g. series no.) 

 

3 PROTECTION — STORAGE — TRANSPORTATION 

 

3.1 PROTECTIVE COATINGS 

 

        All internal and external cast iron surfaces are protected with epoxy paint, applied electrostatically. The   
 paint is approved for contact with food products. 

               The thickness of the anti-corrosion coating layer is min. 250 

µ

m. 

         Mould surface is prepared for the application of the epoxy coating in accordance with the technical     
        documentation and PN-EN ISO 12944-5: 2009. 
                The screws connecting the body and the cover are manufactured as stainless, grade OH18N9 or Fe/Zn5      
        (galvanised steel). 
 
 

3.2 PACKAGING 

 

Cast iron flange valves TYPE 7010, TYPE 7050 and threaded TYPE 7040 are packaged on         

       EURO pallets (1200x800) and secured with a heat shrinked hood. 

 

3.3 STORAGE 

 

 

Cast iron flange valves TYPE 7010, TYPE 7050 and threaded TYPE 7040 should be stored  

       indoors. 

  

Summary of Contents for 7010

Page 1: ...proved for use by President of Factory JAFAR S A User s failure to follow the instructions and guidelines included in this operation and maintenance manual exempts the manufacturer of all obligations...

Page 2: ...N 4 2 2 MATERIALS 5 2 3 DIMENSIONS 7 2 4 STANDARDS 10 2 5 ORDERING PRINCIPLES 10 2 6 MANUFACTURE AND ACCEPTANCE 11 2 7 MARKING 11 3 PROTECTION STORAGE TRANSPORTATION 11 3 1 PROTECTIVE COATINGS 11 3 2...

Page 3: ...ally placed piping 1 3 TECHNICAL SPECIFICATION Cast iron air valves TYPE 7010 are intended for purposes of aerating and deaerating systems for potable water and other liquids obtain agreement from the...

Page 4: ...use it has lower density than water Ball density is chosen so that during air release via the valve the ball is positioned in the lower part of the body and during water filling raised together with t...

Page 5: ...aerating the ball as the water level in the valve chamber decreases the nozzle output hole opens and assumes the lower position in the position of descended lever During work with a TYPE 7010 valve t...

Page 6: ...005 5 Nozzle Stainless steel 1 4301 PN EN 10088 1 2014 6 Lower lever Stainless steel 1 4021 PN EN 10088 1 2014 7 Top Lever Stainless steel 1 4021 PN EN 10088 1 2014 8 Bolt Stainless steel 1 4301 PN EN...

Page 7: ...2 2015 7 2 3 DIMENSIONS TYPE 7010 DN H L D K l x n G G1 Masa kg 50 GW 2 187 156 165 125 19x4 5 4 7 80 242 195 200 160 19x8 4 2 14 100 319 195 220 180 19x8 2 18 150 350 265 285 240 23x8 3 33 200 350 27...

Page 8: ...OPERATION AND MAINTENANCE MANUAL 12 2015 8 TYPE 7040 G H L Masa cal kg 3 4 1 6 1 1 7 5 4 1 7 6 4 1 8 mm 135 85...

Page 9: ...L 12 2015 9 TYPE 7050 DN H L D K l x n G G1 Masa kg 50 GW 2 250 108 165 125 19x4 5 4 8 5 80 280 128 200 160 19x8 4 2 15 5 100 316 141 220 180 19x8 2 19 5 150 355 173 285 240 23x8 2 34 5 200 355 173 34...

Page 10: ...ves for water supply Fitness for purpose requirements and appropriate verification tests Part 4 Air valves PN EN 1706 2001 Aluminium and aluminium alloys Castings Chemical composition and mechanical p...

Page 11: ...minal pressure type of body material producer trade mark and a ledge to include an identification mark e g series no 3 PROTECTION STORAGE TRANSPORTATION 3 1 PROTECTIVE COATINGS All internal and extern...

Page 12: ...es should be installed in easily accessible places which enable regular controls with scheduled frequency Correctly sized holes should be provided in the installation design to ensure uninterrupted ai...

Page 13: ...unnel state of external surfaces should be checked and if necessary rinse them thoroughly with water Attention In case of mechanical damage the device should not be installed on the pipeline The pictu...

Page 14: ...regarding the air fittings i e oriented as shown in the diagram of possible orientations In order to provide full operational efficiency rinsing valves with clean water is recommended once a year In o...

Page 15: ...ANCE MANUAL 12 2015 15 5 WARRANTY CONDITIONS The manufacturer grants warranty for the product being installed and operated according to this OMM The conditions and period of the warranty is specified...

Reviews: