Jafar 4495 Operating Manual Download Page 4

 

 

 

 
 

OPERATING MANUAL 

07-2021 

4/11 

 
 

 

DN 

[mm] 

ISO 

5211 

Closing/opening torque value on valve shaft required 

for (Nm), 

gas media* 

P/N 

4497 

Δ

1.0 [MPa] 

1.6 [MPa] 

40 

F05 

16 

24 

50 

F05 

24 

35 

65 

F05 

31 

43 

80 

F05 

43 

70 

100 

F07 

66 

94 

125 

F07 

110 

156 

150 

F07 

156 

219 

200 

F10 

329 

368 

250 

F10 

438 

506 

300 

F10 

625 

781 

350 

F10 

1,313 

1,594 

400 

F14 

1,719 

2,344 

500 

F14 

3,469 

4,000 

600 

F16 

5,000 

5,781 

700 

F25 

9,219 

11,719 

800 

F25 

11,719 

14,063 

900 

F25 

13,281 

17,188 

1000 

F25 

15,625 

19,531 

1200 

F30 

17,188 

22,031 

Table 2. Operating torque values for gas media

 

* Applicable to networks which conduct chemically inert gases (e.g. air without oil). For the remaining gas group, 
a separate document is available: “

P/N 4497 Operating Manual for Gas Applications

”. 

 

 

The minimum valve switchover time (to close or open) dependent on the DN size (nominal diameter) is listed 
in Table 2: 

DN (mm) 

Switchover time (s) 

40-350 

10 

400-600 

16 

700-800 

40 

900-1200 

50 

Table 3. Minimum valve switchover time

The valve switchover time is the minimum time to close or open the valve connected to a pump which delivers a 
medium. The time values listed in Table 2 are calculated with the following formula: 

=

∙ ℎ ∙ ( − 1)

 ∙ √

 

 

T –>  switchover time (s) 
L –>   piping length (m) 
g –>  9.81(m/s

2

h –>  nominal pressure in metres of sweet water 
column 

V –>  flow rate (m/s) 

k –> shockwave pressure rise factor, calculated in 

relation to the nominal pressure (1-1.25) 

 
The  listed  time  values  are  calculated  for:  L=500(m),  V=  4(m/s),  k=  1.25.  If  the  closing  time  is  shorter,  it  is 
mandatory to install water hammer dampers (and standard safety valves are unfit for this application). 

Summary of Contents for 4495

Page 1: ...OPERATING MANUAL 07 2021 1 11 OPERATING MANUAL Concentric butterfly valves P N 4495 4496 4497...

Page 2: ...OPERATING MANUAL 07 2021 2 11 CONTENTS 1 INTENDED USE 3 2 TECHNICAL DESCRIPTION 3 3 PRODUCT IDENTIFICATION MARKING 6 4 STORAGE TRANSPORT 7 5 INSTALLATION 7 6 OPERATION 10 7 SAFETY 10 8 WARRANTY 11...

Page 3: ...4497 are sealed in both directions of flow Application temperature range 0 C to 70 C Nominal pressure ratings 1 0 MPa 1 6 MPa Nominal diameter range P N 4495 lug valve DN40 DN600 mm P N 4496 flanged v...

Page 4: ...N 4497 Operating Manual for Gas Applications The minimum valve switchover time to close or open dependent on the DN size nominal diameter is listed in Table 2 DN mm Switchover time s 40 350 10 400 60...

Page 5: ...ium ring on which a rubber sealing ring is mounted The lug valves P N 4495 and the wafer valves 4497 feature either of the two end seal version A replaceable insert dovetail style in the size range of...

Page 6: ...location on the valve specified in the documentation features the nameplate which contains the following data Fig 1 Valve nameplate sticker 1 Manufacturer s company and country of origin 2 Manufactur...

Page 7: ...installation process do not leave any installation tools bolts nuts or welding wire inside of the piping or they can stop at the end seal the rubber insert or within the closure panel of the valve Th...

Page 8: ...s is that the deposits can be entrained from the upstream of the valve by the maximum possible flow passing the bottom part of the valve closure during the opening operation Fig 4 Fig 4 A Incorrect va...

Page 9: ...piping bend or tee Fig 5 Recommended distances from the piping bends For the valves in the size range of DN200 to DN2000 the axis of the closure drive shaft must be perpendicular to the centreline of...

Page 10: ...warranty granted by the manufacturer 7 SAFETY All installation and operation tasks related to the product shall be only be done by qualified professionals with sufficient training and experience to as...

Page 11: ...odifications on order The final selection of the product which meets the optimum criteria for the installation project in question is made by the installation designer who should consider this Operati...

Reviews: