JBE-P2L1 Panel Manual V1.2 EN
Page 21
Release Date: January 5, 2021
Rev 01
5.3
Description of user access levels and default login passwords.
The access to certain panel functions is restricted to different user levels to avoid unauthorized operations.
The main screen will request a password when the user tries to execute a function that requires an access
level higher than the level of access currently granted.
The fire panel will automatically return to User Access Level 1 after 30 seconds of inactivity. This timeout
period can be temporarily extended by activating " commissioning mode " with level 3 user access.
Table 10: Access Levels and Passwords.
5.4
Operations available to all users (access level 1 and above)
This chapter
describes the functionality accessible to the building’s first responders, who are considered a
general public user with training and responsibility for initial investigation of incidents related with the fire
system. These functions can be exercised without a password.
5.4.1 Silencing the buzzer
To silence/re-activate the buzzer from the panel in situations as alarm, fault or test, the user can press the
buzzer silence/acknowledge key to silence the buzzer. To re-activate the buzzer, press the same key
again to re-activate the buzzer.
Users can review all previous and ongoing event information from the View menu by pressing either
control keys (refer to Figure 12) or function keys (refer to Figure 13).
Nivel de
acceso
Personal/
usuarios designados
Contraseña
requerida
Función
1
User access level 1
-
First responders
No password
needed
This level allows public users to view
ongoing events in the panel and
perform basic operational tasks.
2
User access level 2
-
Trained operator
YES
Default:
111
This
level
allows
authorized
operators who have been trained to
carry out designated operations on
the control panel.
3
User access level 3
-
Installer Maintenance
/commissioning
personnel
YES
Default:
1111111111
This level allows designated users to
either run full system configuration or
regular maintenance tasks.
3.1
The
panel’s
physical key
Installation and maintenance