Overview 

 

JBE-2101  is a conventional  manual call point (MCP)  designed to  be 

compatible with a wide range of conventional fire panels and input 

modules. This MCP sets an installer-selectable resistive load to the fire loop 

when its resettable element is pressed. 

After activation, the MCP will remain in alarm until it is reset with the 

supplied  reset key. There is no  glass break element  in this device, so the 

reset operation is conveniently done without the need to replace  any 

element.   

The JBE-2101 also features a pair of normally open clean (voltage-free) 

contacts, which close at activation. These can be optionally used for a local 

action or to provide an activation signal to third party systems. 

Technical data 

Category 

EN 54-11 type A indoor MCP 

Working voltage

 

6-30 V DC 

Connection 

2-wire conventional zone 

Wire size 

0.5 – 2.5 mm

Quiescent current

 

0 mA

 

Alarm load

 

Built-in 680 Ω and 470 Ω + option for external R. 

Clean contact rating 

0.1 A / 30 V DC 

Working temp. 

-10

 ~ 55

 

Storage temp. 

-30

 ~ 75

 

Environment Humidity 

≤ 95% RH (no condensation nor icing) 

Red LED Indication

 

Steady on when in alarm. 

Dimensions (LxWxH)

 

90×90×52 mm

 

IP rating 

IP40 

Weight 

160 g 

 