M-2101-1: JBE-2101 Manual Call Point data sheet V1.0
Jade Bird Fire Alarm Systems – JadeBird.eu.com 1
/
4
Overview
JBE-2101 is a conventional manual call point (MCP) designed to be
compatible with a wide range of conventional fire panels and input
modules. This MCP sets an installer-selectable resistive load to the fire loop
when its resettable element is pressed.
After activation, the MCP will remain in alarm until it is reset with the
supplied reset key. There is no glass break element in this device, so the
reset operation is conveniently done without the need to replace any
element.
The JBE-2101 also features a pair of normally open clean (voltage-free)
contacts, which close at activation. These can be optionally used for a local
action or to provide an activation signal to third party systems.
Technical data
Category
EN 54-11 type A indoor MCP
Working voltage
6-30 V DC
Connection
2-wire conventional zone
Wire size
0.5 – 2.5 mm
2
Quiescent current
0 mA
Alarm load
Built-in 680 Ω and 470 Ω + option for external R.
Clean contact rating
0.1 A / 30 V DC
Working temp.
-10
℃
~ 55
℃
Storage temp.
-30
℃
~ 75
℃
Environment Humidity
≤ 95% RH (no condensation nor icing)
Red LED Indication
Steady on when in alarm.
Dimensions (LxWxH)
90×90×52 mm
IP rating
IP40
Weight
160 g