M-2100-1: JBE-2100 Manual Call Point data sheet V1.0
Jade Bird Fire Alarm Systems – JadeBird.eu.com 3 / 4 JBE-2100.DSH.EN.210128
Installation
Always observe local fire and electric installation regulations.
1.
Secure the base to the wall (surface or flush mounted).
2.
Connect the wiring to the base as per the following diagram:
Terminals
Connection
1 & 2
Signal loop L1, L2 (no
polarity)
7 & 8
(Optional) Normally open
clean contact switch
Max rating: 0.1 A, 30 V
3,4,5,6
Not connected
3.
Program an unused loop address (1 to 200) to the MCP head using the
JBE-AT1 tool.
4.
Insert the MCP face into its base and push firmly.
5.
The head can be secured to the base by fitting an optional self-tapping
screw (ST2.9x8) into its boss next to the reset keyhole.
6.
Register the MCP into the fire panel’s configuration.
7.
Test each MCP and wiring integrity after installation and periodically
according to local fire regulation.
Maintenance
Alarm test should be conducted regularly, recommending every 6 months.
Resetting an activated MCP
1.
Open the tab in the bottom of the MCP face.
2.
Insert the reset key.
3.
Rotate key counterclockwise until the frangible element returns to its
position.