M-P2L1-1 EN
Page 38
Release Date: November 15, 2019
Rev 01
Figure 19: Example Output Action
5.5.2.6.3 Reviewing the action
Once an action’s programming has been entered into the panel configuration, it can be reviewed in a
single screen with the coding below:
Input scenarios combination = Output programs triggered
Where the input scenarios are coded as S(Zone, alarm type, quantity) and the programmed outputs
programmed are coded as P(group number, delay, hold ).
OR aggregations of inputs are coded with the addition “+” sign.
AND aggregations of inputs are coded with the product “x” sign.
That is: Scenarios S(x,y,z) are considered to return “1” if they are met and “0” otherwise. All output groups
at the rightmost hand side of the “=” sign will be activated if the calculation of input functions returns “1”.
5.5.2.6.4 Actions involving SND and FR output groups: unlinking them from zones
In the panel’s default configuration, a single detector or MCP alarm in any zone will trigger the activation of
SND and FB output groups.
If you require a more sophisticated action for these output groups (such as coincidence detection), unlink
the activation of SND and FB output groups from the alarms in the affected zones. Otherwise, they will
always activate with the first alarm. See section 0 for instruction on how to unlink SND and FB output
groups from some or all zones in the fire panel.