IMPORTANT
If your test reveals insufficient electrical supply,
several solutions are possible; First, you could have
your electrical supply upgraded and provide a dedi-
cated, properly wired circuit with 20 AMP capability to
be used for the spa only. Second, you can install a
transformer which would boost your existing power
supply. We recommend that you seek the advice and
services of a qualified electrician who can determine
your particular electrical needs for installation of your
spa.
The Palio Portable Whirlpool Spa requires a 115
VAC 20 AMP capacity electrical supply. If the wiring of
the circuit in which your spa is connected is not sized
properly for 20 AMPs, or if the outlet used is too distant
from the main service panel, there may be a consider-
able voltage drop. Such a voltage drop would not only
cause the unit to malfunction, but it may also cause
permanent damage to the spa's electrical system.
Before operating you spa, therefore, we recommend
that you test the spa's intended electrical supply circuit
for sufficient voltage. To do this, you will need as AC
voltage meter and a small electrical appliance rated at
1200 (min.) - 1600 (max.) watts, such as a toaster or
small heater. With the appliance turned off, plug it into
the receptacle and take a voltage meter reading from the
adjacent receptacle. Next turn on the appliance to its
maximum setting and again measure the voltage as
before. The difference between the two voltage read-
ings must not be more than 5%. For example, if the
"OFF" voltage is 115, the "ON" voltage must not be
below 109. If there is a voltage drop of more than 5% or
if there is less than the 105 V minimum operating voltage
at the receptacle, the electrical supply is insufficient.
The minimum voltage must be maintained during spa
operation.
19
20 AMP RECEPTACLE
1200-1600 WATT (MAX.)
APPLIANCE