5
Option
Home
CANCEL
NEXT
ENTER
Use the
Up
and
Down
keys to set the
Home
number for the thermostat. The
Home
number
can be set from 01 to 32. Skip this option if no
other thermostats and modules are nearby.
After selecting the Zone and Home numbers for
the thermostat, the same address must be
programmed into the HVAC Module. Power up
the module and press the program button. The
module will accept a new address for thirty
seconds. The LED on the module will alternately
blink red and green while it is waiting for a new
address after which the LED will display whatever
state the thermostat is in.
10
Programming the
HVAC Module
Press Program Button
Option
CANCEL
NEXT
ENTER
Selecting Equipment Type
The HVAC Control Module can be set for
either gas/electric or heat pump operation.
Press the
NEXT
key to select
Option 04
and press the
Up
or
Down
key to select
00 = Gas/Electric or 01 = Heat Pump
operation.
11
Set To
Fan Operation
Press the
NEXT
key to select
Option 05
. The fan
can be set to 00 = Gas operation where the
equipment activates the HVAC system fan during
heating calls or to 01 = Electric operation where
the module activates the fan during heating calls.
In heat pumps and all cooling calls, the module
activates the fan (G) terminal.
12
The LCD display for
Option 03
is shown below.
Press the
ENTER
key to send the new address to
the HVAC module after pressing the module
program key and the LED starts to blink red and
green. When the module LED begins to flash
yellow, it will now only respond to the thermostat
with the same address. You will need to re-enter
the Installer Options menu to finish configuring the
thermostat.
Option
Zone
CANCEL
NEXT
ENTER
LED INDICATION
Flashing Green - No calls
Solid Yellow - First stage cooling
Flashing Yellow - Second stage cooling
Solid Red - First stage heating
Flashing Red - Second stage heating
Solid Green - Fan