TEST, CHECK AND STARTUP
1. Verify that all component wires have been connected to the proper terminals and are secure.
2. Apply 24 Volt power to the zone control panel.
3. Confirm that the ESP-400 POWER ON LED is on.
4. Put each zone thermostat in the OFF position.
5. With no calls taking place, the zone LEDs on the ESP-400 should be on confirming that all
dampers are in the open position.
6. Force a heating or cooling call from the zone one thermostat.
7. ZONE 1 LED on the ESP-400 should stay on and ZONE 2, 3 and 4 LEDs should go out.
8. When the equipment is energized, the PRESSURE ABOVE SETPOINT LED on the ESP-400 will
come on if there is an increase in system static pressure. The ESP-400 will begin to modulate
open all zone dampers that are in the closed position until the pressure increase is relieved.
9. Repeat step 6 for each zone thermostat in the system.
10. Once Test, Check and Startup is completed, place all zone thermostats in their normal mode of
operation.
ESP-400 SPECIFICATIONS:
Panel Dimensions:
Height:
8.0”
Width:
6.0”
Depth:
1.375”
PC Board Mounting:
Snap Track mounted to enclosure base
Operating Temperature Rating:
-40° F to 150° F
Operating Humidity:
5% to 90% RH non-condensing
Wiring:
18-gauge wire for all connections
TERMINAL DESIGNATIONS:
Panel Power
R
24Vac (Hot)
X
24Vac (Common)
Zone Panel Damper Inputs (4)
PC
Power Close
PO
Power Open
Damper Outputs (4)
PC
Power Close
C
Common
PO
Power Open
Pressure Sensor
PS1
PS2
4
06-1237-040616