TM-201A  multi-functional electronic thermometer, 

- 6 - 

MNU51203 

Example 

of using the F5 mode

 

The thermometer monitors charging of the hot water 

reservoir (e.g. in a circuit with a solid fuel boiler) 

The relay will be closed if the T1 temperature 

 

of the  heating water is higher than the T2 temperature  
in the reservoir by the required number of degrees 

 

(P5.1, switching difference). 

The relay will be opened if the difference of the T1 – T2 

temperatures decreases to the set value (P5.2, opening 
difference), or if the maximum set hot water temperature  
in the reservoir (P5.5) is achieved. 

Thus, the settings of the closing and opening difference 

can be used to control exceeding the heating water 
temperature. You can also set the minimum T1 operation 
temperature to avoid cooling the boiler during the power 
increase stage (P5.3). 

 

 

 

5. Warning 

indication 

A missing temperature sensor that is required by the selected function is indicated by flashing of 

LED 3 

and the respective 

LED 1 

or 

LED 2

. If only one sensor can be connected in a particular mode, it must always be connected to the 

T1

 terminal. 

In the F1 mode the warning indication is active on exceeding the limit values. The acoustic indication can be deactivated 
with the P1.3 parameter. If in the F1 mode no sensor is connected to the T2 terminals, the P1.4 parameter must be  
set to OFF. In the F2 – F5 modes lighting of LED 3 may indicate closing/opening of the relay (if indication of the relay status 
is activated by the respective parameter).  

6. Technical 

parameters 

 

TM-201A thermometer 

 

Supply voltage  

11 V to 17 V DC  

Standby consumption/maximum consumption  

20 mA/50 mA 

Measuring range  

-40 °C to 125 °C 

Temperature sensor type 

NTC 10 k

:

, B25/100 = 3455 K 

Operating temperature range 

-10 °C to +40 °C   

Seasonal space heating energy efficiency 

ڦ

S

 = 1 % (acc. Regulation (EU) No. 813/2013) 

Temperature control class 

I. (acc. Regulation (EU) No. 813/2013)  

OUT output 

switching contact, max. 1 A/250 V, resistance load 6 A, protection class II 

Acoustic/optical indication  

Siren/LED 

Ingress protection class 

IP 41 (in accordance with EN 60529) 

In conformity with  

EN 60730-1, EN 61000-6-1, EN 61000-6-3, EN 50581 

 

Recommended temperature sensor 

 

Type 

CP-201T Jablotron (NTC 10 k

:

, B25/100 = 3455 K) 

Measuring range  

-25 °C to 105 °C  

Sensor accuracy 

± 1% at 25 °C, ± 2 °C in the range of -25 °C to 105 °C 

Specifications 

CP-201T Manual (NW)       MNC52900 

 

JABLOTRON ALARMS a.s. hereby declares that the TM-201A is in a compliance with the relevant Union 
harmonisation legislation: Directives No: 2014/35/EU, 2014/30/EU, 2009/125/ES, 2011/65/EU. The original of the 
conformity assessment can be found at www.jablotron.com - Section Downloads. 
 

Note: Although this product does not contain any harmful materials we suggest you return the product  
to the dealer or directly to the producer after use

Reviews: